Pls I installed PT100 with 3 core with this PICC 152A. The cold pipe line is expected to be 7dec celsius. But we are seeing 57 Dec celsius . What can be the problem? What can be the problem? If
Have you selected the input properly in Input Parameter are you sure the temp sensor is PT 100 plz confirm once more how many wire you have in your PT 100 Temp sensor
Are you taking 4 to 20 mA signal on plc then see My video SCP BLOCK ON ALLEN BRADLEY PLC WITH PROCESS INDICATOR SELEC -PIC152A-VI LADDER PROGRAMMING ua-cam.com/video/mSjvN_xfPoo/v-deo.html
Brother i install PCI 152A- VI instead of Old PCI 152N-B2. Now i face a problem. Process indicator not give Analogue Output. It show only 4 mA. This analogue Out put connected with PLC Analoge module. As a result SCADA not show temperature. But Process indicator self disply show perfectly. What can i do.
Ok so have you check in the plc its not giving any analog signal in your ladder logic .what plc you are using ? You have to On the signaling parameters in PIC 152 level 3
Sir this meter is designed for temp display and and the name of feedback you will get current and analog output , For the air pressure control you cant use this meter
Brothers relay outputs are Potential Free relay i mean to say that there are two relay output let you have set some temp and you want feedback that temp has reached so you can give 24 or 240 v supply from outside to comman and when the temp set point reached then relay changed the state and give the feedback .
GO to Level 0 and the last parameter is RST from that parameter you can reset the meter , just go in parameter and then go on RST and then press enter then you will get YES Or No obtion pressing yes will reset the meter
The fault s.br can remove if you will do proper RTD wiring if you will do wrong wiring you will get this error so plz check RTD side wiring or Temp meter side wiring or wire maybe broken
Sir pci152 controlar me water level ke liye use kr sakte h
Dear sir my pic 152 shows 24 degree but actual temprature is 31 degree how can i calibrate?? Can you help me this
Yes sir please click on this link ua-cam.com/video/3Y8U0NRkU6w/v-deo.html This will help you to calibrate your PIC 152
Sir thank. Sir. humidity kese pta lagaye is meter se .please sir explain waiting.
Aye temp meter hai but ek baat bataye app ka humidity sensor Kya signal dayta hai volt or mA agar dayta hai to LUL 0 Mai Volt Aya mA select kar loo
Sir very nice video tanks
Pls I installed PT100 with 3 core with this PICC 152A. The cold pipe line is expected to be 7dec celsius.
But we are seeing 57 Dec celsius .
What can be the problem?
What can be the problem?
If
Have you selected the input properly in Input Parameter are you sure the temp sensor is PT 100 plz confirm once more how many wire you have in your PT 100 Temp sensor
Can you please suggest how to scale 4-20mA in betwwen 0-325 Scale range?
Are you taking 4 to 20 mA signal on plc then see My video SCP BLOCK ON ALLEN BRADLEY PLC WITH PROCESS INDICATOR SELEC -PIC152A-VI LADDER PROGRAMMING ua-cam.com/video/mSjvN_xfPoo/v-deo.html
@@MR_Industrial_Automation no we have connected pressure transmitter to PIC152 which gives output of 4-20mA
Dear Rashid please make a video for selec PIC 152 controller for vacuum control. Please let us know how we will do the program for that
Dear sir i have some questions regarding vaccum control if you allow i can call you
Bro indicator repairable or not. Please tell me. If any service center availble please tell me.
No bro it's there is not service center by the way what happened to your indicator
Brother i install PCI 152A- VI instead of Old PCI 152N-B2. Now i face a problem. Process indicator not give Analogue Output. It show only 4 mA. This analogue Out put connected with PLC Analoge module. As a result SCADA not show temperature. But Process indicator self disply show perfectly. What can i do.
Ok so have you check in the plc its not giving any analog signal in your ladder logic .what plc you are using ? You have to On the signaling parameters in PIC 152 level 3
@@MR_Industrial_Automation I use Siemens ET-200 PLC.
@@OIUzzal ok so check in your ladder you are getting signal or not when the temp rise how you done the wiring properly
Sir can it use with air pressure transducer( for air pressure control)
Sir this meter is designed for temp display and and the name of feedback you will get current and analog output , For the air pressure control you cant use this meter
for air pressure you can use other meter if you told me the whole using purpose then i can suggest you the model
How to clear 5.br error in selection 152A-Vl processor indicator
Sv8 digital meter k bareme Banaye video
Room oxygen controller hoga bro?
App oxygen ka signal kaisay layenge meter pay do you have any device
Do you have any device who will give signal to temp Controller
Pls make video on pid controller of massibus controller
In masibus there are 5 PID controller it is better if you suggest. The Model no Thank you
Kya ye 24volt dc p on ho Sakta hei
Haan 220V and 24Volt dono supply pay available hai but you have to choice 24 volt model
Brother, please let me know what the relay outputs are for.
Brothers relay outputs are Potential Free relay i mean to say that there are two relay output let you have set some temp and you want feedback that temp has reached so you can give 24 or 240 v supply from outside to comman and when the temp set point reached then relay changed the state and give the feedback .
Sir plese tell me setting parameters for alarm 1 & 2 setting
Ok give some time
Sir please explain all the parameter of selec Twix 2 spot counter
Ok sir i will try to explain give some time
Plz subscribe the channel so when i explain you got the update
Sir, please explain all the parameters of PID 330 controller..😊
Assalam Alykum
plz explain the ch403 controller
Walekumasslam ok
Sir pasword bhul gye hai.srif LUL 5 aa rha hai kase reset kre
Give me some time I will tell you plz wait
Sir, finally how to do reset ?
Go on level 0 , the last parameter is for rst reset the whole meter I have also show in my video
How to program for vfd amps
On meter input just select 0 to 10 volt Input and do connection on VFD Potentiometer terminal
@@MR_Industrial_Automation tq
Can u suggest for rpm
Pic 152 showing 50 degrees instead of 25 degree centigrade
What input you are using PT100 or any other signals
Sir controller water level mesur
Tamil video upload please sir
Dear sir i dont tamil really sorry can you understand hindi or english otherwise i will try to translate
In tamil
Plz subscribe my channel
how to price
Rs 2700(Discount price ) its depend on discount
Plz check level 3 for retransmission signal i have explained in video if again you are not getting signal you can call me
Pic 152 ko reaset kaise kiya jata h
GO to Level 0 and the last parameter is RST from that parameter you can reset the meter , just go in parameter and then go on RST and then press enter then you will get YES Or No obtion pressing yes will reset the meter
Sir pasword bhul gye hai.srif LUL 5 aa rha hai kase reset kre
But lock me LUL 0 kase aayega.
LUL5 hi rahta hai
Ok plz wait I will tell you give some time
आपका व्हाट्सएप नंबर उपलब्ध होगा
G
How to clear 5.br in selection pic152A-Vl
The fault s.br can remove if you will do proper RTD wiring if you will do wrong wiring you will get this error so plz check RTD side wiring or Temp meter side wiring or wire maybe broken
Without sensor not change only on Lul 5 not start next step