🎯 Key points for quick navigation: 00:05 *⚙️ Introduction to Drive Setup* - Introduction to the SINAMICS G120 drive setup with focus on modular components, - Explanation of the basic operator panel (BOP) and intelligent operator panel (IOP) for parameter settings, - Mention of equipment used including control unit CO240 E2, training module, and Siemens motor. 01:30 *🛠️ Resolving Communication Errors* - Addressing common buffer error due to unconnected control unit, - Procedure to change communication protocol by modifying parameter p2030 to resolve error, - Restarting training mode to apply changes and verifying successful error resolution. 03:38 *🔄 Factory Reset and Initial Parameters* - Executing a factory reset to ensure correct parameter settings, - Selection of application class and standard motor norm for drive control, - Importance of motor plate information for correct drive parameter setup. 05:32 *🔍 Setting Specific Motor Parameters* - Detailed input of motor specifics including voltage, current, and frequency, - Explanation of motor cooling type and control method configuration, - Use of automatic parameterization for Siemens motors. 09:10 *🎛️ Parameter Macro and Motor Identification* - Description of parameter macros and selection of Macro 12, - Importance of ramp settings and motor identification parameter p1900, - Verification of settings through manual and automatic control modes. 11:34 *✅ Final Testing and Conclusion* - Testing drive-motor communication in manual mode and using switches, - Successful operation confirms correct setup and absence of wiring errors, - Emphasis on accurate motor plate data and wrap-up of setup process. Made with HARPA AI
Hola, se puede guardar la parametrización que has realizado al variador en el panel operador (BOP o IOP) y luego descargarlo en otro variador. Esto se utiliza normalmente cuando tienes varios motores con iguales características y para no estar parametrizando individualmente, solo parametrizas el primero y luego puedes guardar esa parametrización en el panel operador y descargarlo en los otros variadores, ya que la parametrización se almacena en la unidad de control. Lo puedes visualizar a partir de la pagina 453 del manual que puedes descargar en la descripción.
Tengo una consulta que me ha abordado recientemente, con el programa Sarter y Step7 usando un telegrama PZD 6/6, querría enviar la consigna de velocidad en Hz a un g120 con profinet io, como tendría que hacer la configuración para controlar la velocidad.
Hola, el manual adjunto en la descripción puedes verificar los telegramas y si quieres hacer la configuración por profinet lo puedes visualizar en el siguiente enlace: ua-cam.com/video/mabVWSZm0BI/v-deo.htmlsi=v1qPH6_V9hRIsIAd
Hola, puedes visualizar el diagrama de conexión en el manual adjunto en la descripción, si no requieres la velocidad en manual con un potenciómetro, puedes utilizar la macro de consignas fijas
Hola , no es recomendable, ya que al parametrizar el variador se tiene que poner los datos de la placa del motor. Una recomendación es revisar bien la parametrización del consumo de corriente
Lo intento configurar y no puedo en mi caso tengo una entradas digital de puesta en marcha y otra analógicas para regulación de la frecuencia atraves de un modulo analógicas Siemens que gobiernu el programa scada. mi duda es si tengo que cambiar él modo de comunicación? Ya que en automático no me funciona él variador.
Hola, en el manual hay una macro de conexión que habilita el protocolo de comunicación y con una entrada digital puedes cambiar por si lo quieres controlar desde un PLC o desde el mismo variador con sus propias entradas
tengo un detalle, cuentro con 3 botones para las velocidades, pero no me reconoce las entradas digitales, solamente me reconoce el boton de paro, y las demas no las reconoce, cual es el parametro o como puedo configurarlas, saludos.
