Relay testing with self made testing kit. (English Subtitle)

Поділитися
Вставка
  • Опубліковано 28 лис 2024

КОМЕНТАРІ • 39

  • @tanumoychakraborty6900
    @tanumoychakraborty6900 3 роки тому

    Thankyou from WB,india please keep it up it is so useful for new site engineer like us.May God give you strength and happiness so that you can continue with this noble job of teaching.

  • @md.mehedihasan87
    @md.mehedihasan87 8 місяців тому +1

    Very helpful video

  • @sachinsinghal9
    @sachinsinghal9 3 роки тому

    I want to know about the wiring for phase overcurrent and earth fault current , three CTs are used for three phase , how are they connected for phase overcurrent and earth fault current detection.

  • @arnabchattoraj7444
    @arnabchattoraj7444 2 роки тому

    Great video sir... But one question... Jodi fault current above 3.3In hoi, tahole ki idmt r delay time, second stage delay time er cheye always beshi hbe? Oi reference point ta kivabe pabo?

  • @PalashDas-do7is
    @PalashDas-do7is 4 роки тому

    Good.go ahead

  • @engr.jamirulislam8910
    @engr.jamirulislam8910 3 роки тому

    Outstanding sir !!!

  • @mehadyhasan9245
    @mehadyhasan9245 Рік тому +1

    ❤❤❤

  • @kohchingyih671
    @kohchingyih671 4 роки тому

    Hi Sir, may I know the rating of the variac you used? If we use 300Va step down transformer 220v / 12v, from your video I understand that 46V and primary side of step down transformer is equal to 25A at secondary side. Base on the calculations, the ampere of primary side of the step down transformer is 300Va/46v = 6.52A. it mean the rating of the variac must be bigger that 6.52A to generate 25A at step down transformer secondary side it is? If convert to Va, it mean we need to choose 1.5kva variac?

    • @bdprofessionals-8474
      @bdprofessionals-8474  4 роки тому +1

      Hello there, the secondary current which is 25A in this case is being drawn in short circuit condition(Low voltage side). Since the %Z of this transformer is about 21% thus in short circuit condition if you apply 21% x 220 = 46 volt at Primary it will cause to draw rated current at every side. Now what is the rated current of a 220/12V, 300 VA transformer? It's 300/220 = 1.36 A at primary and 300/12=25A at secondary. Thus in short circuit condition (at Low voltage side) applying 46 volt in primary will cause to draw that rated 1.36A through primary. If the %Z for example is 50% for a typical Transformer then 50% x 220 = 110 V will cause to flow that 1.36 A on that typical transformer. Thus primary voltage is dependent on %Z for Low voltage short circuit condition. Thus you need 1.36Ax220V=300 VA Variac. So you need at least same size of Variac as Transformer. However, I am using 300 VA transformer with 500 VA Variac. Hope you will understand. For any further quary Please. let me know

    • @kohchingyih671
      @kohchingyih671 4 роки тому +1

      @@bdprofessionals-8474 Thank a lot. Now I understand already. Really thank for your great explanation.

  • @sachinsinghal9
    @sachinsinghal9 3 роки тому

    1. Can u please explain about the connection between transformer and relay. Which relay terminals to use.
    2. What will be the VA of th autotransformer , equal to VA of 230/12V transformer?

    • @bdprofessionals-8474
      @bdprofessionals-8474  3 роки тому +1

      Hello Mr. Singhal, Here is what you have asked for:
      1. Connection between Transformer and Relay is as "series Load" where the load resistance is the contact/coil (Analog Input contact/coil i.e. Current, Voltage etc. of the relay) resistance of the relay which is actually Zero. Thus transformer experience Zero impedance at secondary and thus Short Circuit operation is occurred. This transformer is doing the same job as secondary of any high voltage CT does for the relay.
      2. Transformer VA depends upon the output Current (Current Injection) limit that you desire. For example as i have used here 300 VA with 12 Volt Secondary thus i can draw 300/12=25 Ampere at the short circuit condition.
      If still you have any confusion or further query feel free to comment.
      ---bdprofessionals

    • @sachinsinghal9
      @sachinsinghal9 3 роки тому

      @@bdprofessionals-8474 Thank you for the detailed reply. I want to know about the VA of the auto transformer also, is it same as step down transformer? Thanks in advance.

