High Voltage testing with SensorLink - Troubleman's kit

Поділитися
Вставка
  • Опубліковано 23 січ 2025

КОМЕНТАРІ • 219

  • @Bobsdecline
    @Bobsdecline  3 роки тому +43

    Another great use for the voltstik - It can verify tap positions on a Voltage regulator!
    I apologize in advance for the absolute cheesiness at the 5:38 mark! 🤣 - Have a great week everyone!

    • @blockisle9
      @blockisle9 3 роки тому +1

      Did your company have add it to a list of approved equipment and set up policy on its use

    • @WELLINGTON20
      @WELLINGTON20 3 роки тому +3

      69,000KV??? 69 MILLION VOLTS?

    • @Bobsdecline
      @Bobsdecline  3 роки тому +3

      Lol someone else mentioned that! 😳 Ahem * 69kv 🤣🤫🍻🍻

    • @chrispy725
      @chrispy725 2 роки тому

      I've used a similar ampstick by the same company. I think it saves 9 measurements and you basically touch the amp clamp to the line and count 4 seconds and it should have a measurement. They come in handy for verifying phasing on relays. They also make a "wide mouth" version.

    • @MisterKingBing
      @MisterKingBing 2 роки тому

      I'm not sure that I would rely on the voltstik to verify neutral position on a voltage regulator. Specs for the voltstik state plus/minus 1% while one step of a voltage regulator is less than that (5/8th%). It would likely easily detect neutral position but I just don't think I would rely on it as one of my neutral indications. But for troubleshooting regulator trouble, it is a great tool.
      I really like the sensorlink products. We use the ampstik quite often when we do recloser maintenance. We verify amp readings from the ampstik to what the recloser control is showing to verify the integrity of each CT and CT circuit.
      I love your videos and love the content!

  • @russjam121
    @russjam121 3 роки тому +7

    Hi from the UK 👊 I want to say thank you for your videos. I've never worked in the electricity industry. I am now medically retired but watching your videos is very entertaining and interesting to watch and kills time . I have seen many documentaries on the linesman industry in Canada and the u.s. and is a fascinating subject but your videos are just that bit more informative and detailed and you give a more comprehensive look into the day to day life of a troubleshooter to find what the cause of the outages or issues on the lines are and plans the solution to get power back to your customers. So thank you for all your hard work and videos.

    • @Bobsdecline
      @Bobsdecline  3 роки тому +1

      Thanks so much for that Ghost Dragon! It's comments like these that make it worth sharing these videos 👊🙏. Cheers!!

    • @mathman0101
      @mathman0101 3 роки тому

      Completely agree your work on videos and effort to show this is high quality and no doubt interesting for those in the industry and still learning.

  • @scrotiemcbogerballs8286
    @scrotiemcbogerballs8286 3 роки тому +25

    God bless all linemen we don’t have power without them

    • @fitybux4664
      @fitybux4664 2 роки тому

      Eh. You might have a few months in an apocalypse before the power grid stops working. 😆

  • @bigjd2k
    @bigjd2k 3 роки тому +21

    At 16:11 be careful not to short out adjacent connections with the hook!
    Great videos, keep ‘em coming!

  • @yeeterooni7352
    @yeeterooni7352 Рік тому

    I'm just a normal residential electrician. It's cool to watch people working with tens of thousands of volts. Love watching you go underneath those lines buzzing. They just sound badass.

  • @twilllinemanforhire6266
    @twilllinemanforhire6266 3 роки тому +17

    Whats up. House looks good. Can’t wait to start getting products to review. Good job!

    • @Bobsdecline
      @Bobsdecline  3 роки тому +4

      Thanks T! For what it's worth I'll do another shout out sometime, your vids are always great!

  • @TheTurpin1234
    @TheTurpin1234 3 роки тому +14

    I think it's awesome that you have a company sending you a free product and it's a great opportunity as long as you give you honest opinion on it, not just what they tell you to say. Which is what you did, but if you get something for free, that makes it sponsored lol. You get a awesome tool, we get a great video, and they get probably the best direct advertising link to linemen. I'm not a lineman, I've just always had a interest in electricity, and I like to know how everything works. Love the vids!!! Great work!!!!

