Neutral Grounding Resistor Sizing and application|Restricted Earth Fault Current

Поділитися
Вставка
  • Опубліковано 28 лис 2024

КОМЕНТАРІ • 163

  • @timm8311
    @timm8311 4 роки тому +4

    I often find I have trouble understanding India accents, but your drawings and explanations were great. Plus your English was good. Thank you for taking the time for this lesson and sharing your knowledge. Very Good.

  • @bhaskarmazumder7780
    @bhaskarmazumder7780 2 роки тому

    খুব সুন্দর ও সহজ করে বোঝানোর জন্য অনন্ত ধন্যবাদ আপনাকে💕 স্যার💕🙏💕

  • @Doti_231
    @Doti_231 2 роки тому

    great explanation
    may this channel will be more great

  • @mukeshgt
    @mukeshgt 4 роки тому +4

    Very nicely explained. Thanks.
    Can you please put some light on power rating (Kw) of the NGR to be specified ?
    As the withstand current is limited to 10 sec. only, then the continuous power rating of the resistor can be quite less than the peak power rating.
    Any idea about it sir. ?

  • @MM-fg3ep
    @MM-fg3ep 3 роки тому

    explained in a very simple way... amazing work!

  • @rajibadhya8653
    @rajibadhya8653 4 роки тому

    Very much interesting....awasome

  • @shubhchaudhari487
    @shubhchaudhari487 4 роки тому +1

    Thank u Sir... But this point explained on 2:12 always bothers me ...
    Let say an earth fault occured in system at 100 meter away from transformer... Then how it can be flows back to transformer neutral via EARTH!!
    I mean earth is a such good conductor???
    Please guide me on this?

  • @thinkseeeatthroughvickus4555
    @thinkseeeatthroughvickus4555 4 роки тому +3

    Sir, what is the criteria to select 400A as upper limit for neutral current.

  • @vsrgadepalli9851
    @vsrgadepalli9851 2 роки тому +1

    Whts the basis to restrict e/f to 400amps.
    Can u give any reference of IS

  • @syedwaseemuddin2995
    @syedwaseemuddin2995 4 роки тому +1

    Thanks for the video i was searching for Impedance grounded system i found this and i think its same.
    One question. For commercial facilities and residential areas, grounding impedance
    shall be 1000 A, 10 Second Resistor. I found this in one standard book.

  • @papaiarunava
    @papaiarunava 2 роки тому

    Thanks for this wonderful video. What is the guiding factor of selecting 400A or 600A.

  • @Nivupedia
    @Nivupedia 4 роки тому

    Very nice explained 👍. Put this information over your blogs as well.

  • @sajidmahmood7351
    @sajidmahmood7351 2 роки тому

    Awsome video in details...Thanks

  • @rukmagoud
    @rukmagoud 2 роки тому

    Sir if the fault occurs phase to phase and ground then phase to phase voltage shall be taken for grounding resistance calculation. In your case u have taken phase voltage because u have considered phase to earth fault. So when it is ph-ph and ground fault. There is line voltage that is driving current Sir please clarify?

  • @alltech9978
    @alltech9978 3 роки тому

    NGR is in series or parallel ?
    In NGR Resistor is connected in series or parallel ?

  • @sanjeevrana8317
    @sanjeevrana8317 5 років тому +1

    Impeccably Excellent. Make video on 66kV, 132kV, 220kV, 400kV, 765kV ground resistance calculation. Also on HVDC Earthing fault calculation. Thanks

    • @lalitkumar237
      @lalitkumar237 4 роки тому

      Make video on 66kV & above voltage level sir

  • @surendrakverma555
    @surendrakverma555 4 роки тому

    Very good lecture Sir. Thanks

  • @victormahadev7158
    @victormahadev7158 2 роки тому

    Sir please clarify me earth fault current is grounded , afterthat why fault current is feeding to Source via neutral ?

  • @srijansingh9834
    @srijansingh9834 Рік тому

    Sir how to determine rated Current for NGR resistance value calculation

  • @hartocahyono2428
    @hartocahyono2428 Рік тому

    Verry good, easy to understand.
    Please explain why you change 11kv to 11.5kv? I'm not clear to understand..thank you.

