Works in theory but not in practical case. Timer relay needs to be added in order to avoid generator receiving power from the mains. It can happen because contactors aren't perfect. They make a small time to switch state. Finally we have to figure out how to make the generator start/shuts automatically. I think best solution is to use a small plc with UPS
Don't you think we need a mechanical interlock between the two contactors to avoid electric Sparks at the event when utility power comes back while the gen.set is running. Just asking anyway...
When main power comes back then also load will run on generator....main power contactor will not latch again...you have to add one relay which latch on main power and use its NC contact in series with main contractor's NC to latch/unlatch generators contactor and one on delay timer which runs on main power and use its NO contact in series with generator contactors NC to latch/unlatch the main contactor again......then it will be automatic.(priority should be main power) and also have to think about how generator will start at the time of main power failure.
Menurut saya itu wiring masih salah, karena saat listrik padam kontaktor langsung membuka jalur genset tanpa menunggu jeda sedangkan genset masih kondisi start, alat listrik akan langsung short, karena tegangan dan frekuensi genset masih rendah.
hello. i need your help i really dont understand how is a connection being automatic. just look, take consideration at a time all the supply power ( main and generator) are ON. unfortunately the main power getting OFF. of course according to connection the generator power will continue to work. but when a main power returns the current will flow toward a NC of the generator contactor ,Which is by the time the NC of the generator becomes NO so it will not allow the current to flow direct to main contactor coil. hence in order to a main contactor to be ON the generator should be put OFF manual. so how is a system termed as automatic?. please help me may be i didnt understand
The problem is we cant see the contractor pinout names. But u did absolutely right. Do u know how figured out. By zooming you video to see the pinout names.
Can this be used for a Westinghouse 9500 generator and a 6000 watt pure sine inverter that has gen start wire ports to recharge our 24 volt 300 hr battery? In other words we are looking for away for when our battery gets run down the inverter kicks on the generator to charge the battery. Your facts please.
This is not a ATF switch. Ja sure when mains fails the C1 will unlatch and you start the generator then C2 will latch but when mains return it will stay on generator feed until you stop the generator. Add 2x timers to the circuit that handles the change over with a time delay to protect your installation from switching between primary and secondary feed.
This wont work! Look at Right Contactor, when the Main Power Supply returns, the Right Contactor is still energized thereby keeping the NC points in an Open State, preventing the Left Contactor from energizing. It will automatically switch from Mains to Generator, but it will not switch from Generator to Mains when the power returns. Adding a Timer with a 1 Second Delay will resolve this.
They are interlocked. If you want to see it. Just zoom the video. The connection is just like this from mains phase on main contractor coil A1 to generator contractor Nc then back to main line/phase. The same for generator. Black wire to coil A2 independently
@@gtechninja They are not mechanically interlocked. Yes they are electrically interlocked but to ensure there is no possible way the utility side supply could ever be connected to the generator supply this transfer must have a mechanical interlock that will not physically allow both to connect. www.google.ca/url?sa=i&url=https%3A%2F%2Fca-en.alliedelec.com%2Fproduct%2Fsiemens%2F3ra1954-2a%2F70269936%2F&psig=AOvVaw3zIp-BkRbYLnrei48vDQeo&ust=1597145369327000&source=images&cd=vfe&ved=0CAIQjRxqFwoTCMCejK3EkOsCFQAAAAAdAAAAABAD
Hi engineer I built a automatic change over switch using three contactor's using three phases of power to switch the power to one load but at some point the two contactor's become on what should be done to avoid the same
Very simple but the generator has to be on, and will take the load when the main line is cut. To be more automated it would need like a button on the generator that its contacts are passing though the auxiliary contact on the contractor, that way when it closes the auxiliary contact is like pressing the button “on” on the generator!
I understand pictorial diagram ...in pictorial diagram u connect the wires to contactor terminal but connecting which terminal NO or NC ? I drew schematic diagram and understood ...but many peoples may be confused, So please provide schematic diagram (control circuit and power circuit or ladder type) end of the video please???