Hola, en este caso si tienes la unidad de control CU240E-2 puedes utilizar la macro 3 : "sistemas transportadores con 4 frecuencias fijas" , lo puedes visualizar en el manual adjunto en la descripción en la pag.117. Por otro lado, para configurar las entradas digitales la información se encuentra a partir de la pag.229 del manual
Hola, la diferencia es que el variador SINAMICS G120X se utiliza para las aplicaciones de bombeo , ventilación y compresores. Lo puedes visualizar mejor en el siguiente enlace : ua-cam.com/video/X04UqFQInfA/v-deo.htmlsi=fDak44ypjLZXyQgu
Bom dia, estou com o inversor G120 Controlado por uma entrada analógica. P1080=0 P1082= máxima do motor (1800RPM) Para macro 12 Problema é que ele da erro quando passa de 40 HZ. Já resetei várias vezes e não consigo fazer ele modular de 0HZ A 60 HZ. Me ajuda 🙏🏽
Hola, el error que aparece lo puedes buscar en el manual adjunto en la descripción en el apartado de "Lista de alarmas y fallos", donde podrás encontrar la causa del fallo y como solucionarlo. Asimismo, comprueba los datos de la placa del motor con la parametrización.
🎯 Key points for quick navigation:
00:05 *⚙️ Introduction to Drive Setup*
- Introduction to the SINAMICS G120 drive setup with focus on modular components,
- Explanation of the basic operator panel (BOP) and intelligent operator panel (IOP) for parameter settings,
- Mention of equipment used including control unit CO240 E2, training module, and Siemens motor.
01:30 *🛠️ Resolving Communication Errors*
- Addressing common buffer error due to unconnected control unit,
- Procedure to change communication protocol by modifying parameter p2030 to resolve error,
- Restarting training mode to apply changes and verifying successful error resolution.
03:38 *🔄 Factory Reset and Initial Parameters*
- Executing a factory reset to ensure correct parameter settings,
- Selection of application class and standard motor norm for drive control,
- Importance of motor plate information for correct drive parameter setup.
05:32 *🔍 Setting Specific Motor Parameters*
- Detailed input of motor specifics including voltage, current, and frequency,
- Explanation of motor cooling type and control method configuration,
- Use of automatic parameterization for Siemens motors.
09:10 *🎛️ Parameter Macro and Motor Identification*
- Description of parameter macros and selection of Macro 12,
- Importance of ramp settings and motor identification parameter p1900,
- Verification of settings through manual and automatic control modes.
11:34 *✅ Final Testing and Conclusion*
- Testing drive-motor communication in manual mode and using switches,
- Successful operation confirms correct setup and absence of wiring errors,
- Emphasis on accurate motor plate data and wrap-up of setup process.
Made with HARPA AI
Excelente video. Gracias por la informacion.
Gracias Martin, excelente video 😊
Thanks for your great effort. I learned a lot from the video
Gracias, buen video!
❤
Buen video!!!....no me arranca el motor....suena que enciende el variador pero no tengo frecuencia de trabajo
Hola, intenta realizar el control en modo manual con el botón hand auto para descartar problemas de cableado
Muito boa a explicação, se for para gravar como eu faria
Hola, se puede guardar la parametrización que has realizado al variador en el panel operador (BOP o IOP) y luego descargarlo en otro variador. Esto se utiliza normalmente cuando tienes varios motores con iguales características y para no estar parametrizando individualmente, solo parametrizas el primero y luego puedes guardar esa parametrización en el panel operador y descargarlo en los otros variadores, ya que la parametrización se almacena en la unidad de control.
Lo puedes visualizar a partir de la pagina 453 del manual que puedes descargar en la descripción.
La entrada analógica le puedo meter de 4-20ma? O hay que cambiarle algún parámetro para que lea corriente?
Hola, lo puedes verificar en la página 104 del manual adjunto en la descripción, hay un interruptor para AI0 , AI 1 para V o mA
Tengo una consulta que me ha abordado recientemente, con el programa Sarter y Step7 usando un telegrama PZD 6/6, querría enviar la consigna de velocidad en Hz a un g120 con profinet io, como tendría que hacer la configuración para controlar la velocidad.