    • @anandtata4484
      @anandtata4484 2 місяці тому

      Load voltage is 11kV , no load voltage is 11.5kV , because during faults in line to ground , loads shall disconnected, in that case voltage Come back to it original state ,11.5kV , 11kV is load voltage due to voltage drop

  • @muhammadabduljaleel1811
    @muhammadabduljaleel1811 Рік тому

    Excellent explanation

  • @arumugamkaruppiah9214
    @arumugamkaruppiah9214 4 роки тому

    Thank you very for explaining for sizing the NGR for various capacity of Trs.

    • @murugans8006
      @murugans8006 3 роки тому

      Where is the power (Watts) capcity of resistor

  • @rockysubu8384
    @rockysubu8384 3 роки тому

    Very nicely explained.

  • @mangeshbhosale4767
    @mangeshbhosale4767 Рік тому

    Very nicely explained

  • @souravmitra5656
    @souravmitra5656 3 роки тому

    Very good information we got. Thanks to ETIP team. Please make a video on substation SAS and control. And scada architecture. Please

  • @Raselkhanvlogs
    @Raselkhanvlogs 9 місяців тому

    By using Earthing Transformer, what will be the connection diagram

  • @debarpanchanda9038
    @debarpanchanda9038 3 роки тому

    Thanks, sir for the video. Most clearly explained video about NGR on youtube. Also sir, requesting you to make that video you have mentioned that how to handle the fault current of the above 33KV Wye connected Transformer through its grounding.
    Thanks in advance sir...

  • @thinkseeeatthroughvickus4555
    @thinkseeeatthroughvickus4555 4 роки тому

    What is the situation NET (nutral earthing Transformer ) is used. Can you please advice its calculation?

  • @mitulkulshrestha8067
    @mitulkulshrestha8067 4 роки тому

    Very good explanation

  • @sumangorai2031
    @sumangorai2031 6 місяців тому

    How to calculate generator or transformer earth fault current which one we are limiting through NGR.

  • @2507jas
    @2507jas 2 роки тому

    Can you please make video for Neutral current transformer.

  • @dkverma2330
    @dkverma2330 4 роки тому

    Nicely explained. What IS is applicable for such calculations?

  • @islambenyettou2008
    @islambenyettou2008 5 років тому

    thank you so much sir for your explanation ... it's so useful and helpful

  • @yokeleetan8525
    @yokeleetan8525 3 роки тому

    how come when you draw the vphase it looks like line voltage since it is between phase and neutral? sorry to ask.

  • @anirbanbanerjee4366
    @anirbanbanerjee4366 3 роки тому +1

    Sir i want to request u to plz tell how to decide fault current for transformer of 15/20 MVA and ratting in 110kv /33 kv ..

    • @electricaltechnologyandind5335
      @electricaltechnologyandind5335  3 роки тому

      Check my fault current calculation video. Method is same. But for suc high voltage there shall not be any significant motor contribution.

  • @flyhighwithyourdreams.2132
    @flyhighwithyourdreams.2132 5 років тому

    Sir why we taken 400 A limit current for 11.5KV,6.6KV,3.3KV. Those are different voltages.So why we taken same 400A limit current?

  • @asithajayarathna130
    @asithajayarathna130 2 роки тому

    Great video

  • @muthuvelganesh6554
    @muthuvelganesh6554 4 роки тому

    What it is rated for 10 sec.?
    Is it necessary to specify power rating of NGR based on the fault current controlling through NGR during fault?

    • @garylogan5833
      @garylogan5833 3 роки тому

      Both NER and earthing transformer neutral need to be rated at earth fault current. 10 seconds to account for protection auto reclosing, can be longer if required. NER resistance calculated from earth fault current level, not power. So main aspects are resistance, current and current withstand duration

  • @inshort5707
    @inshort5707 2 роки тому

    Very nice 👍🏻👌

  • @deltawye297
    @deltawye297 5 місяців тому

    amazing video.