Sor contractor ka pin out karte thoda to jayada achha samjh aata, and video ke sath agar explanation dete to jayada clear ho jata kyonki last me jo apne interchange karne ke liye connection kiya wo clear nahi hua ki kyu kiya aur kaise kiya.
Automatic star generatornya mana bos,,?ini cuman interlock saja supaya listrik PLN dan generator gak beradu,kalau kya gni mau jadi automatic changeover berati generator harus hidup terus..
ac supply and generator supply also on at the time which supply go to output this diagram is anyone supply cut at the time work but both supply on at the time contactor how to work
Sir, main supply input must always be attached at the top of a differential and magnetotermic devices, and the output at bottom. The same is for power contactors!!!! This is an electrical normative!!!!!! So you made a very very big Mistake. Sorry, but this is!!!!!!! To next!!!!!!
Mains attached on top as input!!! only if marked such,,, there are many RCD which can be wired top or bottom as long as A and N are wired as marked. For contactors it doesn't matter whether which way in or out.
Don't use this in US. Violates more than one section of the NATIONAL ELECTRIC CODE, and probably several State and Regional electrical Ordinances. Mainly it does not have Positive Break before Make circuit protection
Oscar Gomez not really, what’s going to start the generator, if it’s not running, there nothing monitoring the mains and generator voltages, there’s a phenomenon called hunting, where voltages are on the cusp of acceptable and unacceptable, this will cause the generator to kick in and out, there’s no manual override. As I stated it’s not a practical circuit.
Works in theory but not in practical case. Timer relay needs to be added in order to avoid generator receiving power from the mains. It can happen because contactors aren't perfect. They make a small time to switch state.
Finally we have to figure out how to make the generator start/shuts automatically. I think best solution is to use a small plc with UPS
Thank you so much for share your opinion
Don't you think we need a mechanical interlock between the two contactors to avoid electric Sparks at the event when utility power comes back while the gen.set is running.
Just asking anyway...
When main power comes back then also load will run on generator....main power contactor will not latch again...you have to add one relay which latch on main power and use its NC contact in series with main contractor's NC to latch/unlatch generators contactor and one on delay timer which runs on main power and use its NO contact in series with generator contactors NC to latch/unlatch the main contactor again......then it will be automatic.(priority should be main power) and also have to think about how generator will start at the time of main power failure.
ua-cam.com/channels/owxc6ikTiZqoIekSQGxjUQ.html
2 time relays should be installed in this system to prevent the phases from colliding.thank you.
you welcome
That Shure
Menurut saya itu wiring masih salah, karena saat listrik padam kontaktor langsung membuka jalur genset tanpa menunggu jeda sedangkan genset masih kondisi start, alat listrik akan langsung short, karena tegangan dan frekuensi genset masih rendah.
Which of software do you use for making this animations?
we are used animation
Thank you.
@@JrElectricSchool PowerPoint animation?
Great
There was a bad connection. Generator is not disconnected when the main energy returns. the generators continue to feed
If u do not use a time delay in between the changeover, the circuit breaker may often trip. My practical experience.
hello. i need your help i really dont understand how is a connection
being automatic. just look, take consideration at a time all the supply
power ( main and generator) are ON. unfortunately the main power getting
OFF. of course according to connection the generator power will
continue to work. but when a main power returns the current will flow
toward a NC of the generator contactor ,Which is by the time the NC of
the generator becomes NO so it will not allow the current to flow direct
to main contactor coil. hence in order to a main contactor to be ON the
generator should be put OFF manual. so how is a system termed as
automatic?. please help me may be i didnt understand
The problem is we cant see the contractor pinout names. But u did absolutely right. Do u know how figured out. By zooming you video to see the pinout names.
i will try to making this video zooming
Thank you
Can this be used for a Westinghouse 9500 generator and a 6000 watt pure sine inverter that has gen start wire ports to recharge our 24 volt 300 hr battery? In other words we are looking for away for when our battery gets run down the inverter kicks on the generator to charge the battery.