    • @ronblack7870
      @ronblack7870 3 роки тому +1

      well likely if the product is great the utility he works for will buy some of them. so it pays off nicely for the company. he got a free husqvarna high voltage pole saw which also worked great.

    • @TheTurpin1234
      @TheTurpin1234 3 роки тому +1

      @@ronblack7870 The point is that this IS a sponsored video. Its clearly a good product. I'm not saying he was being dishonest or anything. But this is sponsored.

    • @m0cafet627
      @m0cafet627 2 роки тому +1

      Right? That is the literal definition of sponsored content haha.
      But, at least it was a good review in a detailed way.

  • @Malomex13
    @Malomex13 3 роки тому +10

    I think being a lineman is freaking awesome..... I've always been fascinated with what you all do.. Be safe and God bless...

  • @scottbruner9987
    @scottbruner9987 3 роки тому

    12:11 It was really cool how you showed the amp stick some love by belting it in.

  • @joshuat2751
    @joshuat2751 3 роки тому +47

    as an HVAC tech its funny to think that to us 240 - 460v is high voltage when there are people working around 10k- up to over 100k lol.

    • @stiggyness1976
      @stiggyness1976 3 роки тому +5

      Here in the UK, we have national grid voltages of 132kv, 252kv and 400kv. Local grid voltages are down to 66kv, 33kv and 11kv.

    • @RT-qd8yl
      @RT-qd8yl 2 роки тому +3

      I've worked on some HUGE chillers for refrigerated warehouses that were fed with over 1kV, but that's the biggest I've been around, not counting industrial busbars. I started out with res/com HVAC and moved up to ind refrigeration; best move of my life.

    • @michaelguido7505
      @michaelguido7505 2 роки тому +2

      @@RT-qd8yl ind refrigeration. Are you on roofs a lot? Whole reason I don’t want commercial is because I hate roofs

    • @RT-qd8yl
      @RT-qd8yl 2 роки тому

      @@michaelguido7505 Quite often, especially RTUs and rooftop condensers. Even if you're not on the roof, you might be crawling inside a Kool-Jet mounted 30 feet up on a warehouse wall. That's one of the reasons I got out of that side of it. I couldn't handle all the climbing, carrying compressors up ladders, etc anymore. Now I work on the factory side of things and stay on ground level, haha.

    • @FerociousPancake888
      @FerociousPancake888 8 місяців тому

      240 will still pop ya. Doesn’t feel very good. I’m sure you know that though lol

  • @sodiumvapor13
    @sodiumvapor13 3 роки тому +1

    Love the sound when you're near the large power transformers

  • @three-phase562
    @three-phase562 3 роки тому +3

    Interesting device, the voltstick even has a built in proving unit for testing for absence e of voltage procedure. Thanks for the demo.

  • @zackstrang5963
    @zackstrang5963 3 роки тому +1

    Great video Aaron! Always solid information and attention to detail. Keep up the great work.

  • @kiawandajr1097
    @kiawandajr1097 3 роки тому +3

    Sensorlink is a very good product and has been around a long time. Thanks for sharing some of their new bling.

  • @MrBanzoid
    @MrBanzoid 3 роки тому +3

    Looks like a great and safe bit of kit.

  • @ILikeMetricMusic
    @ILikeMetricMusic 3 роки тому

    Another great video :). It’s great to see new products that can make you guy’s job safer.
    A few nights ago I got to see a line fuse “get smoked” (the term the utility guy said) and light on fire as well as spark. It had rained earlier in the day but I have no idea why it went crazy. Heard loud buzzing and saw sparks, then saw it was on fire 😳.

  • @dammdaniel9953
    @dammdaniel9953 3 роки тому +1

    Gawd dammmmmm working with 200+ amps you guys have steel guts ..

  • @davesworkshop2714
    @davesworkshop2714 3 роки тому +2

    New to the channel, great videos 👍, greetings from Ireland. Im an electrical engineer by profession so I tend to avoid anything to do with work but really enjoy your videos. I worked on LV and ELV for years but now the bulk of my work is windfarms and grid stabilisation projects. We generally handle from mast base to distribution grid connection. Worked up to 110kv up to now but chasing a 220kv job now. All under ground though.

