  • @ne0teric
    @ne0teric Рік тому +1

    Have one going bad atm and even the computer tech that plugs into the microprocessor control doesn't even know this (he left the last replacement on %), couldn't find this info anywhere now that I bought another needed replacement.
    Thank you so much. This will save me lots of yelling at me from superiors tbh.

  • @jonasthomsen8665
    @jonasthomsen8665 9 місяців тому

    Hi,
    Can you please make a video on how to program the SA5000 sensor, output 1 to send 4-20mA temperature signal, and output 2 to show digital flow measurement?
    Please if possible show how to set the range of the temperature for the 4-20mA signal aswell.
    Thanks in advance.

    • @ifmefectorUSA
      @ifmefectorUSA  8 місяців тому

      @jonasthomsen8665 thank you for your question! On the SA series sensors with the analog output option, only output 2 can be set for an analog signal.
      At the 4:30 mark in this video, you can see us toggle to the EF menu, then into the CFG menu. Within the CFG menu there is a parameter called “SEL2” and if you set this to temp, output 2 is now configured to output an analog signal for temperature.
      Once this is configured you can set your range for the analog signal by setting the ASP2 and AEP2 settings. You can see how to navigate to these settings around the 4:30 mark as well.
      ASP2 is the temperature value in which you will receive a 4mA signal and AEP2 is the temperature value in which you will receive a 20 mA signal and the rest of the range is scaled linearly.
      Feel free to call our service center at 800-441-8246 or email our Application Engineers at info.us@ifm.com if you have any additional questions.

    • @8284Andy
      @8284Andy 3 місяці тому

      Hi. I would like to check oil temperature continiously.
      But display changes in 30 second.
      Can you please let me know how to solve this problem?

    • @gibbedyg9369
      @gibbedyg9369 10 днів тому

      @@8284Andy have a look at "dAP" settting in the manual and see if that describes your issue.