  • @xintao0521
    @xintao0521 4 роки тому

    Good stuff!! 👍👍

  • @sudhirskamble
    @sudhirskamble 3 роки тому

    Thanks sir and please make video on zigzag transformer of two winding transformer

  • @sureshpadhy2243
    @sureshpadhy2243 3 роки тому

    Excellent explanation, but how you have selected 400 A and 10s for opposing EF current

  • @varshithbhargav8075
    @varshithbhargav8075 5 років тому

    its excellent but one question about earth fault current consideration 400A. can we take it as standard value??
    what is the basis for this consideration of 400A e/f current? please explain

    • @electricaltechnologyandind5335
      @electricaltechnologyandind5335  5 років тому

      i haven't found any basis, may be based on experience it has been standardized. more over it can be varied but you have to design the transformer core withstand capability accordingly. suppose your transformer core can withstand earth fault current of 200A, then your Earth Fault current should be restricted to 200A or less. you have to specify the earth fault withstand current of transformer according to the earth fault current

  • @douglasmsavino
    @douglasmsavino 4 роки тому

    Would these calculations also apply for a neutral grounding reactor (coil) ?

  • @shashankkumar7770
    @shashankkumar7770 4 роки тому +1

    Sir we have taken 100amp fault current for 15 MVA trafo,6.34%impedance.ngr-63.5 ohm.

  • @pnmendoza18
    @pnmendoza18 4 роки тому

    Hi, What is/are the exception/s for not installing NGR in 11,3.3 or 6.6 kv? Kindly share some info on this because I have a 5MVA x'mer with 3.3 kV without NGR and the computed L-G fault is lesser than the 3Phse fault... Is that enough reason or there few more reasons technically?

    • @electricaltechnologyandind5335
      @electricaltechnologyandind5335  4 роки тому

      All thr above voltage levels are generally provided with ngr. 3.3kv with solid earth is a new type of system for me.... Is the transformer star star??? Or delta star???? What is the upstream configuration???

  • @rajeshsutar683
    @rajeshsutar683 8 місяців тому

    explain very nice

  • @pavankumar-ey3bw
    @pavankumar-ey3bw 2 роки тому

    Why to taken 400A.....what is the reason

  • @hartocahyono2428
    @hartocahyono2428 3 роки тому

    Please make video about Vector group of transformer as simple as exolain your this video👍

  • @BL-wu9jw
    @BL-wu9jw 3 роки тому

    Is there an international standard to derive the 400A used as EF current limit?

    • @garylogan5833
      @garylogan5833 3 роки тому

      In UK, NER is selected to match the nominal current value of the power transformer winding. I suppose you want a duty that is enough to trip protection, but doesn't cause too much stress on equipment.

  • @flyhighwithyourdreams.2132
    @flyhighwithyourdreams.2132 5 років тому

    Sir why limit the neutral current for high voltage. If any problem for winding like damaged for circulating current?

    • @electricaltechnologyandind5335
      @electricaltechnologyandind5335  5 років тому +2

      for high voltage earth fault current will be higher. also there shall be possibilities of ground potential rise and life threat due to step and touch voltage. so for high voltage ngr is used. but for voltage of and above 66kv again solid earthing is done, and the potential rise hazard is taken care off by suitable earthing design

    • @flyhighwithyourdreams.2132
      @flyhighwithyourdreams.2132 5 років тому

      Thanks

  • @prakashs538
    @prakashs538 2 роки тому

    Time 10 sec means what and how is calculated

  • @krishnapandey9220
    @krishnapandey9220 4 роки тому

    very good.

  • @TheMahali
    @TheMahali 5 років тому +1

    Can u tell me the purpose of loading resistor in NGTR and explain video about

    • @electricaltechnologyandind5335
      @electricaltechnologyandind5335  5 років тому +1

      Neutral of generator of large power plant is earthed through a single phase earthing Transformer. Primary is connected between the generator neutral and load resistance is connected across the secondary. So it will make a transformer with secondary loaded.
      I shall make video on that

    • @ak3612
      @ak3612 5 років тому

      @@electricaltechnologyandind5335 sir please make video on NGTR which is generally used in large generating station

  • @thinkseeeatthroughvickus4555
    @thinkseeeatthroughvickus4555 4 роки тому

    Please do a video on
    1) NGR with transformer. (to reduce size of NGR)
    2)

  • @inshort5707
    @inshort5707 2 роки тому

    How do you restrict it to only for 10 sec.