    • @Bobsdecline
      @Bobsdecline  3 роки тому +1

      Great to meet ya Dave! Definitely can't go wrong with green energy projects. I've never been to Ireland, my folks have ... I'd love to visit your country someday! 🍻 Cheers!

    • @davesworkshop2714
      @davesworkshop2714 3 роки тому +1

      @@Bobsdecline if our lockdowns ever end! Let me know if you do and I might be able to arrange a few substation tours!! Be like a working holiday!

    • @Bobsdecline
      @Bobsdecline  3 роки тому +1

      That would be really cool Dave! I appreciate that 🍻

  • @oldredcoonhound2182
    @oldredcoonhound2182 3 роки тому

    I believe these guys are true emergency first responders. They are constantly dealing with shit that can and will kill them on a daily basis. 👏👏

  • @matthewbeasley7765
    @matthewbeasley7765 3 роки тому +2

    Schneider Electric bought Power Measurement back in 2005. That ION 7550 has some years on it.

  • @68spc
    @68spc 3 роки тому

    Nice video. I do enjoy your content a lot. I’m glad you got this product. Anything you can stay on the ground to do work with is not only a time saver but also keeps you safer from falling.

  • @appliancerepairshorts
    @appliancerepairshorts 3 роки тому

    Wow!! What you guys do is so amazing. So much voltage and amperage

  • @TheAustrianLineman
    @TheAustrianLineman 3 роки тому +2

    Thanks for the new episode 👌🏻

  • @allenshepard7992
    @allenshepard7992 2 роки тому +1

    Hand written test and cert is great.
    Works on low voltage as well as high.

  • @TnTBLACK95
    @TnTBLACK95 3 роки тому +1

    We've been using these for several years and there are a few issues with the voltmeter. The clamp for your neutral or your 2nd conductor if you're going phase to phase is really cumbersome to take off.. It'll end up having your cord wrapped around the conductor. I took mine off and used a second extendo and and put a single eye log on that lead and just hang the extendo on the neutral or 2nd connector . Also the the power button to the Volt meter you have to take off from the resistor to turn on. As soon as you power up the Volt meter hang it on an energized conductor if possible so so it does not automatically turn back off.

  • @ethernet0
    @ethernet0 3 роки тому +1

    Good video, educative montage with unique shots. I hope you will keep on enjoying your job for years to come. I don’t work on stuff above 230v (Europe), because I know others will always be able to do a better job than me.

  • @missyd0g2
    @missyd0g2 3 роки тому +1

    your a lineman out of.... even have a song about lineman. I ran a large data center. High voltage is very important. most data centers cleanup the power and have backup generators. Data Centers never sleep. High voltage lineman and linewoman also have someone working 24 by 7. unsung essential worker. Thank you for what you do.

    • @colorlessgreenidea3349
      @colorlessgreenidea3349 3 роки тому

      Care to share some of that datacenter power equiptment porn? Relevent, interests.

  • @AdmSpock
    @AdmSpock 3 роки тому +2

    The Ohmstick would be an awesome tool too. It can measure resistance over a connection.

    • @wb5mgr
      @wb5mgr 2 роки тому +1

      They sort of have those. They are called thermal cameras 😉 You can see right where you have high resistance connections that are generating heat.

    • @ianthompson2802
      @ianthompson2802 2 роки тому

      I only mess with up to 24v stuff rn ( but will be forced to deal with higher as ev equipment becomes more common) in school we were told never measure ohms on a live circuit not sire if that changes with lineman applications tho

  • @TheChipmunk2008
    @TheChipmunk2008 3 роки тому +3

    Nice piece of kit. The voltage readings at the end off the padmount threw me a bit, till I remembered canada uses 600v /347ish instead of the 277/480 in the US...
    I'm from the UK where it's almost all 240/415 still (despite the nominal voltage being 230/400.) We do have a bit of 480v split phase still around where the farm is at the end of a 1ph spur (actually technically 2ph, we do delta connections on the primary side here, makes leakage easy to detect and trip out on)

    • @brenteichel7661
      @brenteichel7661 3 роки тому +1

      Oilfield equipment like pump jacks still use 480/277 in Canada, sometimes you will use 480 single phase. Most other commercial customers are 347/600 if fed off the distribution

    • @TheChipmunk2008
      @TheChipmunk2008 3 роки тому

      @@brenteichel7661 Interesting... I presume to allow inventory control for oil companies that work in both the US and Canada?