  • @ranjansahu2362
    @ranjansahu2362 4 роки тому

    Very nice sir.... Plz upload p141 realy testing...
    Plz explain about the transformer used here...

    • @bdprofessionals-8474
      @bdprofessionals-8474  4 роки тому +1

      300 VA, 220/12 volt transformer

    • @ranjansahu2362
      @ranjansahu2362 4 роки тому

      @@bdprofessionals-8474 got it sir.. but how to get 25amp... Thats little confusing...
      Kindly explain me sir..

    • @bdprofessionals-8474
      @bdprofessionals-8474  4 роки тому +1

      Short secondary side. At this situation you need to supply impedance voltage at primary (220 volt side) which is here near 50 volt

  • @atiqulislam6318
    @atiqulislam6318 3 роки тому

    Please upload 7SR relay

  • @engr.jamirulislam8910
    @engr.jamirulislam8910 3 роки тому

    Please upload 850 and 845 relay setting accordingly kindly sir !!!

  • @shailendrasinghrajawat1619
    @shailendrasinghrajawat1619 3 роки тому

    Pls make video in hindi or English

  • @sagormohammad349
    @sagormohammad349 4 роки тому

    LED kivabe settings dibo setao dekhayen

  • @soumya2221
    @soumya2221 4 роки тому

    Kmn kore oi secondary onjection kit ta banabo r koto va rating r.. Pls jodi ktu bolen

    • @bdprofessionals-8474
      @bdprofessionals-8474  4 роки тому +3

      Need 1 Variac (0-250 volt) and a transformer. If you buy 300 VA with secondary 12 Volt XF then you can draw 300/12= 25 Amp Current. Thus for 5 A CT secondary you can test upto 5*In Protection settings. And these all are available at Nababpur, Dhaka.

    • @soumya2221
      @soumya2221 4 роки тому

      @@bdprofessionals-8474 transformer secondary 12v and ov short kore... Oi duto terminal teke 2 to wire relay protection ct terminal a dite hobe to sir??

    • @bdprofessionals-8474
      @bdprofessionals-8474  4 роки тому +1

      Protection terminal coil has almost zero ohm. Thus if you connect xf secondary to the 41&42 (for micom) xf secondary will be short circuited

    • @soumya2221
      @soumya2221 4 роки тому

      @@bdprofessionals-8474 thanx a lot sir

  • @ArifulIslam-wj3sc
    @ArifulIslam-wj3sc 4 роки тому

    Very nice

  • @engr.mehdyhasan
    @engr.mehdyhasan 4 роки тому

    Can I test 33kv CT like Current Injector?

    • @bdprofessionals-8474
      @bdprofessionals-8474  4 роки тому +1

      Regardless of voltage level you can check any CT. You only need to ensure the supply of primary current of the CT. With this kit you can test but need a large VA transformer

    • @engr.mehdyhasan
      @engr.mehdyhasan 4 роки тому +1

      @@bdprofessionals-8474 Sir কত VA হলে ভাল হবে? ৩৩কেভি সিটির প্রাইমারী তে কি ট্রান্সফারের output Voltage দিবো? Diagram দিলে খুশি হতাম

    • @bdprofessionals-8474
      @bdprofessionals-8474  4 роки тому +1

      If you want to test a 400/5 ampere CT then to have 400 amp at 12 volt need 400×12=4800 VA

    • @engr.mehdyhasan
      @engr.mehdyhasan 4 роки тому

      Thank you sir, can you make video about trouble shooting of PFI?

  • @atiqulislam6318
    @atiqulislam6318 3 роки тому

    Please upload 7SR relay