A Beginners Guide To DALI Lighting Controls

Поділитися
Вставка
  • Опубліковано 8 лют 2025

КОМЕНТАРІ • 50

  • @efixx
    @efixx  Рік тому +9

    Continue the series
    DALI wiring
    ua-cam.com/video/XmucYqxYEH4/v-deo.html
    Lighting control techniques
    ua-cam.com/video/XmucYqxYEH4/v-deo.html

  • @kennymills7442
    @kennymills7442 Рік тому +4

    Ive just started as a commissioning engineer and currently doing a lot of training with one of the biggest players in the lighting controls market. Really interesting work.

  • @syproful
    @syproful Рік тому +3

    knx and dali is a dream and the absolute standard for the last 10years in most premium houses. This is a great video.

  • @craigbuist4636
    @craigbuist4636 Рік тому +2

    DALI is great kit and installed in all of our projects. A lot of people don’t know about it which has always surprised me with all of its benefits. Great video guys.

  • @BATESYHD
    @BATESYHD Рік тому +1

    Work in one of the biggest shopping centres in Europe and it’s everywhere, really looking forward towards future videos!!!

  • @vitalii.mizeraka
    @vitalii.mizeraka Рік тому +1

    It's great that you've started series of videos with DALI. Your fan, boys! Fault finding with this system would be beneficial for your channel.

  • @TrevorThompson-d5o
    @TrevorThompson-d5o 4 місяці тому

    Very useful! I've been in the lighting industry a long time and this was eloquent.

  • @Goabnb94
    @Goabnb94 8 місяців тому

    A common arrangement in NZ has been to run normal cable (red as active) and then a separate 2 core cable (red and white) for DALI control. Which leads to the situation you mention - possibility of DALI becoming live to mains voltage. Supposedly it won't damage equipment, but absolutely isolate properly.
    I did one job where we ran 4 core and earth cable, with phase 2 and 3 being used for DALI, and installed that into sockets that had extra pins for it too. Prep the driver on the ground, plug it in and install into grid ceiling, super easy. Some people don't do that because they think its cheaper to go with two separate cables, but the labour savings more than make up for it.

  • @tombrown3533
    @tombrown3533 Рік тому

    To get around LED dimming in a domestic setting ive used dali drivers for downlights and dimmed on a standard 1-10v dimmer. Works a treat. Even better the drivers went spare on the day job!

  • @anthonygirgis144
    @anthonygirgis144 Рік тому +1

    great video! although i do not have an engineering background (stage lighting background) this video was super helpful to understand DALI

  • @noura4701
    @noura4701 11 місяців тому

    Thank you for the great explanation and visuals! very helpful and entertaining at the same time

    • @efixx
      @efixx  11 місяців тому

      Glad it was helpful!

  • @pjcamp1on
    @pjcamp1on Рік тому +3

    Not all Dali systems can handle 64 input devices, ie PIR's switch interfaces and scene plates so check with the system provider.
    Also Dali systems can have emergency monitoring so if you have a Dali fitting with a Dali driver and Dali inverter that fitting will count as 2 addresses of you 64.

  • @snoopftw8448
    @snoopftw8448 Рік тому +2

    At 6:00 you said that the Dali signal isn't polarity sensitive. I can guarantee you that if you mix the polarity it will not work. I always use black as minus (like in dc) and grey as positive. If i add another light where i switch it to grey aas minus and black as positive it will not work, i know from experience having to open several lights to figure out which one the apprentice miswired.

    • @stefanoberg8583
      @stefanoberg8583 Рік тому +2

      A Dali device that is not adding power to the system (led driver, panel, sensor, relay etc.) is not polarity dependent. It is only in the rare cases where you have two power supply then they needs to be connected to match polarity. Saying that I do agree that in any system having a consistent polarity as you said black as minus is best practise regardless of polarity sensitivity or not. Most manufacturers have +/- or D1/D2 printed on the connectors to aid installers with this. From your experience with fittings and problems with polarity it sounds like the drivers them self provides power to the system and yes then they must be connected with the same polarity.

  • @davidclark3603
    @davidclark3603 Рік тому +7

    Thank god I retire next year. I can't wait!!!!!

  • @johnwaby4321
    @johnwaby4321 Рік тому +1

    Very interesting.

  • @calmeilles
    @calmeilles Рік тому +1

    I've heard people complain that the DALI protocol is incredibly slow. Well compared with DMX that's true but at 1,200 baud it'll still be working 600 times faster than you can flick switches!

  • @davidomeara4704
    @davidomeara4704 9 місяців тому

    Fantastic video

    • @efixx
      @efixx  9 місяців тому

      Thanks! 😃

  • @steverob9895
    @steverob9895 Рік тому +1

    Any advice on fault finding or faulty components. We have a building with dali controls, 1 controller failed last year leaving the whole building in darkness,its taken ages to get parts as the system is an old one.