    • @brenteichel7661
      @brenteichel7661 3 роки тому +1

      @@TheChipmunk2008 likely the equipment is made for the American market, and it’s cheaper and simpler to produce one thing. When we build new 480 v transformer banks we use old transformers. We don’t have any new stock 480v equipment

  • @lewy1
    @lewy1 3 роки тому +1

    I like the overhead amp stick, but I prefer the hasting phasing sticks especially if you have to check phasing between circuits, also prefer as much as possible to do all of my testing on test points on the underground.

  • @LovSven2011
    @LovSven2011 2 роки тому +1

    Nifty tools and meters. To me personally they may seem like inventive toys, to you an inevitable and necesarry tools. 🙂

  • @lewy1
    @lewy1 Рік тому

    As far as dead front transformers go I prefer to do all of my testing on the capacitive test points. Also it’s a good practice to do an amp check every time before you pull an elbow, you should have an idea before you pull it if you are dropping load or breaking parallel or if it’s a dead operation, the amp check will confirm what you think you are doing. Amp checks and potential checks will keep you out of trouble.

  • @Nathan15038
    @Nathan15038 3 роки тому +21

    You know that there’s a lot of power running through it when you can literally hear it like moan

  • @mackayhfx
    @mackayhfx Рік тому

    Is this what you use to check and see if the lines are energized during an outage to make sure generators aren't backfeeding into the grid?

  • @herestoyoudoc
    @herestoyoudoc Рік тому

    haha nice reference to "Pulp Fiction" at 1:55 🤣

  • @willwaconsya3433
    @willwaconsya3433 Рік тому

    Maybe you have shown it but can you demo how to splice an HV cable? I went to school for HV splicing. Doing it in warm conditions inside a class room was fine. But knowing that you guys have to do this in bad weather with extreme cold weather wearing gloves still amazes me.

  • @nateroth1302
    @nateroth1302 3 роки тому

    Have fun and stay safe! Great video and always great content.

  • @johnbeattie5765
    @johnbeattie5765 8 місяців тому

    Retiree , worked for ( Etobicoke ) / Toronto H . E . C . for 36 years and started in the early 70 's right out of school . Did numerous and different jobs and our highest voltage was 27,000 . Happy Trails . ✌ out 🇨🇦 🇨🇦

  • @kencarnahan2253
    @kencarnahan2253 2 роки тому

    Used them 25 years ago, but the wireless is a great idea, used to let the extendo extended and drop it down to a second person he would get the reading then toss it back in the air for the stick man to get the next phase

  • @supporterofeverythingyouli6255
    @supporterofeverythingyouli6255 3 роки тому

    I was a Lineman for the county, and I drove the main roads.

  • @davemackinnon6487
    @davemackinnon6487 3 роки тому

    That's an amazing set of tools!

  • @fitybux4664
    @fitybux4664 2 роки тому

    10:06 Is power factor also measured at substations?

  • @themajasticcreature
    @themajasticcreature 3 роки тому

    Ah yeah. UA-cam recommendations know what I like. I'm currently working in a transformer building company. ETRA

  • @jorangel87
    @jorangel87 2 роки тому

    We use the DVI 500 and the DVM 80 here in Chicago

  • @photorealm
    @photorealm Рік тому

    How do you trust doing de energized work on a line if there is the possibility that some ones grid tied solar is also feeding the line and their equipment fails to de energize or worse, it de energizes then randomly fails mid work? Is that even a thing that could happen?

  • @powerlinekidforsman9360
    @powerlinekidforsman9360 3 роки тому

    at 5:45 i noticed that there were 2 poles just standing there are those new build poles or what

  • @tomboyd7109
    @tomboyd7109 3 роки тому

    If that U-shaped pickup had one arm longer than the other it would be easier to get it engaged overhead.
    Be safe. Thanks for the info.