Hola, el manual adjunto en la descripción puedes verificar los telegramas y si quieres hacer la configuración por profinet lo puedes visualizar en el siguiente enlace:
ua-cam.com/video/mabVWSZm0BI/v-deo.htmlsi=v1qPH6_V9hRIsIAd
Hola,
Como podria conectar al equipo una parada de emergencia?
Es necesario que la parada sea en Hand o auto..
Hola , desde la pág. 297 del manual puedes ver la conexión de la parada de emergencia.
Puedo hacer cambio de giro sin utilizar las entradas digitales, solo con el mismo panel desde algun parametro u algo?
Hola, en el manual revisa el parámetro P1110
Hola buenas trades , tengo el variador sinamics g120 pero no me habilita la opcion manual ..
Hola , con el botón Hand auto puedes habilitar la opción manual para tener el control desde el panel operador
Hola, que bornes tengo que conectar entre si para que que la marcha sea automatica y no manual?
Hola, puedes visualizar el diagrama de conexión en el manual adjunto en la descripción, si no requieres la velocidad en manual con un potenciómetro, puedes utilizar la macro de consignas fijas
Hola buenas tengo una consulta, podria usar un variador de 3kw en un motor de 4kw haciendo este funcionar a menos revoluciones?
Hola , no es recomendable, ya que al parametrizar el variador se tiene que poner los datos de la placa del motor. Una recomendación es revisar bien la parametrización del consumo de corriente
Saludos...Felicitaciones..
Algún contacto para hacer una consulta... gracias..
Hola , puedes enviarme un correo a magallaneshierromartin@gmail.com
Lo intento configurar y no puedo en mi caso tengo una entradas digital de puesta en marcha y otra analógicas para regulación de la frecuencia atraves de un modulo analógicas Siemens que gobiernu el programa scada. mi duda es si tengo que cambiar él modo de comunicación? Ya que en automático no me funciona él variador.
Hola, en el manual hay una macro de conexión que habilita el protocolo de comunicación y con una entrada digital puedes cambiar por si lo quieres controlar desde un PLC o desde el mismo variador con sus propias entradas
MANUAL SINAMICS G120 :
www.mediafire.com/file/lqcoffdzyun3tiy
Useful
tengo un detalle, cuentro con 3 botones para las velocidades, pero no me reconoce las entradas digitales, solamente me reconoce el boton de paro, y las demas no las reconoce, cual es el parametro o como puedo configurarlas, saludos.
Hola, en este caso si tienes la unidad de control CU240E-2 puedes utilizar la macro 3 : "sistemas transportadores con 4 frecuencias fijas" , lo puedes visualizar en el manual adjunto en la descripción en la pag.117. Por otro lado, para configurar las entradas digitales la información se encuentra a partir de la pag.229 del manual
Cual es el parametro para variar la frecuencia desde el BOP estimado?
Hola , lo puedes realizar activando el botón hand auto
Amigo hola hise, todo lo del video y el SETPOIN no me manda datos, ayuda
Falto modificar laa rpm, a mi me paso
Cual es la diferencia entre este y el G120X
Hola, la diferencia es que el variador SINAMICS G120X se utiliza para las aplicaciones de bombeo , ventilación y compresores. Lo puedes visualizar mejor en el siguiente enlace :
ua-cam.com/video/X04UqFQInfA/v-deo.htmlsi=fDak44ypjLZXyQgu
Bom dia, estou com o inversor G120
Controlado por uma entrada analógica. P1080=0
P1082= máxima do motor (1800RPM)
Para macro 12
Problema é que ele da erro quando passa de 40 HZ. Já resetei várias vezes e não consigo fazer ele modular de 0HZ A 60 HZ.
Me ajuda 🙏🏽
Hola, el error que aparece lo puedes buscar en el manual adjunto en la descripción en el apartado de "Lista de alarmas y fallos", donde podrás encontrar la causa del fallo y como solucionarlo. Asimismo, comprueba los datos de la placa del motor con la parametrización.
Que significa la X ?
Hola, cuál es la "X" que mencionas