CONNECTING FACTORY IO WITH CODESYS MODBUS
Вставка
- Опубліковано 8 вер 2024
- Below are the variables I used when connecting Factory IO with CODESYS
//STATION INPUTS
I0 AT %IX0.0:BOOL; // START
I1 AT %IX0.1:BOOL; // STOP
I2 AT %IX0.2:BOOL; // POINT A
// STATION OUTPUTS
Q0 AT %QX0.0:BOOL; // CB1 FORWARD
_____________________________________________________________
NB: NO SPONSOR NO AFFILIATIONS
"It helped me a lot. Thank you very much."
The bit toggling like that is a good indication that you have a register enabled, check your driver configuration and make sure registers is set to 0. Is toggling because the register overrides the bit on each scan.
Great video I learned a lot. As for the flickering 'STOP' button problem, I found out just by switching the address to for example 'IX0.7' fix the problem. Don't really know the details, but sometimes it happened
Great sound.
many thanks, codesys on my pc scans but does not discover the Desktop?
Hello,could this simulation without hardware PLC Codesys?😀
is codesys v3 free?
its open source..free