How to check your Electrical motor winding - Continuity & Insulation resistance test

Поділитися
Вставка
  • Опубліковано 1 лют 2025

КОМЕНТАРІ • 120

  • @shoh888
    @shoh888 2 роки тому +5

    Thank you for the video. basically to check insulation value you dont need to disconnect the star configuration (unless you encounter a bad reading and then start checking separately) if CB is off you can check the insulation test as it is.

    • @mosesabunike2055
      @mosesabunike2055 Рік тому +2

      You're the first I've heard and seen in practice not disconnecting the star configuration.

    • @shoh888
      @shoh888 Рік тому +3

      @@mosesabunike2055 when circuit breaker is off. The cable is connected with the motor coils and joined in star connection. If you make insulation test with the chassis, you can make from every terminal in cb with the chassis. And if problem found then you can start disconnecting to isolate the problem. Both cable and winding can carry 500V dc pulse.

    • @Roq-stone
      @Roq-stone Рік тому

      That’s right

  • @danielteyehuago1633
    @danielteyehuago1633 Рік тому +7

    Wow! Well explained. Thanks for sharing it with us. I really appreciate it. I learnt three steps
    1. Visual inspection; check for burnt cable etc
    2. Continuity test; using the ohm meter or digital multimeter
    3. IR test; using the meggar or Insulation Resistance tester

  • @anthonyobiano
    @anthonyobiano Рік тому +2

    Your explanation is clear and to the point. 🎉 thank you

  • @30mAkills
    @30mAkills 2 роки тому +13

    Hi, its not 1 mOhm, but its infinity sign (I), so IR value is more than 200 mOhms @500V in this case.

    • @zawaung1988
      @zawaung1988 2 роки тому +1

      I was confused before I see your comment. 1 Mohm is bad.

    • @meomarte
      @meomarte Рік тому +1

      Imagine how bad one milliOhm is. :)

  • @JaykeSapalaran-iq3qs
    @JaykeSapalaran-iq3qs Рік тому +1

    Great video tutorial 👍♥️ thank you for sharing your knowledge ♥️🇵🇭

  • @jcuruenac
    @jcuruenac Рік тому +2

    I have a question, between shaft and earth, motor must be in continuity or open circuit?

  • @dariankrieger4813
    @dariankrieger4813 24 дні тому

    Best video on UA-cam thank you

  • @boukhirahocine4912
    @boukhirahocine4912 Рік тому +1

    thank you so much . how about contactor coil test

  • @fidelisdaniel2034
    @fidelisdaniel2034 4 місяці тому

    Please sir your lecture on motors mega ohms and insulation and resistance is very educative thank you. Sir please how can I get the multimeter so I can be using it for my job I'm an electrician

  • @aleksibakhturidze8050
    @aleksibakhturidze8050 2 роки тому +36

    The connection is star not delta !

    • @murigukabugi
      @murigukabugi Рік тому +1

      That’s right

    • @isaiahcastillo3087
      @isaiahcastillo3087 Рік тому +3

      He corrected himself in the video using captions

    • @ucheinnocent2680
      @ucheinnocent2680 10 місяців тому +1

      How can one determine in the a particular motor is connected in star or delta configuration?

    • @ucheinnocent2680
      @ucheinnocent2680 10 місяців тому +1

      How can one determine the configuration of the motor?

    • @TlD-dg6ug
      @TlD-dg6ug 9 місяців тому +1

      @@ucheinnocent2680 The motor spec/model plate has that info. If it doesn't, you have to do resistance testing to find the coils, and then either wire them series or parallel. Honestly if you don't know how to tell the difference, you shouldn't be working with electricity unless you learn what you need to before ever touching it.

  • @vkk3292
    @vkk3292 Рік тому +1

    What is the minimum resistance value need for a winding? Is there any equation for that?

  • @kennyla4060
    @kennyla4060 8 місяців тому

    Where are you putting your red probe when testing the windings? Was it the earth terminal or chassis?

