Trip circuit supervision relay function | TCS

Поділитися
Вставка
  • Опубліковано 21 жов 2024

КОМЕНТАРІ • 83

  • @somanathanraju847
    @somanathanraju847 3 роки тому +1

    You explanation is very simple and knowledgeable. Any body a bit electrical knowledge can learn.

  • @JoelLopez-mc3zl
    @JoelLopez-mc3zl Рік тому

    Thank you Sir for sharing great additional knowledge for me being working in the Oil Gas Refinery. God bless you more

  • @umerali1956
    @umerali1956 3 роки тому +1

    Thanks a lot. One of the best videos for Electrical Engineers.

  • @sra1649
    @sra1649 3 роки тому +3

    Dear Brother, thanks for making such a useful videos. If one has little bit experience can also be able to gain knowledge from you. In running plants or unit went for shutdown every one can't get access to protection system. In this channel you are sharing your knowledge and experience , thank once again for your efforts. Some of your subscribers may discourage due to lack of their experience in the relevant field/ language problem , pl don't bother.
    We are enjoying your videos, pl go ahead.

  • @switchgearguru
    @switchgearguru 9 місяців тому +1

    very well explained....to the point...

  • @petarsimic2303
    @petarsimic2303 5 років тому +5

    Excellent explanation!! Can we get more videos about configuring and parameterizing relays?

  • @kurapatianwesh9114
    @kurapatianwesh9114 4 роки тому +1

    Very good explanation sir..

  • @debatoshbhowmik
    @debatoshbhowmik 5 років тому

    Super Anna.... Ur explanation are really good

  • @andhbhakt5552
    @andhbhakt5552 3 роки тому +1

    Explained very nicely.
    Please share video of LBB protection.

  • @mohsantufail4997
    @mohsantufail4997 4 роки тому +1

    Excellent work 👍

  • @emreistek8685
    @emreistek8685 4 роки тому +1

    So compact study. Thanks.

  • @georgeabalon6481
    @georgeabalon6481 4 роки тому +1

    Nice video brother. Very helpful keep up the good work!!! Kudos!!

  • @akhilsm6840
    @akhilsm6840 2 роки тому +1

    Super bro keep going

  • @tusharkantasatapathy2770
    @tusharkantasatapathy2770 5 років тому

    Very Nice Sir !! Really I learned about TCS Relay !! Thanks a lot !!

  • @assamelectricaltechno8732
    @assamelectricaltechno8732 4 роки тому +1

    Good job sir

  • @najeeb1578
    @najeeb1578 2 роки тому +1

    Useful momentz thankz alot do you have VAX31ZG0750BA model wiring diagram

  • @malirahulpr
    @malirahulpr 4 роки тому +1

    Thankyou sir it's helpful

  • @ILAYARAJAraja
    @ILAYARAJAraja 3 роки тому +1

    Super anbu

  • @cricketinformationcapsule
    @cricketinformationcapsule 5 років тому

    Sir your explanation is very good.I have one request plz make series wise all video and explain in english. Thanks

  • @arun4846
    @arun4846 2 роки тому +1

    Superb 👍

  • @mohammediqbal9729
    @mohammediqbal9729 2 роки тому

    Sir can we connect indication in series with pre close and post close circuit in series with Shunt trip coil, instead of tcs relay

  • @mohanrajk6517
    @mohanrajk6517 5 років тому

    Excellent explained

  • @dhrupadsaha4171
    @dhrupadsaha4171 4 роки тому +1

    Thanks you so much Sir 🙏🙏

  • @ravi4453
    @ravi4453 2 роки тому +1

    Can you explain AVR drawing of 300MW Alternator....

  • @sajeshkannnur
    @sajeshkannnur 3 роки тому +1

    Dear bro how to avoid this mal alarm during closing and open because every time it will record fake alarm in scada

    • @baranitech1026
      @baranitech1026  3 роки тому

      we have to make TCS blocking logic during open and closing time bro ..

  • @gurpreetsinghee
    @gurpreetsinghee 3 роки тому +1

    Tell us about numerical supervision relays, e.g. avana, jvs etc

  • @safsaf1222
    @safsaf1222 4 роки тому +1

    What will be happen if the drop voltage which supplied the A& B coils became near the nominal voltage as the series resistances value became not stable or failed? Maybe tripping coil of c.b will operate. Or ? What will happen?

    • @safsaf1222
      @safsaf1222 4 роки тому +1

      Also, I am facing the issue for transformer 33kv c.b was opening many times during load without any indication, is that has relation to TCS or not ? Plz advise

    • @baranitech1026
      @baranitech1026  4 роки тому

      NO

    • @electricalsubstationmainte7671
      @electricalsubstationmainte7671 4 роки тому +1

      If resistance failed i.e open circuit. isn't it? in that condition Tcs relay will not work.

  • @smrutiranjanbeheraelectric6394
    @smrutiranjanbeheraelectric6394 4 роки тому +1

    Sir
    In case of Preclosing condition,both A& B coil closing??

