How to configure CFC | Digsi-4

Поділитися
Вставка
  • Опубліковано 1 гру 2024

КОМЕНТАРІ •

  • @jvignerte
    @jvignerte 2 роки тому +3

    You are very kind to share this information, may life pay you back double. Best regards

  • @jatinkumarpatel2269
    @jatinkumarpatel2269 2 роки тому +1

    Great Sir, Explained quite nicely!

  • @ashishrajput8950
    @ashishrajput8950 7 місяців тому +1

    Sir, i need your help...Cfc not initialise..
    Below error come.
    (257:5)
    One or more objects or a type cannot be represented. Server's7jomcsx.dll'_S7J_ECPLAN_CT objects could not be loaded.
    Make sure the required software packages are installed.
    I was tryed digsi 4.93,94,95,96.
    Same error come on windows 10.

    • @baranitech
      @baranitech  7 місяців тому

      SOME FILE Could be clashed on Register, try to formatted os and then install digsi software thank you

  • @biswaljayanti665
    @biswaljayanti665 4 роки тому +1

    Very good job

  • @khaledeid2508
    @khaledeid2508 3 роки тому +1

    how I can send a command over IEC 61850 using logic ?!! what is the input for this block ??!!

    • @baranitech
      @baranitech  2 роки тому

      for IEC 61850 receiving can be done in I/O routing with selecting data sheet.

  • @shahidlatif2421
    @shahidlatif2421 4 роки тому +1

    Dear Sir thanks for sharing good Knowledge.
    Sir cfc chart not open on my laptop. How can i open cfc chat even cfc input and output Configured

    • @baranitech
      @baranitech  4 роки тому

      Any message coming

    • @shahidlatif2421
      @shahidlatif2421 4 роки тому +1

      @@baranitech sorry for late
      Sir when I click on cfc setting and click on cfc nothing happened. Even can't insert new cfc chat.

    • @baranitech
      @baranitech  4 роки тому

      @@shahidlatif2421 did you checked for other types of relay

    • @shahidlatif2421
      @shahidlatif2421 4 роки тому +1

      @@baranitech yes I checked but didn't work.

    • @baranitech
      @baranitech  4 роки тому

      @@shahidlatif2421 please try to reinstall software

  • @surya-pc7nx
    @surya-pc7nx 3 роки тому +1

    Please make timer functions like on delay and off delay timer usage in CFC functions.

  • @AdnanJayyousi
    @AdnanJayyousi Рік тому +1

    I cant see CFC in my list and also I am not able to add CFC chart, why ?

    • @baranitech
      @baranitech  Рік тому

      type of version you choose may be different. try to check with other MLF version of the relay. thank you

  • @tanmoyghorai4751
    @tanmoyghorai4751 Рік тому

    Can you please explain how to configure timer in CFC thanks in advance

  • @omarzedan1261
    @omarzedan1261 3 роки тому +1

    Hi please, how to enable or disable CFC in run time dynamically???

    • @baranitech
      @baranitech  3 роки тому +1

      i will check

    • @omarzedan1261
      @omarzedan1261 3 роки тому

      @@baranitech dear friend there is no way to disable run time dynamically in sipeotec 4 you can use the command (cancel command) to disable command not all the cfc chart. I appreciate your kind replay friend.

  • @noufi043
    @noufi043 3 роки тому +1

    Hi sir I need to make cfc logic for voltage healthy condition. That is if voltage is healthy the one of the BO should be high. Please guide me to make that

    • @baranitech
      @baranitech  3 роки тому

      Step-1 :Do configuration for MV type UL1E --L3E in Measurment function from masking IO to CFC Step2: IN CFC use Lower set point block it will be inside comparison . on that you can set vaule and configure for your voltage healthy condition. if you want i will make video for you ..

    • @noufi043
      @noufi043 3 роки тому +1

      @@baranitech ok thank you let me try.

    • @noufi043
      @noufi043 3 роки тому

      Sir can you make a video on it i need BO 7 high when voltage is healthy please send to WhatsApp +919562655940

    • @baranitech
      @baranitech  3 роки тому

      ua-cam.com/video/z5kZtvOBRXM/v-deo.html i made for you

    • @noufi043
      @noufi043 3 роки тому

      Thank you sir will you please give your contact number

  • @vipsingh908
    @vipsingh908 3 роки тому +1

    Pls make cfc for auto re close .. this protection not working ..some error in logic

  • @alanfigueiredo5233
    @alanfigueiredo5233 2 роки тому +1

    Please, can teacher or someone help me? I don´t know what means TNC, TCS, 86Opt. help me please!

    • @baranitech
      @baranitech  2 роки тому +1

      i will make video regarding this

    • @alanfigueiredo5233
      @alanfigueiredo5233 2 роки тому

      @@baranitech Thank you very much, i`m looking forward about that!

  • @hishamhussein4399
    @hishamhussein4399 3 роки тому

    Hi sir, after i click on compile button, its pop up a message "Process Completed with warnings". . after that download the program into siprotec, then Error led lights up. Is the warnings can trigger the Error led ?

    • @baranitech
      @baranitech  3 роки тому +1

      normal the warning will not make error on relay . but when you compile you should not get error on digsi . once compile go for run sequence. to min the warnings.

    • @hishamhussein4399
      @hishamhussein4399 3 роки тому

      @@baranitech ok noted with thanks sir.. 👍