  • @garyfifield5858
    @garyfifield5858 3 роки тому +1

    please do a video on how to build an2 rig o have a lot problems with sorting out this test been blocked from doing the British an2 but need to build an am2 myself to sort my problems thanks

  • @sanjaykrishnakrishna-jr4bc
    @sanjaykrishnakrishna-jr4bc Рік тому

    Sir I like your videos very useful I need to know how to injuct resistance test again

    • @maintenanceengineeringinsider
      @maintenanceengineeringinsider  Рік тому +1

      It is expressed in the video. Put your multimeter to Resistance measurement, then check for low resistance, less than 100 ohms. If the measured resistance is high, then there is a problem

  • @danielasare1165
    @danielasare1165 2 роки тому +4

    Great video mate except the connection i believe is in star

    • @CHOPPA78
      @CHOPPA78 2 роки тому

      He said it was star NOT delta

  • @gurdeepdhindsa1786
    @gurdeepdhindsa1786 6 місяців тому

    How much Voltage you put in IR test for 3 phase cable (phase to phase)????

  • @marijaismail8397
    @marijaismail8397 3 роки тому +2

    Good job mate👍

  • @bangbambang1387
    @bangbambang1387 Рік тому

    Is it okay if one of the measurement is ~800 m ohm and the others is above 5 g ohm?

  • @shittuibrahim8534
    @shittuibrahim8534 Рік тому +1

    Thank you for the lesson.
    GOD bless you.

  • @ajohn502
    @ajohn502 2 місяці тому

    what do you mean if the motor is "wedged"?

  • @namanyaosbert3619
    @namanyaosbert3619 Рік тому +1

    Thank you very much brother

  • @hosraiyan
    @hosraiyan 2 роки тому

    great video so far,i like it and subscribe waiting for more video!

    • @maintenanceengineeringinsider
      @maintenanceengineeringinsider  2 роки тому

      What topic would you like to see

    • @hosraiyan
      @hosraiyan 2 роки тому

      @@maintenanceengineeringinsider more in motor maintainance and repair,also automation from basic.

    • @hosraiyan
      @hosraiyan 2 роки тому

      @@maintenanceengineeringinsider more in motor maintainance and repair,also automation from basic.

  • @Xxxcappie23
    @Xxxcappie23 3 роки тому +1

    Do a single phase motor test too please. Would like to see what happens when capacitors are involved. ...

    • @maintenanceengineeringinsider
      @maintenanceengineeringinsider  3 роки тому +4

      Thank you for suggesting a topic. I don't have a single phase motor, and i will source for it. Single phase motors have two sets of windings and the charge stored up in a capacitor will simulates a third winding. I reckon that the tests should be similar. However, perform test on the capacitance of the capacitor as well.
      We will prove this, in the future.

    • @30mAkills
      @30mAkills 2 роки тому +2

      Capacitors, thermistors should be isolated from the windings under check, otherwise you will get improper readings. Meggering is both science and art.

    • @antoniocarvalho8320
      @antoniocarvalho8320 Рік тому

      @@maintenanceengineeringinsider can you please, answer me some basic question about? Thanks

    • @maintenanceengineeringinsider
      @maintenanceengineeringinsider  Рік тому +1

      How may i help ?

  • @gunatillekaleslie3521
    @gunatillekaleslie3521 Рік тому

    Appreciate if you could take a faulty ( broken) motor for this demonstration

  • @cariyaskeling514
    @cariyaskeling514 3 роки тому +2

    Very good

  • @shittuibrahim8534
    @shittuibrahim8534 Рік тому

    please if a single phase motor is continuous horn,what will be the cause sir.

  • @sthulimbatha9321
    @sthulimbatha9321 2 роки тому

    OL between any winding( U1,V1 etc) and earth is it a fail?

    • @maintenanceengineeringinsider
      @maintenanceengineeringinsider  2 роки тому

      Open loop (OL) during a continuity test, between the windings of an inductor motor is good. Because it means that there is no contact between the windings.
      However, It is very important to test each winding with the chasis of the motor and make sure it is reading OL.
      OL could be good or bad, depending on what you are testing for.

  • @yousefalmuzini7150
    @yousefalmuzini7150 7 місяців тому +1

    great video thanks

  • @samuraix8903
    @samuraix8903 2 роки тому

    Hi after i remove the main supply cable, when i do insulation test do i need to take test on all the windings or just U2,V2 and W2?

    • @maintenanceengineeringinsider
      @maintenanceengineeringinsider  2 роки тому +1

      @samurai X , You remove the configuration plate, and you do insulation resistance test between U2 & V2, U2 & W2 , U2 & Chasis.
      Repeat the same process with V2, and then repeat the same process with W2.