Your facts please.
Very nice
Thank you very much!
is it automatically turned on th generator if theres a power off?
Thank you for the clear explanation. I wish you success. Please, what is the name of the program that you are explaining and drawing on?
we are used animation
Der sir oldwiring bulding ku invertor ela add cheyali telapandi
This is not a ATF switch. Ja sure when mains fails the C1 will unlatch and you start the generator then C2 will latch but when mains return it will stay on generator feed until you stop the generator. Add 2x timers to the circuit that handles the change over with a time delay to protect your installation from switching between primary and secondary feed.
This wont work!
Look at Right Contactor, when the Main Power Supply returns, the Right Contactor is still energized thereby keeping
the NC points in an Open State, preventing the Left Contactor from energizing.
It will automatically switch from Mains to Generator, but it will not switch from Generator to Mains when the power returns.
Adding a Timer with a 1 Second Delay will resolve this.
I would recommend that the two contactors are mechanically interlocked as well.
Thanks for share your opinion
ua-cam.com/channels/owxc6ikTiZqoIekSQGxjUQ.html
ua-cam.com/channels/owxc6ikTiZqoIekSQGxjUQ.html
They are interlocked. If you want to see it. Just zoom the video. The connection is just like this from mains phase on main contractor coil A1 to generator contractor Nc then back to main line/phase. The same for generator. Black wire to coil A2 independently
@@gtechninja They are not mechanically interlocked. Yes they are electrically interlocked but to ensure there is no possible way the utility side supply could ever be connected to the generator supply this transfer must have a mechanical interlock that will not physically allow both to connect.
www.google.ca/url?sa=i&url=https%3A%2F%2Fca-en.alliedelec.com%2Fproduct%2Fsiemens%2F3ra1954-2a%2F70269936%2F&psig=AOvVaw3zIp-BkRbYLnrei48vDQeo&ust=1597145369327000&source=images&cd=vfe&ved=0CAIQjRxqFwoTCMCejK3EkOsCFQAAAAAdAAAAABAD
What are the electrical components are use in the diagram?
Samj to ai ha but app ko btana chahiye tha k NO point py lgai ha ya NC point py wire...
Na hi yeah app ny show krwaya MC ko zoom kr k...
Contactos auxiliares tienes que nombrarlos si es NO ,NC de cada contactor si es monofasico o trifasico
Thank you so much for share your opinion
Hi engineer I built a automatic change over switch using three contactor's using three phases of power to switch the power to one load but at some point the two contactor's become on what should be done to avoid the same
Very simple but the generator has to be on, and will take the load when the main line is cut. To be more automated it would need like a button on the generator that its contacts are passing though the auxiliary contact on the contractor, that way when it closes the auxiliary contact is like pressing the button “on” on the generator!
Hi is it possible to get 3kV DC on the substation if there is a loadsheeding, using this system?
Kaun se software se ye animation banate hai plz🙏 Help me
filmora wondershare,sony vegas pro,
adobe after effects,adobe premiere pro,
adobe photoshop,microsoft office.
Please provide your content no
Very good sir. But if u give us circuit. It will be better.
i will try
Thank you
Sir ji is trick se power supply aane pr generater automatic off or power supply jaane pr automatic on bhi ho jaega reply plzz
yes
That's what I like about Sketch software, taking minutes to explain something that would normally take seconds.
I understand pictorial diagram ...in pictorial diagram u connect the wires to contactor terminal but connecting which terminal NO or NC ?
I drew schematic diagram and understood ...but many peoples may be confused, So please provide schematic diagram (control circuit and power circuit or ladder type) end of the video please???
Thanks for share your opinion
i will try
Of course its a NC contact.
Its an electrical interlock protection. I will add a mechanical interlock too as additional protection.
