API 2000 Calculations: Part 3 - PEMY Consulting (Phil Myers)

Поділитися
Вставка
  • Опубліковано 29 сер 2024

КОМЕНТАРІ • 13

  • @naufalhadi8684
    @naufalhadi8684 3 місяці тому

    Hi, you may use vlookup function for unit change instead of nested if function.

  • @samirst3794
    @samirst3794 Рік тому +4

    Can you send me the excel application please

  • @ratnadeep30
    @ratnadeep30 Рік тому +4

    How do i get this spreadsheet ?

  • @mohammadirfan8848
    @mohammadirfan8848 Рік тому

    Can you please guide me for selecting correct size of pressure and vaccuum valves for bulk fuel storage tanks.

  • @cacaaksin9648
    @cacaaksin9648 4 роки тому

    Thank you for your detailed video!
    In NFPA (edition 2018) it says:
    22.7.3.10.3 The flow capacity of tank venting devices less than
    8 in. (200 mm) in nominal pipe size shall be determined by
    actual test. These tests shall be permitted to be conducted by a
    qualified, impartial outside agency or by ...
    22.7.3.10.4* The Flow capacity of tank venting devices equal to
    or greater than 8 in. (200 mm) nominal pipe size, including
    manway covers with long bolts, shall be determined by test or
    by calculation. If determined by calculation, the opening pres‐
    sure shall be measured by test, the calculation shall be based on
    a flow coeficient of 0.5 applied to the rated orifice, the rating
    pressure and corresponding free orifice area shall be stated,
    and the word calculated shall appear on the nameplate.
    Did you consider the fact (as it says above) that the vent calculation is applicable only for equal or greater than 8 inches?

    • @chelladuraiboopathy7029
      @chelladuraiboopathy7029 4 роки тому

      How to determine the size of the vent then ? If this formula is applicable only for sizes 8" and more, how would i know that the results will be more / less than 8" ? Could you help on this please ?

    • @cacaaksin9648
      @cacaaksin9648 4 роки тому

      @@chelladuraiboopathy7029 I'm open for suggestions on how to do or maybe if you want to share how you calculated it. I compared this equation with API 200 D18 equation which gives you a flow equation through the nozzel. But the NFPA equation seems to be more conservative. Another option I have considered is with Crane table B-12 it gives you pressure drop of air for certain vent diameters at a certain air flow, so you can choose the vent depending on your maximum allowable pressure.

    • @hafizjessore
      @hafizjessore Рік тому

      NFPA which one used , NFPA 30 ?

  • @MaxxEngineers
    @MaxxEngineers 3 роки тому

    When the IFR tank has complied with the center and peripheral circulations vents in Appen H, do we have to consider the normal and emergency vents in API 2000?

  • @chueneelvin2696
    @chueneelvin2696 4 роки тому +2

    Hi Can i please have the excel spreadsheet.

    • @pemyconsulting2955
      @pemyconsulting2955  4 роки тому +1

      If you are interested in licensing or purchasing a copy of the PEMY API 2000 Spreadsheet please contact us at (925) 302-6706, or email brock@pemyconsulting.com

    • @aijaz02
      @aijaz02 4 роки тому +1

      @@pemyconsulting2955 u can get this model using hysys and also excel avaiable and API 2000 also avaiable.

    • @chelladuraiboopathy7029
      @chelladuraiboopathy7029 4 роки тому

      @@pemyconsulting2955 How much do you charge for this spreadsheet ?