  • @mahesstar
    @mahesstar 5 років тому

    explanation good 👍

  • @harichinta5096
    @harichinta5096 4 роки тому

    In our Ngr fault current is 1400 A @ 6.6 KV system voltage. Can you please make a video on t/f S.C caliculation

  • @Pappurocks786
    @Pappurocks786 5 років тому

    Excellent .kindly make a video on earthing transformer stressing upon zero ph seq imedence and sizing

  • @ajaykarne5648
    @ajaykarne5648 4 роки тому

    Why ngr not provided at 220kv transformer, please make video on that

    • @electricaltechnologyandind5335
      @electricaltechnologyandind5335  4 роки тому

      NGR size will be bulky as the insulation will be larger. Also that will have huge cost. Also resistance size will be huge..... Okay i will make video on that.......

  • @vikcy2010
    @vikcy2010 5 років тому

    Thanks for such information. can you give information about NGR supplier? I need it urgently.

  • @pravakardash1967
    @pravakardash1967 2 роки тому +1

    Earth fault current is Max 50A as per CEA 2010

  • @practical3341
    @practical3341 4 роки тому

    What will happen, if we select NGR for rated line voltage,, remaining condition same as explained by you?

    • @electricaltechnologyandind5335
      @electricaltechnologyandind5335  4 роки тому

      Unable to understand... Give example

    • @practical3341
      @practical3341 4 роки тому

      @@electricaltechnologyandind5335 Here at our Power plant site,, about 7-8 times NGR failed. NGR rated voltage given is 12 KV. and transformer is of 21/11 KV

    • @practical3341
      @practical3341 4 роки тому

      @@electricaltechnologyandind5335 Here,, i am not able to attach my NGR rating. my whatsapp no is 9109174024. can send on it,, if you are ok with it.

    • @electricaltechnologyandind5335
      @electricaltechnologyandind5335  4 роки тому

      Email me at
      electricaltechnology04@gmail.com

    • @electricaltechnologyandind5335
      @electricaltechnologyandind5335  4 роки тому

      Send me the details

  • @sandranagamuneiah8142
    @sandranagamuneiah8142 2 роки тому

    Thanks 👍

  • @rbentertainment2605
    @rbentertainment2605 3 роки тому

    How to find out the earth fault current of the transformer

  • @CartoonwonderlandEdu
    @CartoonwonderlandEdu 5 років тому

    Outstanding vedio

  • @خالدالشلبي-د4س
    @خالدالشلبي-د4س 5 років тому

    Thank you very much

  • @rutu8046
    @rutu8046 4 роки тому

    Sir give explain abought 11kv alternator ngr

  • @enriqueh8847
    @enriqueh8847 5 років тому

    Hello, first of all thanks for your training. I have seen that when you have done calculation, you have not used 10 sec so when or where is 10 sec used? Thanks

    • @electricaltechnologyandind5335
      @electricaltechnologyandind5335  5 років тому +1

      10 SEC IS THE WITHSTAND TIME OF THE FAULT CURRENT. THE NGR IS CAPABLE TO WITH STAND 400 A FAULT CURRENT FOR 10 SEC.

    • @enriqueh8847
      @enriqueh8847 5 років тому

      @@electricaltechnologyandind5335 Okay, thank you a lots

    • @cundaan
      @cundaan 3 роки тому

      @@electricaltechnologyandind5335 how can we vary withstand time & it's effect on NGR value

    • @electricaltechnologyandind5335
      @electricaltechnologyandind5335  3 роки тому

      Indian standard specifies 5 sec, 10 sec rating for NGR. So those are followed. But actual earth fault get cleared much earlier i.e. 0.5 sec at max

  • @melinbalan3866
    @melinbalan3866 5 років тому

    How this general current of 400A is defined?