    • @stefanoberg8583
      @stefanoberg8583 Рік тому +2

      The basic function of dali is the broadcast feature - in fault finding a dali power supply and a slider/rotary or the combo is a effective and basic way of testing - it will identify any loads that will not respond making it easier to identify the problem. Next step would be a pc software to connect and diagnose. Question what system do you have?

  • @filipgejdos7075
    @filipgejdos7075 20 днів тому

    please what do u using dor dimming in 8:12 thanks so much

  • @mpalaskokkalis1476
    @mpalaskokkalis1476 Рік тому

    Perfect 👌

  • @Vikingza
    @Vikingza Рік тому

    How would you install DALI lighting controls on lights in a house with a 3 phase incoming supply?

  • @pedrosmits
    @pedrosmits Рік тому +1

    DALI combined with EIB/KNX is also an excellent solution.

  • @aadilmapkar6524
    @aadilmapkar6524 Місяць тому

    I need to know if Dali system can be connected using 1.5sqmm electrical cable or special cable is required

    • @efixx
      @efixx  Місяць тому

      Regular cable is fine.

    • @aadilmapkar6524
      @aadilmapkar6524 Місяць тому

      What is purpose of dali cable if not required??

  • @rafenden
    @rafenden 3 місяці тому

    Will Dali bus work on AWG23 (Cat 7 cable)?

  • @davidclark3603
    @davidclark3603 Рік тому

    How do we maintain this equipment? In a few years time, it is going to break down. Is the equipment standardized,or is it esoteric to each manufactures,? I. E. Can we just go to the van and get a new module?

    • @stefanoberg8583
      @stefanoberg8583 Рік тому

      As many other things this depends on the original installation and they system being used - I have mostly used the Helvar router system and if a device goes missing ( breaks) and you connect a replacement the router will assume the new one is a replacement. This is a option you can disable. Honesty most time I just connect to the system and make sure any devices are programmed as intended, today I think this is true for most larger scale control systems.

  • @glenwoofit
    @glenwoofit Рік тому

    Interesting

  • @vincentbyrne5000
    @vincentbyrne5000 Рік тому

    Hi Guys do you know of any training concerning DALI

  • @FirstDan2000
    @FirstDan2000 Рік тому

    My only gripe with Dali systems is the 6 pin plug. The pins are grouped into 2 groups of 3 - one part being black (the mains wiring) and one part being blue (the Dali wiring) BUT the blue part isn't only for Dali, it also has the permanent live.
    And as I recently had to correct far too many plugs incorrectly connected my gripe is really big. - Why did someone decide the blue part would have 3 terminals, why not just for the 2 Dali conductors?
    The flex7 plugs are better. You simply have to read the legend embossed into the lid.

  • @lumo2981
    @lumo2981 Рік тому

    Can you do a LUTRON guide next? Don’t blame you if you back heel the request 😂

    • @efixx
      @efixx  Рік тому

      Homework’s or Ra2 ?

    • @lumo2981
      @lumo2981 Рік тому

      @@efixx Quantum is the system I’m dealing with. One of their commercial lighting products

  • @Ironic1950
    @Ironic1950 Рік тому

    Light circuits are invariably spur-wired, not ring circuits...

  • @brianpiddock6074
    @brianpiddock6074 Рік тому

    What's wrong with DMX

    • @efixx
      @efixx  Рік тому

      Nothing but Dali had more flexibility for wiring.,

    • @syproful
      @syproful Рік тому

      Baudrate is much slower, meaning you can bundel he data lines with the current wires. It's the best system there is because of this. It's balance of speed and reliability.

    • @mfx1
      @mfx1 Рік тому

      @@syproful DMX is differential so can be run alongside conductor wires as well, many claim it's a bad ide but that's complete rubbish. The main issue with DMX is lack of error checking/correction, it's normally one way (unless you use RDM which is a clunky bodge) and doesn't have built in features for zone control. It's not specifically the baud rate with Dali but the fact that it uses fairly high voltage signalling (0-16v).

  • @pawenozynski1038
    @pawenozynski1038 11 місяців тому +1

    "This system worked for 100s of years" I guess he is also hundreds years old so with electricity...

  • @AmauryJacquot
    @AmauryJacquot 6 місяців тому

    wonder why did they invent DALI when DMX512 existed already

  • @damienheads7151
    @damienheads7151 Рік тому +4

    I have to work with this shit and it’s bloody awful

  • @thecleanspark3335
    @thecleanspark3335 Рік тому

    Mentioning rings almost ruined the video.