    • @samuraix8903
      @samuraix8903 2 роки тому

      @@maintenanceengineeringinsider thanks for the fast reply, can i know why there is no need to take at U1,V1 anz W1? Or what test can do at U1,V1 and W1?

    • @maintenanceengineeringinsider
      @maintenanceengineeringinsider  2 роки тому +1

      @@samuraix8903 U1, , V1 and W1 are three sets of coil, which are known as winding. U1 is the opposite end of U2. So when you test U1 or U2, you have tested one winding.
      I will make a short video about this for you ASAP .

    • @samuraix8903
      @samuraix8903 2 роки тому +1

      @@maintenanceengineeringinsider ah so means i have to do insulation test of the winding on U2, V2 and W2 as well to check if its bad?

    • @maintenanceengineeringinsider
      @maintenanceengineeringinsider  2 роки тому +1

      @@samuraix8903 ua-cam.com/video/YZVi8FMfF5o/v-deo.html

  • @daveb9370
    @daveb9370 5 місяців тому +1

    You are seeing infinity on your megger tester. 1kohm is the too low, 1Mohm is the minimum you want to see on the test.

  • @ezipezy
    @ezipezy 2 роки тому +1

    Good video, thanks. Why did you choose 500V and not 250V or 1000V?

    • @varnchlarson
      @varnchlarson 2 роки тому +1

      I think because maybe the motor is required 480VAC so by using 500VAC your able to push electrons through and read the ohms. I’m still learning myself and not sure if I’m right. Lol

    • @ezipezy
      @ezipezy 2 роки тому

      @@varnchlarson I think the mega pushes 500V DC so not sure if your theory would make sense. good thought tho

    • @maintenanceengineeringinsider
      @maintenanceengineeringinsider  2 роки тому +3

      Hi , I used 500VDC to inject into the winding of the Induction motors, so that i can test to seek if there is any weakness in the insulation or the winding of cables.
      The nominal voltage for this electrical motor is 400VAC. It could be tested with 1000VDC as well. But this is how I was thought and it works for me.

    • @30mAkills
      @30mAkills 2 роки тому +1

      @@maintenanceengineeringinsider so as to save the thermistor (if there is one).

    • @Roq-stone
      @Roq-stone Рік тому +1

      I normally disconnect the thermistor (temperature circuit) and use 1000V. I believe the 1 kV test gives me a more sensitive test. And since these tests are infrequent, I want to catch any pending fault.

  • @randonnaidoo2592
    @randonnaidoo2592 3 роки тому +1

    What happens if it's over 2megaOhm does it still pass or fail

    • @maintenanceengineeringinsider
      @maintenanceengineeringinsider  3 роки тому +1

      Yes, the aim is to get a reading on, or above 1 MegaOhm. The higher the resistance of the insulation material, the better. 1MegaOhm is the minimum recommended by the Eletrotechnical governing body.

  • @AbinosMonaheng
    @AbinosMonaheng Рік тому

    Are you preparing for trade test or what? This motor is connected in star not delta.

  • @flordelinoestoque5706
    @flordelinoestoque5706 Рік тому

    Why, I don't see any capacitor in that motor. Is it a 3-phase, isn't it?

  • @austineomondi5805
    @austineomondi5805 2 роки тому +1

    Cool 😎💯

  • @Roq-stone
    @Roq-stone Рік тому +5

    That’s a wye connection not delta.
    Someone said too. I had to rewind to confirm. A delta would have diagonal across and and one cross over.

  • @Okie-Tom
    @Okie-Tom 2 роки тому

    What ended up being the problem?

    • @maintenanceengineeringinsider
      @maintenanceengineeringinsider  2 роки тому

      I think nothing. This other 2 video have a different result.ua-cam.com/video/DIsUUdYbN_c/v-deo.html ;
      ua-cam.com/video/df3K5aU_nyw/v-deo.html

  • @Ozioma-cq8tj
    @Ozioma-cq8tj 8 місяців тому +2

    Thanks

  • @sanjaykrishnakrishna-jr4bc
    @sanjaykrishnakrishna-jr4bc Рік тому

    Sir thanks your but I didn't clear injuct 500 v

  • @joshuarbanda
    @joshuarbanda Рік тому

    Bro I am so lost 😢 I know nothing of electricity and I'm trying my best to check these conveyor motors. 😅