    • @FAHADKHAN-fu4yk
      @FAHADKHAN-fu4yk 5 років тому +1

      It is not necessary. It depend on power of transformer,and generator.
      Example:
      Power of generator = 3.75MVA
      Voltage line to line = 13.8kV
      Then full load current= 3.75* 1000000/1.732* 13.8
      = 156.9
      We will limit earth fault current to be approximately 30 to 35% of full load current.
      Then earth fault current = 156.9*0.32=50 amp
      Now ohmic resistance which limit the earth fault current will be
      R = voltage / earth fault current
      R= 13.8* 1000/ 1.732* 50
      R= 160 Ohm.

  • @loveswinhate
    @loveswinhate 5 років тому

    Why no need of NGR for 11kv/433v transformer

  • @kanalistanbul310
    @kanalistanbul310 3 роки тому

    appreciate! good effort.

  • @bhadouria2011
    @bhadouria2011 4 роки тому

    why we use 100 Amp or 400 Amp NGR only

  • @rkthemgil
    @rkthemgil 4 роки тому

    In which standard If is noted as 400A

    • @electricaltechnologyandind5335
      @electricaltechnologyandind5335  4 роки тому

      No standard. It is common industrial value taken l. However i have seen 200A, 800A also.
      But for mines area HT earth fault is restricted at 50 A and LT earth fault is restricted at 750 mA. That can be found in CEA guidelines also in IE rules

    • @AMaz-zx9sj
      @AMaz-zx9sj 3 роки тому

      In IEEE 142, page 13, it stated: "Low resistance grounding is designed to limit ground fault current to a range between 100A and 1000A, with 400A being typical"

  • @hzbajlanihzbajlani6699
    @hzbajlanihzbajlani6699 2 роки тому

    What about 6 MVA 11 kV/ 0.4 KV...also the Fault current is high

  • @rohitsinghshrinet3559
    @rohitsinghshrinet3559 4 роки тому

    How 400A came? What will be this value for 415V NGR?

    • @rohitsinghshrinet3559
      @rohitsinghshrinet3559 4 роки тому

      I need to restrict fault current in LT side as the fault current can damage the cables as cable fault level is very less (28kA for 1 sec for 300sq mm) wrt Transformer fault level (70kA).

    • @electricaltechnologyandind5335
      @electricaltechnologyandind5335  4 роки тому

      Why your transformer fault current is so High? There is mistake. Lt trafo fault current should not go beyond 50 kA for trafo upto 2.5 mva and 65 kA for 3.15 MVA.
      Your cable is suitable for 28 ka for 1 sec. But you don't need to let the cable handle fault for that time. Watch my cable sizing video.
      You can restrict earth fault current, but phase fault you can't restrict. So select higher cable size.
      Watch my cable sizing calculation video......

    • @rohitsinghshrinet3559
      @rohitsinghshrinet3559 4 роки тому

      Transformer size is 3 MVA & %Z is 6%. This is the reason for very high current in 415V side.
      Feeders are low capacity, I.g. 500A, so I can't choose 400sq mm cable size.
      Only thing is that I have to control these things by tripping time.
      Correct me if I am wrong

    • @rohitsinghshrinet3559
      @rohitsinghshrinet3559 4 роки тому

      And I think due to Personal safety we dont use NGR at 415V side.

    • @electricaltechnologyandind5335
      @electricaltechnologyandind5335  4 роки тому

      Yes isolate the fault with short time.... Wrong transformer selection is made.....

  • @janardhanjagtap8275
    @janardhanjagtap8275 4 роки тому

    What will be temperature ?

  • @spyrosn1950
    @spyrosn1950 5 років тому

    Say something about the power of the resistance in every case. P=I^2* R

    • @electricaltechnologyandind5335
      @electricaltechnologyandind5335  5 років тому

      Current through ngr will be flown only during earth fault... So loss is irrelevant for that case.

    • @spyrosn1950
      @spyrosn1950 5 років тому

      @@electricaltechnologyandind5335 Yes, but since the resistance is calculated to withstand a load of 400A for 10s, I think it must be a high power one. e.g. for 16.6 ohms /11.5KV, it must be 2650 KW resistance.