  • @notcrzzx4359
    @notcrzzx4359 3 роки тому +4

    You inspired me to be a line man

  • @JohnDoe-tb2fl
    @JohnDoe-tb2fl 2 роки тому

    Love the pulp fiction nod lol

  • @peep39
    @peep39 3 роки тому +1

    How do you guys balance the amps between phases when one of them goes crazy? I imagine load across all three is quite different at times

  • @thegreanmonsterable
    @thegreanmonsterable 3 роки тому +36

    speaking of amps I'd like to hear a linemans take on the initiative to have x-million people coming home and plugging their electric cars into the grid every night at 5 o clock within the next 10ish years

    • @alexanderkupke920
      @alexanderkupke920 3 роки тому +7

      If the cars use somewhat "intelligent" charging circuits and we consider "normal" usage where not all cars are run down to 10% battery or less at the same time, not a lot will happen. Also you will not very likely have millions of people on the same substation.
      They did conduct an experiment here in Germany two years ago I think, where they provided electric cars and chargers in the garage of a 80 or so units apartment complex to find out exactly that, as that was what they were afraid might happen. As most cars had not run down that low and most did not even (have to) charge their cars every day, not a lot happened. Additional amperage over the days was somewhere 8 to 20 amps above before readings and we'll within what the lines could handle. This was 230/400 V three phase of course, so for the US a higher actual amperage can be assumed. (Just for perspective, a regular socket here can provide 16 A peak at 230 V)

    • @raygale4198
      @raygale4198 3 роки тому +7

      @@alexanderkupke920 A 50KW charger is a 50KW charger, in Australia most final distribution transformers are 11kV to 230/400V at 150 to 200 kVA feeding maybe 20 to 40 customers. With infill housing development, knocking down one house and replacing it with 3 smaller units, our infrastructure is already taking a hammering. A 50KW charger would require at least a transformer upgrade, or it's own step down charger. Modern infill higher density development without infrastructure upgrading being done at the same time is causing massive problems.

    • @austenteeuwen4223
      @austenteeuwen4223 3 роки тому +3

      Not a lineman, but the generation, transmission, and distribution would need to be upgraded, which is why there is talk of a million volt line for transmission

    • @alexanderkupke920
      @alexanderkupke920 3 роки тому +4

      @@raygale4198 well, at least around here no one talks about putting a 50 kW Charger in every home. Currently there is a Programm to financially support having Chargers installed in homes, but those are at most 11 kW. Which is plenty to charge a vehicle over night. There are some 22 kW chargers around, but mostly in parking lots etc.
      Everything providing more, e.g. 50 or 60 kW usually can be found only on dedicated charging or service stations.
      A lot of those charges already are intelligent in a way that a bunch of them can be coupled, so few cars can charge at full power or more cars can charge at an automatically reduced power.
      The same technology can be used to control charging load to prevent grid peaks.
      Also, what may be important as well, but very often overseen. A lot of electric vehicles cannot even charge at those rates.

    • @joshuapk9808
      @joshuapk9808 3 роки тому

      @@alexanderkupke920 The newer EV's can take up to 350-400kW of power- that's 800 volts at 500 or so amps. You can find high capacity charging stations at some Porsche dealers.

  • @chrisretired5379
    @chrisretired5379 3 роки тому

    I thought that the interior side of the exit door of metering building should be a full width crash bar, for emergency egress. Instead of the handle ?
    Thanks for all the great videos ! From Alaska.

  • @pauljameson1
    @pauljameson1 3 роки тому

    So what is that buzzing sound at power stations and near low power lines? I’ve wondered that for many years.

  • @richardc1422
    @richardc1422 2 роки тому

    i have a question do you have to be a lineman 1st in order to become a cable spicer?

  • @fitybux4664
    @fitybux4664 2 роки тому

    9:50 Do enormous ZZZZZZZzzzzz scare the crap out of you as a lineman? "That transformer buzzing is like a tiger and it's just showing it's dominance." 😆

  • @mikeznel6048
    @mikeznel6048 3 роки тому +1

    Hey bud, nice to see ya again. Nice den you have there! That at the new place?

