Arc Flash Labeling Strategies - Keeping it Simple!

Поділитися
Вставка
  • Опубліковано 23 січ 2025

КОМЕНТАРІ • 6

  • @socialedukation4511
    @socialedukation4511 Рік тому

    Thank you so much .I am from India but working in Saudi Arabia ..good course...sir..This course to be covered more about Shock protection boundaries...

  • @erasmolopez5679
    @erasmolopez5679 11 місяців тому

    Great Job, very clear

  • @rublar75
    @rublar75 4 роки тому

    38:50 - I encourage implementing & standardizing a 10'-0" LAB. This just gives the worker room and peace of mind. Keep out those Unqualified persons and that way if they do want in, they would have to be accompanied.

    • @bobcocampo
      @bobcocampo 3 роки тому

      What is the cal/cm2 of metal sheets based on material and thickness?

  • @mj625
    @mj625 5 років тому

    I have a question about AF labels on transformers. The incident energy calculation will typically be highest when calculations are based on the secondary side of a step down transformer. However, the shock protection value should be based on the higher voltage, which would be the primary side. We have transformers that are 25K on the primary and 480 on the secondary. Have you ever seen software that can produce information on a sticker that lists the highest incident energy (for secondary side), but also shows shock protection requirements based on the high primary voltage?

  • @bobcocampo
    @bobcocampo 3 роки тому

    What is the cal/cm2 rating of metal sheets