all parameter except for these - [Standard mot. freq] (bFr), page 42 - [HMI command] (LCC), page 62 - [PIN code 1] (COd), (terminal access code), page 104 - The parameters in the [COMMUNICATION] (COM-) menu - The parameters in the [MONITORING] (SUP-) menu
Using FCS will reset all parameters on the drive except for these: [Standard mot. freq] (bFr), page 42 - [HMI command] (LCC), page 62 - [PIN code 1] (COd), (terminal access code), page 104 - The parameters in the [COMMUNICATION] (COM-) menu - The parameters in the [MONITORING] (SUP-) menu Please contact your local Schneider Electric support team if you need further assistance.
It's very stupid they don't give any warning when we push the button for 3 secs to go to local mode it will reset all of the parameter to factory setting.... ABB has a cheaper price for the same vfd class but they can switch between local and remote easily without need to reset all of the parameter to factory setting Really frustrating and IDK what to say about this design🤦
Very Helpful ! THANKS
this vedio helped to solve my vfd problem today
THANK YOU !! i needed this so much =D
Thank you.
so much very help full video.
I have a problem SCF3 ??
What does this blinking menas ?
Thank you for your message. We house most of our documentation in a virtual database here: www.se.com/ww/en/download/. If this does not address your concerns, please reach out to a technical support person in your location.www.se.com/ww/en/work/support/country-selector/contact-us.jsp
Mine is a ATV12 and it is stuck showing freewheel mode . I’m lost. I can’t get it to rdy without local mode or rdy with no led’s on . Whew
Does this remove all settings?? I just wanted to change the speed now I'm stuck
all parameter except for these
- [Standard mot. freq] (bFr), page 42
- [HMI command] (LCC), page 62
- [PIN code 1] (COd), (terminal access code), page 104
- The parameters in the [COMMUNICATION] (COM-) menu
- The parameters in the [MONITORING] (SUP-) menu
Using FCS will reset all parameters on the drive except for these:
[Standard mot. freq] (bFr), page 42 - [HMI command] (LCC), page 62 - [PIN code 1] (COd), (terminal access code), page 104 - The parameters in the [COMMUNICATION] (COM-) menu - The parameters in the [MONITORING] (SUP-) menu
Please contact your local Schneider Electric support team if you need further assistance.
I have no idea what this is. You seem to link to this video where it has no relevance whatsoever.
Merci
Thank u sir
Today i solve this problam
It's very stupid they don't give any warning when we push the button for 3 secs to go to local mode it will reset all of the parameter to factory setting....
ABB has a cheaper price for the same vfd class but they can switch between local and remote easily without need to reset all of the parameter to factory setting
Really frustrating and IDK what to say about this design🤦
Can you not just hold the “mode” button for 3 seconds and it will take you back to remote?
On some atv312 series yes on what I believe older units no. I have two, one that does it each way