    • @Bobsdecline
      @Bobsdecline  3 роки тому +3

      Yea Mike great to see ya too! Yessir, that's the office at the new place 🍻

    • @mikeznel6048
      @mikeznel6048 3 роки тому +1

      @@Bobsdecline Beautiful man. Looks great!

  • @anoimo9013
    @anoimo9013 3 роки тому

    Hi Bob. its nice that you dont have to use clam meter but a fork. The substation you were in the video is a little bit noisy. Is that common? thanks

  • @CraigPater
    @CraigPater 5 місяців тому

    Interesting I go past a 60kv substation on a regular basis and I don't hear that buzzing or humming sound

  • @garyr7027
    @garyr7027 3 роки тому

    I got shocked 😬 thru my phone just watching... now that's some high voltage right there.

  • @NipkowDisk
    @NipkowDisk 3 роки тому

    SensorLink used to be located in Acme, Washington a while back- I knew one of the higher-ups there.

  • @James_Bowie
    @James_Bowie 3 роки тому

    Great stuff! Great review!

  • @rossthompson1635
    @rossthompson1635 3 роки тому +4

    Very interesting. Do you have to get safety approval from your company before using a new bit of gear like that?

    • @everyhandletaken
      @everyhandletaken 3 роки тому

      was wondering the same thing !

    • @Bobsdecline
      @Bobsdecline  3 роки тому +5

      It depends on the situation. In this case, I did speak with my company first. We already have work methods for similar gear and I did receive safety standard documentation

  • @ianmyers1593
    @ianmyers1593 3 роки тому +2

    Im a distribution meter electrician and we use the same amp tong. Great for checking CT'S and testing capacitor KVARS.

  • @LinemanUniverse
    @LinemanUniverse 3 роки тому

    Cool video man special effects awesome👌

  • @chadholmes7051
    @chadholmes7051 3 роки тому +1

    Only thing I thought could have been safer with testing the low volt side of the pad mount was using a single pin probe rather than a hook just seems like a lot of metal to have waving around those big terminals

  • @manmeetworld
    @manmeetworld 2 роки тому

    Do a whole video on load balancing

  • @Nathan15038
    @Nathan15038 3 роки тому

    Damn that looks like a very good kit and I have high hopes for it

  • @Aaron-zu3xn
    @Aaron-zu3xn 2 роки тому

    "shove it up....." is all i heard when i walked back into the room cleaning the house and i'm thinking "he's shoving what where?"

  • @justingodbey475
    @justingodbey475 3 роки тому

    Would love a suggestion on a long collapsing telescopic pole like you use in order to reach bees nests in the fall before they freeze and birds get to them. I just noticed you refer to it as a hot stick and I’ve never heard of or seen one but being made of fiberglass it should be fairly stiff still when fully extended. More so than plastic like I thought it was made of 🤦‍♂️. I don’t need it to be rated for electricity though so I wouldn’t need whatcha got there, but I never knew really knew what I needed before 🤷‍♂️😂. That looks like it would work a treat.

    • @Bobsdecline
      @Bobsdecline  3 роки тому

      I don't think they're are easily available to the public, but then again, I've never really tried to buy one outside of work!. I did see one for sale at a flee market one time!
      There are many different manufacturers including some that are made for arborists that lock together. I've also seen rigid measuring sticks that telescope in this way. Any of these would definitely work for knocking down old wasp nests if you could find one online

  • @sunwriter123
    @sunwriter123 3 роки тому +1

    Just curious if you've ever had to troubleshoot Radio Interference (RFI) caused by any of the following?
    Loose staples on ground conductor
    Loose pole top pin
    Ground conductor touching nearby hardware
    Corroded slack span insulators
    Guy touching neutral
    Loose hardware
    Bare tie wire used with insulated conductor
    Insulated tie wire on bare conductor
    Loose cross arm braces
    Lightning arrestors

    • @Bobsdecline
      @Bobsdecline  3 роки тому +3

      Yes, the most common by far would be the bare tie wire on insulated conductor or vice versa. Another common one I've seen is when conductors are touching and of the same potential, but the actual connection is a few feet away.
      Had a few from loose insulators/pins or cracked porcelain as well, but those ones usually fail before they get trouble shooted for RFI

  • @jbizzyb
    @jbizzyb 3 роки тому

    Depending on the manufacturer, I worked at the facility that made those transformers

  • @rickchapman9232
    @rickchapman9232 3 роки тому +1

    What was the highest voltage you have ever worked with?