Good explanation 👍
Thanks 🙂
Sir how you draw and how u get mcb on screen which software sir teach me sir
we are used animation
ua-cam.com/channels/owxc6ikTiZqoIekSQGxjUQ.html
Sor contractor ka pin out karte thoda to jayada achha samjh aata, and video ke sath agar explanation dete to jayada clear ho jata kyonki last me jo apne interchange karne ke liye connection kiya wo clear nahi hua ki kyu kiya aur kaise kiya.
please ape aschese video ko deke ya ape ko samag ajayge
Sir paano Po Yung 2pole na ats for generator,,,saan poba kinakabit Ang ats sa tabi Ng main breaker,or sa Tabi Ng generator,pa advice po sir
kon se software me animation video banate ho bhai
ham bhot sare software use karte he videos banane ke leya
In this the load doesnt connect to mains automaticaly after the power failure, it do only after stops the DG manually.
Thank you so much for share your opinion!
That true help me see it.. it's manual not auto since no any communication to the generator
What if my generator is on and there is utility light restore that means it will be powering by gen and change to mains supply and back to gen
Pls can you kindly be adding voice lessons to the diagrams to make it easy to understand
Thank you so much for share your opinion i will try
@@JrElectricSchool
Ok... Thank you
Enterlock Circuit . Nice M.contactor .
You are right
Thanks for watching
The contactor is 12v or 24v
this is beautiful
Sound is very good
Thank you
ua-cam.com/channels/owxc6ikTiZqoIekSQGxjUQ.html
Namshkar Sir
3 rooms, house, kitchen
Load MCB,
1 room fan, 2 tube light, 1 Bulb
2 room fan, 2 tube light, 1 Bulb, AC
3 room fan, 1 tube light, 1 Bulb
Kitchen fan, 2 tube light, 1 Bulb, freezer,
Single poleMCB Kitane ka lagaye 10 Amp 16 Amp kitane Amp ka MCB lagaye & 2 pole MCB, RCCB Amp lagaye es ka 1 video banaiye na Sir
ape 2 pole mcb lagaye 32amp or rccb32apme
or single pole mcb 10amp lagaye.
Thank you
@@JrElectricSchool Thanks you Sir...🙏🏻
Sir ap kis software pr ye vidio bnaty
animation
@@JrElectricSchool thanks sir
Bro me ek technician hu mera liya ye video helpful he,ager divice ka nam bata deteto bohot aacha hota,bro rlp diziyaga plz😊
ape kes divice ke bare me janna chate ho?
ua-cam.com/channels/owxc6ikTiZqoIekSQGxjUQ.html
Fine page
Good post
Thanks
Clear understand bro... this is income supply not come.. Generator ON OK... But incase income come not work ..manul off
Thanks for share your opinion
Dearsir pl explainthr diagram
In simple terms... automatic transfer switch.. primary as grid in. Customer load as common. Gen as back up
Thank you so much for share your opinion
But how it automatically works it looks like Manual.. How can we wire to work automatically.
i will try to make video automatically no off.
Thank you
Useless. Don't do like this! Must be use one relay for power incoming on/off sensing.
Thanks
Give the details how many ampers the contactor
60 Amp contactor
Automatic star generatornya mana bos,,?ini cuman interlock saja supaya listrik PLN dan generator gak beradu,kalau kya gni mau jadi automatic changeover berati generator harus hidup terus..
You could easily have labelled those points on the contactor's
Halo. Can you please show a video on doing outdoor lighting please
i will try to make video on your topic.
Thank you
ua-cam.com/channels/owxc6ikTiZqoIekSQGxjUQ.html
It seems that there's short circuit at the contacters as the AC is meeting DC
good video
Thank you very much
nice music but the drawing is way too slow.
Thank you
well done!!!