  • @EmmanuelMasetera
    @EmmanuelMasetera Рік тому

    I Thought electric motor resistance depends on the size of the motor that's why we use R=V/I

  • @muhammadnaeem4834
    @muhammadnaeem4834 Рік тому

    Nice

  • @phonemoesataung166
    @phonemoesataung166 2 роки тому +1

    Thanks mate

  • @eng.yaskhudhurjabbaralhass9412
    @eng.yaskhudhurjabbaralhass9412 2 роки тому

    your resistance always still 1 ohm? you should remove every wire and the connection is star not delta.

    • @30mAkills
      @30mAkills 2 роки тому

      Resistance = 3.5 Ohms all coils.
      Insulation Resistance = "'I'" means Infinity and in this case its more than 200mOhms. (max range of meter @500V).

  • @wisdomorji7118
    @wisdomorji7118 Рік тому +2

    Its connected in star teacher

  • @EvidanceChikuhuhu-zd6nl
    @EvidanceChikuhuhu-zd6nl Рік тому

    Informative video, thank you. However, that motor configuration is delta, not wye

  • @sanjaykrishnakrishna-jr4bc
    @sanjaykrishnakrishna-jr4bc Рік тому

    Can you plz show

  • @jenry70
    @jenry70 2 роки тому

    START CONNECTION!!!

  • @sihlemagcaba8985
    @sihlemagcaba8985 2 роки тому +1

    That is a star connection

  • @evanschitungu4207
    @evanschitungu4207 10 місяців тому

    The lead ra short that mean the motor is connected in star

  • @timboylen7239
    @timboylen7239 Рік тому

    But not see the reading

  • @hassanrefaey7242
    @hassanrefaey7242 Місяць тому

    It’s not delta connection it’s star connection

  • @CarolinaBorlasa
    @CarolinaBorlasa Рік тому

    Thats not delta connction its a wye

  • @simonezangari1306
    @simonezangari1306 15 днів тому

    No delta..star

  • @raymondsigauke8613
    @raymondsigauke8613 2 роки тому +1

    REPEAT AFTER ME #STAR STAR STAR STAR NOT DELTA

  • @Flatlikeme
    @Flatlikeme 10 місяців тому

    DUDE! THY DO YOU TAKE TO LONG ? SOUNDS LIKE YOU ARE DRUNK

  • @whatdoiputhere86
    @whatdoiputhere86 Рік тому

    Dude is hard to listen to. Missing a couple crayons.

  • @ronspencer846
    @ronspencer846 3 роки тому

    Never stated voltage rating of the motor. English skills need improvement

    • @maintenanceengineeringinsider
      @maintenanceengineeringinsider  3 роки тому +1

      Hi, the voltage rating does not really matter here, when performing either Continuity test or Insulation resistance test.
      As per improvement, i totally agree with you. Hablo fluidamente en 4 idiomas.
      Asųsų one ka ina asų?

    • @ronspencer846
      @ronspencer846 3 роки тому

      @@maintenanceengineeringinsider shouldn't the voltage rating of the motor be known as to select the right test DC from the tester ?
      575v motor 1000v test
      240v motor 500v test. etc....

    • @maintenanceengineeringinsider
      @maintenanceengineeringinsider  3 роки тому

      @Ron Spencer, In Factories in England, we run Asynchronous motors at 240 VAC or the more commonly used 400VAC. I run my insulation resistance tests at 500VDC.
      This is enough to search out and indicate weakness in the insulation.
      You do have a reason too. The Insulation resistance tester allows user to inject either 500VDC or 1000VDC. Whichever way, the reading must remain between 1 Megaohm and 2 megaohms. Any reading under 1 Mega ohm is a fail

    • @ef7480
      @ef7480 2 роки тому

      He speaks better English than many people in England..

    • @30mAkills
      @30mAkills 2 роки тому

      @@maintenanceengineeringinsider Please say correctly. Reading above 1mOhm is OK and not between 1 and 2mOhms.

  • @3inchfrankenstein
    @3inchfrankenstein 3 місяці тому

    That looks like a Lowara motor. I wouldn't bother fixing it.

  • @amalensijaved3145
    @amalensijaved3145 9 місяців тому +2

    Nice