  • @LuxAudio389
    @LuxAudio389 3 роки тому +1

    Is there an Amazon affiliate link?😉

  • @allezvenga7617
    @allezvenga7617 3 роки тому

    Thanks for your sharing

  • @billynomates920
    @billynomates920 3 роки тому +1

    i'm gonna blame youtube for missing this but probably my fault, truth be told.
    i liked the pulp fiction suitcase thing. was funny.
    edit: strapping your meter in to the passenger seat while your apprentice goes in the back with the other tools; there is no more high recommendation than that. = too funny.

  • @nixon2tube
    @nixon2tube 3 роки тому

    The one thing I kept thinking was why don't they make that display a LOT bigger so you can look at it comfy from a distance.

  • @cluelessfish
    @cluelessfish Рік тому

    4:46 Bruh forget using that silly stick thingy ya got gloves on just wack em on there with ya hands 🤣

  • @assassinlexx1993
    @assassinlexx1993 3 роки тому

    This is a great tool. Anything that keeps a lineman safe is wonderful.
    Is there a test system to make sure the unit is working correctly?
    Let's hope that was the last of the snow. After all we be missing the bug season. There is nothing like being in a bucket at night with the only light on. To have every bitting bug come because of the light.😡🦟🪰

  • @mikemhoon
    @mikemhoon 2 роки тому +1

    Not much has changed in the last 30 years! Looks a little safer than what we had, but basically the same. 🤷‍♂️

  • @mikefixac
    @mikefixac 2 роки тому

    Using a new tool and getting a reading of 0 Volts, it'd be hard for me to trust that, especially with that kind of voltage. Even working with 120 Volt residential, I'll try some other backup for voltage check.

    • @Bobsdecline
      @Bobsdecline  2 роки тому +3

      While that's a great point!... This product does have very strict and rigorous testing. I received copies of all testing records and certification for this equipment. A great way to confirm a zero reading (and should be done with any voltage measuring tool at each use if possible) is to check the device against a live wire as well .
      Cheers Michael! 👊

    • @mikefixac
      @mikefixac 2 роки тому

      @@Bobsdecline Thank you for getting back to me. You guys are my heroes, thanks for your videos.

  • @Odinsabenteuer
    @Odinsabenteuer 3 роки тому

    hi. can you share a link to your clear/mirrored? safetyglasses please? very intresting channel! greetings from germany!

    • @Bobsdecline
      @Bobsdecline  3 роки тому +2

      I'll see what I can find! I picked these ones up at a "Stihl" shop. That's what's engraved on the side. They were only 10 bucks and I love em. They are rebranded tho, I'll try and remember to let you know the manufacturer!

  • @matthewmiller6068
    @matthewmiller6068 3 роки тому

    For some reason I always expected substations and overhead lines all the cabling to be like 10s of thousands of amps...given I know just our furnace sucks up >100 amps at 240 volts. I know wattage and all that's only like 3A at 7200V and would scale down at even higher voltage but its hard to imagine how many houses and businesses are on a line it wouldn't add up anyway.

    • @Leo-pd8ww
      @Leo-pd8ww 3 роки тому +1

      Power loss in conductors is proportional to the current squared. Step up transformers raise the voltage and lower the current for transport. Transported power remains the same.

  • @tjairicciardi9747
    @tjairicciardi9747 3 роки тому

    great video

  • @Taylor-bx8op
    @Taylor-bx8op 3 роки тому

    Why does electricity humm???

    • @Ihaveanamenowtaken
      @Ihaveanamenowtaken 3 роки тому +4

      You’re hearing the laminated core of the transformer vibrating at line’s frequency.

    • @jeddavis8468
      @jeddavis8468 3 роки тому +1

      @corey Babcock The hum is a lower note here in Australia where I now live and other countries that use 50 HZ power. I'm from the US so the 60 HZ hum is familiar to me.

    • @petehiggins33
      @petehiggins33 3 роки тому

      It's called magnetostriction. The changing magnetic field in the transformer core causes it to expand and contract at twice the mains frequency hence generating sound.

