31 year old Heat Pump Copeland scroll cut open & inspected.

Поділитися
Вставка
  • Опубліковано 14 жов 2024

КОМЕНТАРІ • 47

  • @edlauren9434
    @edlauren9434 4 дні тому +1

    Very good video! Very interesting! Slicing a compressor layer by layer.. Very informative!

  • @LarryTimmins
    @LarryTimmins Рік тому +3

    Outstanding video! Ive been in the hvac business for 35 years and have rarely seen such a knowledgeable autopsy of a compressor. 31 years is a good run

  • @languagejourney6906
    @languagejourney6906 Рік тому +1

    Awesome video first time i’ve den a video where someone shows that part of how the scroll Compressor lubricates makes a lot more sense seeing it then just explained

  • @elgkas9928
    @elgkas9928 Рік тому +3

    Great video. Very informative and interesting to see the internals.

  • @repairitdontwreckit4257
    @repairitdontwreckit4257 Рік тому +1

    Excellent video. Your explanation of how things we’re wearing was easy to understand. Overall based on the age it didn’t look to bad. Thanks.
    Roger

    • @love2hvac
      @love2hvac  Рік тому

      Thanks, yes inside things looked really great, decently had a lot of life left in it and all the wear was external, car on and overheat=low on charge.
      Bearing wear from floodback=low superheat, (airflow, over charge overfeeding metering device)
      Copper plating=improper dehydration=acid=eats copper away from the system.
      Imagine how long the compressors would last if:
      We installed them correctly,
      Maintained correctly,
      And did not have to change refrigerants.

    • @repairitdontwreckit4257
      @repairitdontwreckit4257 Рік тому

      No kidding. Seeing the interior components and the damage related to superheat, low oil and other issue creates takes the mystery out of the gauge readings and why they are so important. Thanks again. Roger

  • @StopTheBurn
    @StopTheBurn Рік тому +2

    This thing ran 31 years!? Great manufacturing I would say. I hope the new ones are built as well. 😅

    • @mikafoxx2717
      @mikafoxx2717 2 місяці тому +1

      And a good install! No water, no air, no oxidation, no leaks.

  • @philiph1234
    @philiph1234 10 місяців тому +1

    What’s your opinion about adding thermal protection to the compressor discharge line ? Thanks

  • @MikeB9771
    @MikeB9771 Рік тому +1

    As always , awesome video Ty

  • @Mikecianfrocco
    @Mikecianfrocco Рік тому +1

    Amazing video bro!!!!

  • @victor.mnoriega3586
    @victor.mnoriega3586 Рік тому +1

    I like the way teach thank you

  • @MinnesotaHvAc
    @MinnesotaHvAc Рік тому

    GREAT video!!! There is on thing I didn’t see why can’t I pull a vacuum at times through a scroll. I tap the top and it will drop to sub 500 micron and then back up to 1000 microns. Then on my third attempt we head a clunk in the compressor and boom 293 microns with a 20 minute decay to 498 microns. What is happening in 2023 compressors. I do have 2 pallets of failed warranty compressors sitting there. Maybe it time to grab the go pro. Maybe it time to think about some content on my old channel.

    • @love2hvac
      @love2hvac  Рік тому

      What brand of compressor was that?

  • @samersarah957
    @samersarah957 Рік тому +2

    Thank you for all what you to do Ty!
    If a big leak happened and lots of oil was lost what is the right way to measure and add it?🌷Thank you.

    • @love2hvac
      @love2hvac  Рік тому +1

      Good question, no easy way on a resi system, there is no oil sight glass like commercial. You can compare suction superheat to discharge superheat. If they get too far apart it's a good sign it's low. However the only way to really know is to drain and measure.

    • @Dicofol1
      @Dicofol1 Рік тому

      @@love2hvac Can you add a sight glass on Resi system ?

    • @love2hvac
      @love2hvac  Рік тому

      @@Dicofol1 for refrigerant yes, for oil no.

  • @deanmartin1966
    @deanmartin1966 Рік тому +1

    Ty your wife is going to be mad that you used her Pyrex measuring cup. Lol. Good video

    • @love2hvac
      @love2hvac  Рік тому

      Shhhhhhhhh 🤫 she does not know, and nobody should tell her!!!!

    • @michaelszczys8316
      @michaelszczys8316 Рік тому

      How do you they're not his?
      Pyrex cups aren't just for kitchens.

