  • @andrewcadby
    @andrewcadby 6 місяців тому +3

    22:42 A circuit protected by a 30mA RCD has a max permitted Zs of 1667 ohms. There is no need to change the circuit breaker for B20. It is a long circuit, so theoretically could suffer from voltage drop, but real world that is highly unlikely to happen.
    23:40 exposed single insulation in a ceiling void would be a C3 IMO, I wouldn't be re-terminating these assuming CPCs are continuous.
    23:49 2.5mm on a 32A MCB feeding one single or twin socket is fine, perfectly compliant. It is the same as a spur from a ring final.

  • @grantmccallan8136
    @grantmccallan8136 4 місяці тому

    How do you know it’s a 100A supply? Out of curiosity

  • @stevedecoensel1975
    @stevedecoensel1975 6 місяців тому

    Do you need to down rate the ring to 20 because it’s protected by an RCD so the readings can be as high as 1667 ohms can’t they?

    • @finneyelectrical
      @finneyelectrical  6 місяців тому

      You have a point if everything is RCD protected. Just something I’ve always done is make the zs land within the max zs for the mcb. The ADS is on the RCD then rather than the mcb that’s all. Is it better to be over Ed by both? Let me know

  • @billybulmer7386
    @billybulmer7386 6 місяців тому +1

    How long would it normally take you to carry out an EICR on your own with a property that size?

    • @finneyelectrical
      @finneyelectrical  6 місяців тому +1

      I did quite a bit of filming in this but 3-4 hr

    • @stevedecoensel1975
      @stevedecoensel1975 6 місяців тому

      Edited..

    • @ef7480
      @ef7480 6 місяців тому +3

      Apparently about half an hour if you are one of these 'drive by' ''NICEIC registered' clowns appointed by estate agents....

    • @finneyelectrical
      @finneyelectrical  6 місяців тому +1

      @@ef7480 well they had some cheaper guy to come do it for like £100+vat 😂 other guy let them down of course

    • @ef7480
      @ef7480 6 місяців тому +1

      @@finneyelectrical - £100 'plus vat' for an EICR? What a load of clowns. Probably used a Rolson multimeter😆