    • @Leo-pd8ww
      @Leo-pd8ww 3 роки тому +1

      Because it's having a good day.

  • @ПостороннимВ-в1п

    Спасибо за труды и информацию 👍. Сколько стоит такие приборы?

  • @pmbjngls
    @pmbjngls 3 роки тому

    Looks like your wearing the salisbury electrical glove.

  • @reveal-lk6ip
    @reveal-lk6ip 3 роки тому +1

    Ну это напряжение 6-10 кВ, для линейных электромонтеров. Я один обслуживал четыре подстанции 110-35-10 кв, и приходилось делать переключения на всех напряжениях с открытыми разъединителями на открытых подстанциях. Well, this voltage is 6-10 kV, for linear electricians. I alone served four substations of 110-35-10 kV, and I had to make switchings at all voltages with open disconnectors in open substations.

  • @jolyonwelsh9834
    @jolyonwelsh9834 3 роки тому

    I take you guys for granted.

  • @lawrencemunyajaricha8876
    @lawrencemunyajaricha8876 Рік тому

    Bob can I have a way of getting intouch with u

    • @Bobsdecline
      @Bobsdecline  Рік тому

      Best way is DM on insta of FB 🍻

  • @MichaelRBaron
    @MichaelRBaron 3 роки тому +9

    I can't imagine taking the truck home every night. My neighbors would be pestering me to do government jobs nonstop!

    • @Shadi2
      @Shadi2 3 роки тому +3

      I'd be worried about someone breaking into it to steal tools

  • @wazza33racer
    @wazza33racer 3 роки тому

    Australia is now having a big problem with a glut of solar power in the middle of the day. Its gotten so bad, the grid is going to penalize customers for exporting too much power to the grid. Making sure that everything is accurate and accountable is going to be big issue going forward. Anything that makes all those checks and balances easier is always a bonus.

  • @roymercer6967
    @roymercer6967 3 роки тому

    It's current not amperage. Amps is the unit of measurement. I don't think amperage is a real word. With that said, I am fairly new to your channel and have already learned a lot. Clearly you are highly knowledgeable and experienced in this field and I really enjoy your content. Thanks for what you do.

  • @robertlitman2661
    @robertlitman2661 3 роки тому +1

    16:10 has me a bit uncomfortable. I know it's LV, but the exposed metal on that hook looks like it can exceed the clearances between phases. Of course, it looks different on my screen than it does to your eyes. Otherwise, nice kit.

  • @altonrowell8137
    @altonrowell8137 3 роки тому

    I use car jumper cables and stand in a puddle of water useing a radio shack multi meater.

  • @macdadstromboli2762
    @macdadstromboli2762 2 роки тому

    Got a question for you:
    You have all of that safety stuff on, which I am guessing is the requirements for doing whatever work you are doing. 👍
    Umm, but you have your necklace on? 🤔
    Isn't that an open invitation for major disaster?

  • @wouldntyouliketoknow9891
    @wouldntyouliketoknow9891 3 роки тому

    Wait, 69,000kV??? Like, 69MV?? roughly 69 times higher than the highest transmission voltage on earth? Or did you mean 69kV (standard sub-transmission voltage)

    • @Bobsdecline
      @Bobsdecline  3 роки тому

      Wouldn't you like to know ... 🤔Lol jk.
      Omg did I say 69000kv in the vid 😳

  • @fratfrat3146
    @fratfrat3146 Рік тому

    Hangi ülke?

    • @Bobsdecline
      @Bobsdecline  Рік тому

      Kanada!

    • @fratfrat3146
      @fratfrat3146 Рік тому

      @@Bobsdecline I have a dream to come to Canada:)) I also do high voltage work, our system is 30 kva. I have been in this sector for 15 years, but your network is very old, the high voltage network in turkey is different and new.

  • @shahidbashir8735
    @shahidbashir8735 3 роки тому

    Nice

  • @drewdunny5
    @drewdunny5 7 місяців тому

    Hopefully you get compensated properly.

  • @kirkkitchen9822
    @kirkkitchen9822 3 роки тому

    Single phase service!