    • @deanmartin1966
      @deanmartin1966 Рік тому

      @@love2hvac lol

    • @deanmartin1966
      @deanmartin1966 Рік тому

      @@michaelszczys8316 true. Lol

  • @robertcounts5300
    @robertcounts5300 Рік тому +1

    I have never seen a 31 year old HP with the original compressor, seen a lot fail at 10 to 15 years. I have 35 years in the field running service.

    • @love2hvac
      @love2hvac  Рік тому +1

      We need to do better at installing,
      Proper dehydration methods,
      Proper suction piping,
      Proper airflow,
      Proper charging.
      Next comes proper servicing. The 15 minute vacuum, suction looks good, had anometers, and beer can charging doesn't cut it.
      A good service tech and maintenance can't overcome a bad install. Some installs even look good but without proper vacuum,. It will never see it's potential.
      Compressors do not die, they are murdered.

  • @haithamwajeeh
    @haithamwajeeh Рік тому

    This is very wonderful and an excellent explanation... We want a clarification and explanation about the suction line heat exchanger SLHE, Trane innovation in heat pump chiller.

    • @love2hvac
      @love2hvac  11 місяців тому

      The idea is to use the suction gas to sensibly cool the liquid refrigerant aka add subcooling, this reduces the amount of flash gas after the metering device.
      On the suction side, the warmer liquid passing on one side of the heat exchanger helps ensure all the liquid refrigerant is boiled to a vapor in the suction side of the heat exchanger before entering the compressor.

  • @DerSchrottBastler
    @DerSchrottBastler Рік тому

    it seems to me: back in the days, they could build things to last. how long modern compressors work? 10? 15? 20 years? under "optimal" conditions?
    a few questions: is the oil the original oil from 1992 or was it replaced, when yes, when it got replaced? im a little bit curiouse.

    • @love2hvac
      @love2hvac  Рік тому

      Original oil.
      Refrigerant oil does not wear out, it can get contaminated with improper vacuum or taking hoses in and off introducing moisture. It can get birt form overheating such as a leak, low suction pressure, high superheat, high suction gas temperature. The discharge line should never exceed 225.
      A car engine has massive heat, blow by from combustion, left. Over carbon from air and fuel. A Refrigeration compressor does not have any of that.
      Copeland still builds these scrolls the same way but they have added some protection such as a thermal operating disk, pressure relief valve, and anti reverse rotation valve.
      They are still made here in the USA in Sydney Ohio. They built and test them for 100% to be operating at least 20 years. Due to improper installation and maintenance is the reason for shorter life.
      There is nothing to wear out and fewer moving parts than a reciprocating compressor.
      The biggest issues today are improper installation, and leaking evaporator coils.

  • @patmcbride9853
    @patmcbride9853 Рік тому

    If only the SEER2 compressors would last that long.

    • @love2hvac
      @love2hvac  11 місяців тому +1

      No difference in the compressor of SEER1 vs 2. Seer to really just requires manufactures to use static pressure to simulate ductwork.

  • @8joh58
    @8joh58 11 місяців тому

    Hi I have always wondered if the Nitrogen flows through the compressor when brazing it in? Can u please answer the question it’s very important to me thanks

    • @love2hvac
      @love2hvac  11 місяців тому

      It won't flow through the compressor but it will greatly reduce the amount of oxygen and greatly reduce the oxidation effect.

    • @8joh58
      @8joh58 11 місяців тому

      Why it won’t? Because only 3psi? What about if pressurized the system? Does flow through compressor 🙏 please explain, u r very knowledgeable , I watch one of your video said it’s does flow through that’s why I am confusing thanks

    • @8joh58
      @8joh58 11 місяців тому

      Please explain thanks

    • @love2hvac
      @love2hvac  11 місяців тому

      @@8joh58 excuse the compressor will not allow anything to move through it without it operating. When a compressor shuts off, it holds high pressure on one side. The pressures won't equalize until it bleeds through the metering device.
      The compressor has check valves in place to prevent the high side from bleeding back and the low side cannot move the compressor and motor to get to the high side.

    • @8joh58
      @8joh58 11 місяців тому

      So which means nitrogen never flow through the compressor when brazing it in, even if u flow nitrogen pressurized the system with 300 psi-350psi? But when system empty out the refrigerant, there isn’t pressure inside the system, nitrogen still can’t flow through compressor? Please 🙏

  • @WallaceRoseVincent
    @WallaceRoseVincent 5 місяців тому +1

    Your wife is going to kill you if she finds out you poured refrigerate oil in the measuring cup.

  • @chrisscott1547
    @chrisscott1547 3 місяці тому +1

    Most people pronounce galling "golling" or "gaulling."