    • @csgupta7017
      @csgupta7017 4 роки тому

      @@spyrosn1950
      What will be Wattage of resistance. Will it be. I*I*R ??

  • @tamilselvan8784
    @tamilselvan8784 5 років тому

    Thank u sir

  • @prasunchatterjee4432
    @prasunchatterjee4432 5 років тому

    Sir where NCT is connected?? And why its require?

    • @electricaltechnologyandind5335
      @electricaltechnologyandind5335  5 років тому +1

      There are two possibilities
      1. NCT connected at transformer neutral bushing
      2. NCT connected to NGR.
      Both are used in industry. Transformer having solidly earthed neutral nct shall be connected at bushing only.
      Earth fault current returns through the neutral. So nct is required to detect earth fault current. I will make a vdo in nct selection. So please stay tuned.

    • @prasunchatterjee4432
      @prasunchatterjee4432 5 років тому

      @@electricaltechnologyandind5335 sir thank you for your support

  • @adityatiwari8044
    @adityatiwari8044 4 роки тому

    We have a NGR of 66.39 ohms at 11.6 KV

  • @enestunc9983
    @enestunc9983 5 років тому

    thanks

  • @taritbanerjee9276
    @taritbanerjee9276 3 роки тому

    while calculating the value of NGR, you have not considered the X1, X2 & X0 of transformer, please check

    • @electricaltechnologyandind5335
      @electricaltechnologyandind5335  3 роки тому

      This is a simplistic approach often considered in industry. Yes there is a method with other sequence impedance. But the difference will be absolutely negligible because the ngr resistance is very high compared to the transformer and also it will 3 times while considered in the zero sequence network. So both will give you same result.

  • @taufiquebaig1
    @taufiquebaig1 5 років тому

    Ngr is connected in HT generator.... Kindly check

  • @anoopkhan2268
    @anoopkhan2268 Рік тому

  • @khan_tanzeem0521
    @khan_tanzeem0521 3 роки тому

    👏🏼

  • @VinayKumar-py1iz
    @VinayKumar-py1iz 4 роки тому

    400 A is not common earth fault current for all voltage level 33,11,6.6,3.3 kv
    Please clear that
    Here same voltage level have two type ngr
    1. 9.90 ohm
    2. 18 ohm

  • @atharvpandey9164
    @atharvpandey9164 11 місяців тому

    Why 400A not 100 A

  • @shaikkhaja2821
    @shaikkhaja2821 5 років тому

    Sir can u check your calculations

    • @electricaltechnologyandind5335
      @electricaltechnologyandind5335  5 років тому

      Please tell me in detail

    • @shaikkhaja2821
      @shaikkhaja2821 5 років тому

      Sir equation is showing 11.5*1000/1.732*400 k but when u calculate 11.5*1000/1.732/400 after that only value will be come so please check that equation in video.

    • @electricaltechnologyandind5335
      @electricaltechnologyandind5335  5 років тому

      11.5 *1000/(1.732*400) or 11.5*1000/1.732/400 ohm, may be i have missed a bracket. Simple ohm's law, for 11.5 kv line to line voltage the phase voltage is 11.5*1000/1.732, dividing this by 400A you will get the ohmic value

  • @csgupta7017
    @csgupta7017 4 роки тому

    Where 10 sec time is in calculation.

    • @electricaltechnologyandind5335
      @electricaltechnologyandind5335  4 роки тому

      10 sec is not there for ohm calculation. But when you select the cross section of the NGR conductor then the 10 second factor will come.

    • @ajinkyakhandare190
      @ajinkyakhandare190 4 роки тому

      @@electricaltechnologyandind5335 can you please explain in detail about this 10 sec.

    • @nishananda9838
      @nishananda9838 4 роки тому

      @@ajinkyakhandare190 Earlier NER design it is considered as 30 sec on liquid resitors but now a days NER design for 10 sec chosen to allow occurence of multiple events.

  • @gulrays73
    @gulrays73 4 роки тому

    Not complete command on subject

  • @leewong4329
    @leewong4329 4 роки тому

    I cant understand

  • @mitubarik3361
    @mitubarik3361 3 роки тому

    Hindi mein hota to achha hota