Thank you
ac supply and generator supply also on at the time which supply go to output
this diagram is anyone supply cut at the time work
but both supply on at the time contactor how to work
interlock
Thanks for watching
ua-cam.com/channels/owxc6ikTiZqoIekSQGxjUQ.html
ល្អgood
Thank you
Poltry 30 kv genrtor kitne amp ka comtacter lena chahiye
Name it for every instrument and say detail about each part
Thanks for your opinion
i will try
Contactor
Dp mcb
ua-cam.com/channels/owxc6ikTiZqoIekSQGxjUQ.html
बिना नाम दिए कया चित्र बनाया, कुछ तो नाम हो आदमी कया समझेगा
ua-cam.com/channels/owxc6ikTiZqoIekSQGxjUQ.html
Totally redic...where's the mechanical interlock?? And you're going to run that portable generator 24/7/365??
Useless,give the full details of all components and operation while giving connections
Poor diagram. What are those things? A relay? Magnetic contactors? I wii be the one to teach you.. i k know how..
Thanks you so much for share your opinion
Sir, main supply input must always be attached at the top of a differential and magnetotermic devices, and the output at bottom.
The same is for power contactors!!!!
This is an electrical normative!!!!!! So you made a very very big Mistake.
Sorry, but this is!!!!!!! To next!!!!!!
Thank you so much for share your opinion
Mains attached on top as input!!! only if marked such,,, there are many RCD which can be wired top or bottom as long as A and N are wired as marked. For contactors it doesn't matter whether which way in or out.
Super... 👍
Thank you so much
@@JrElectricSchool Subscribe my akun @Suhardi Madhani,.. Thanks... 🙏
Yaa 3 phase me kam karega
There is not automatic. Is only a electric interlock. How start and stop the generator?
manual
Muy interesante gracias
great one, keep it up
Thank you so much
Wow fantastic 💝😌☺️😊
Thank you so much
nice
Thanks
What does the switch do
Super g
Thanks
Need equipment list
Sir keep up, and I like pls sir how can I get diagram text book.
sorry
Please show how it's work
Super
Thanks
Good bro
Thanks
Bravo!!! Thanks👍
my pleasure!
Good job. عمل جيد
Thank you! Cheers!
It’s the song 🎵 for me 🤪
Молодец яхши чикбди
sorry i am not understand your language
please tell me Bangla,Hindi,English
Thank you.
Very nice 👌👍😊
Thanks a lot 😊
Not proper explain, this video make confusion. It's ready made device for automatic on off genrator. You should provide live demo for this.
i will try
Thank you
good Video but no nc problem
Thank you so much for share your opinion
Vedio
Tooop
Thank for watching this video
गूंगे हो ऐसी चीज का क्या मतलब जिसका कोई विवरण न हो.
Why don't you use just a relay
even if it is not used
Thanks for watching
Generator still not Automatic Running if City Electrical off.
yes
fast forward till the end. so borring. but usefull
Thank you
Is not usefull please don't try it at home ur generator will blast
Bhai ji isme timer or main aane par dg cat realy kaha hai
This sistem is not automatic.
Only you do a connection to change the circuit with the generator.
Bạn lắp đi dây vào CB ngược à?
sorry i am not understand your language
please tell me Bangla,Hindi,English.
Thank you.
Don't use this in US. Violates more than one section of the NATIONAL ELECTRIC CODE, and probably several State and Regional electrical Ordinances. Mainly it does not have Positive Break before Make circuit protection
I wouldn’t recommend this circuit. It’s not a practical circuit that any electrical engineer would endorse.
Thanks you so much for share your opinion
With this circuit the generator turns on automatically.?
Oscar Gomez not really, what’s going to start the generator, if it’s not running, there nothing monitoring the mains and generator voltages, there’s a phenomenon called hunting, where voltages are on the cusp of acceptable and unacceptable, this will cause the generator to kick in and out, there’s no manual override. As I stated it’s not a practical circuit.
Hang up the pliars my man you ment to draw
Waaaw thenk youuuuuuu
Thank you ! keep watching
the connection is nt usefull. waste
my ideal usa manuaL OPERATE ;; DOUBLE THROW DOUBLE POLE ;;; EASY TRANSFER FRM FRIVATE TO GENERATOR
Thank you so much for share your opinion