  • @yousefalotaibi8343
    @yousefalotaibi8343 5 років тому +1

    Thank you

  • @PC_Affairs
    @PC_Affairs 4 роки тому

    If breaker trip continuously TCS showing healthy or not

  • @vishnu218177
    @vishnu218177 4 роки тому +1

    What will happen if both A and B coils got failed....
    It will also account as faulty trip coil .Is it right?

  • @MrJamalodeen
    @MrJamalodeen 4 роки тому

    Brother are you giving training to the engineers through training center?

  • @pritamsinghchauhan1338
    @pritamsinghchauhan1338 4 роки тому +2

    Why are TCS Relay failure reason.
    TCS relay indicator not glowing Green or Red.

  • @kundanlal9077
    @kundanlal9077 3 роки тому +1

    Relay trip coil ko kitni votage deti hai

    • @baranitech1026
      @baranitech1026  3 роки тому

      approximately it will be 80% but you have to check Pickup and drop test to find this value.

  • @Mhdmnr68
    @Mhdmnr68 5 років тому

    Can u explain in 110v dc system how we getting 55v posetive to earth or negative to earth.(normally we ge 110v between + to- .then how geting 55v respect to earth)
    How getting return path when any erth fault occure in 110v dc system

    • @rajeshtk1246
      @rajeshtk1246 5 років тому +1

      The DC battery system is to be kept ungrounded normally to avoid leakages. In battery charger, the mid point of the battery cell system is earthed via a high resistance.(Equivalent to not grounding the dc system). This will help you get the +55 V when you test betwen a positive point in the circuit and the earth. Likewise is the case with the -ve and earth. i.e, the return path is via the earthed high resistor.

  • @electricalwithkapil7137
    @electricalwithkapil7137 4 роки тому

    Sir ,i have one question If we can do preclose connection in post close and vice versa what should be happen?

    • @electricalwithkapil7137
      @electricalwithkapil7137 4 роки тому

      @@baranitech1026 Sir that's mean there is no effect on TCS indication and trip circuit working.

    • @rajeshtk1246
      @rajeshtk1246 4 роки тому

      It will cause in TC burn out as the Post Close Supervision path will have a trip supply from the Master Trip relay in the event of a fault. So, after the breaker is opened, the Trip supply will directly come to the TC and it will remain there continuously causing TC burn out. Also, your post close and preclose TC healthy indication will not b available.

    • @adnansworld744
      @adnansworld744 4 роки тому +2

      @@baranitech1026 & @kapil prasad
      Coil "C" will pick up only when Trip coil open or DC supply fail only.
      During intermittent time , that is CB open to close or open to close - Coil "C" will not pick up , because the coil "C" ( contact ) have inherent delay for Pick up. Hence no alarm will not come during transaction period .

    • @adnansworld744
      @adnansworld744 4 роки тому

      @@baranitech1026
      Coil C ( Contact) have inherent Pick up delay. Hence coil 'C" never pickup during CB operation transaction period. ( Open to Close or Viceversa)
      It will pick only in Three conditions
      1) DC supply fail
      2) Trip coil open
      3) Loose connection in Trip circuit .
      Thanks Engr. Barani
      Can share your Email ID

    • @electricalsubstationmainte7671
      @electricalsubstationmainte7671 4 роки тому

      pre close and post close wire ko agar aap breaker end pe change karte hai to kuch problem nahi hoga agar aap TCS relay me change karte hai to TC coil burn ho jayega fault condition me breaker off hone ka baad usse hamesha +ve milte rahega.tc burn ho jayega.

  • @yousefalotaibi8343
    @yousefalotaibi8343 5 років тому

    Can you explain the Directional oc & ef relay

  • @Mhdmnr68
    @Mhdmnr68 5 років тому

    👍👍👍

  • @shihabahmed5399
    @shihabahmed5399 4 роки тому

    Please could you zoom ?it's not clear, information

  • @nrathore1908
    @nrathore1908 4 роки тому

    English k chakkar me short circuit ho jayega sir hindi me bhi bna diya kro

    • @viveksingh3989
      @viveksingh3989 3 роки тому

      ua-cam.com/video/alOIhZU7kUU/v-deo.html
      Hindi walo ke liye specially

  • @eletricalkingdom7612
    @eletricalkingdom7612 Рік тому +1

    Hindi language

  • @dilipsahusahu680
    @dilipsahusahu680 4 роки тому

    Hindi

  • @jkj1459
    @jkj1459 4 роки тому

    WHAT IS A & B PLEASE EXPLAIN FIRST COMPONENTS OF CIRCUIT FIRST BEFORE EXPLAINING THE CIRCUITRY. UP T 1.23 YOUR EXPLANATION WAS GOOD AFTER THAT YOU DID NOT TELL DETAILS "A" AND "B" AND ITS FUNCTION . VERY POOR EXPLANATION SIR . SORRY .

    • @rajeshtk1246
      @rajeshtk1246 4 роки тому

      A Coil is for Post Close Supervision of Trip Coil. B Coil is for Pre Close Supervision of Trip Coil. If A coil or B coil picks up, the C coil will pick up.

  • @vijayhotkar1977
    @vijayhotkar1977 3 роки тому +1

    Hindi nahi aati ky aapako

  • @narendersharma5523
    @narendersharma5523 4 роки тому

    भाई जी हिंदी में समझाओ