congratulations for your great job of teaching others now that this technology is entering new york city due to its high demand and few technicians to make repairs congratulations although I don't speak Spanish but I understood your concern why others learn repairs and how to identify the errors and solve it thanks
Hi. Bon mj I am your subscriber Thank you so much your videos is Very informative and I am also working in daikin Mitsubishi LG O.gerenal vrv & non vrv air conditioner I have 8years experience Installation and maintenance
Hello, we see it as a simple repair, but it is a job that takes several hours and knowing or having the capacity and the original parts to solve the error because it is not working and its replacement. I need you to teach how to solder the pressure switches so as not to damage them in the installation or silver solders the vacuum and recharge the unit with freon new minds because it is not in the video the freon leaks into the atmosphere it is not collected for its new uses another Once it is loaded with new freon and how to load it and know when it is at its normal capacity. Thanks a lot
Try to check R1T (for ceiling cassette,air thermistor is seal type,remove the wire clip and measure) Example temperature 30° is 16k ohm+- temperature 10° is 40k ohm+-
@@BonMj Thank you very much for your answer. It was corroded. I replaced it. I gave a value of 20k (in 25C, it is about 16k in 30C). The air conditioning started to cool but only for 10-15 minutes. Later, the outdoor unit turns off and the indoor unit only acts as ventilation, no cooling. After disconnecting the power and connecting, the cooling works again for 10-15 minutes and turns off (and the room is still hot). Heating seems to be working normally. Do you have a solution?
Yes the Refrigerant will leak out.. Anytime you tap into a refrigerant system you would need to reclaim/recover the refrigerant.. This is one of my major gripes with Daikin, just about every other manufacturer uses a 1/4 flare male/female for the pressure switches yet Daikin still have this ridiculous setup which makes you recover all refrigerant before replacing the HP switch..
F404 is “First Slave Outdoor Unit Compressor 1 Liquid Compression Error. This is stating that the system has detected a low discharge superheat across the First Compressor (M1C) of the First Outdoor Unit. This unit detects this by monitoring both the Suction and Discharge temperature and is triggered when the suction temperature falls below 3degC and the discharge superheat is below 10deg C. The most common issue that causes this to happen is the outdoor unit having liquid refrigerant flooding back to to it from the indoor units. This is only an Error Code and will allow the system to continue to run.
congratulations for your great job of teaching others now that this technology is entering new york city due to its high demand and few technicians to make repairs congratulations although I don't speak Spanish but I understood your concern why others learn repairs and how to identify the errors and solve it thanks
Thanks
He is speaking Japanese.
Hi. Bon mj I am your subscriber
Thank you so much your videos is
Very informative and I am also working in daikin Mitsubishi LG O.gerenal vrv & non vrv air conditioner I have 8years experience Installation and maintenance
Congratulations..Mr bon. Great explanation...
Thanks bro
Great Job Bon as always
Thanks bro
Marcos from brazil .Very good your work ,congratulations
Thank you very much!
Nice Mr Bon , say hello from BALI
Thanks bro
Great job Bon.
Thanks
Well done Mr Bon
Thanks bro
Iam come to Sir daikin itc bhadrachalam
Good job bon
Thanks
Bro are you release all of the gas or carry out refrigerant recovery before cut out low pressure sensor?
Hi sir Bon, did you pump down when you replaced the pressure switch?
thanks sir Bon
Welcome
Good jon 😘🇮🇳
Thanks
Hi Bom, may i know where did u get that s brazing cylinders set? I would like to buy in Singapore also. Thanks alot.
Teck Hoe AirConditioning Parts Pte Ltd
8 Lorong 15 Geylang
Did you repair it in the same day?
Wow Singapore congratulations nyc new york city 🍎
Thanks bro.
Hello, we see it as a simple repair, but it is a job that takes several hours and knowing or having the capacity and the original parts to solve the error because it is not working and its replacement. I need you to teach how to solder the pressure switches so as not to damage them in the installation or silver solders the vacuum and recharge the unit with freon new minds because it is not in the video the freon leaks into the atmosphere it is not collected for its new uses another Once it is loaded with new freon and how to load it and know when it is at its normal capacity. Thanks a lot
Hi.
I have problem with my Daikin (C9 error).
What is the value of the thermistor in the device: FCAHG125F?
Thank you for your help!
Try to check R1T (for ceiling cassette,air thermistor is seal type,remove the wire clip and measure)
Example temperature 30° is 16k ohm+-
temperature 10° is 40k ohm+-
@@BonMj Thank you very much for your answer.
It was corroded. I replaced it.
I gave a value of 20k (in 25C, it is about 16k in 30C).
The air conditioning started to cool but only for 10-15 minutes. Later, the outdoor unit turns off and the indoor unit only acts as ventilation, no cooling. After disconnecting the power and connecting, the cooling works again for 10-15 minutes and turns off (and the room is still hot).
Heating seems to be working normally.
Do you have a solution?
@@mac0pod do you check all thermistor reading.like liquid pipe thermistor or gas pipe thermistor
sukses selalu bos ku good 🙏🏻
Terima kasih master🙏
阿舅
Before change that sensor, are we need to take out all the gas ?
CU only
@@BonMj i dont understand
@@nurfirdausabdrahman8487 outdoor unit,I guess you should do recovery or pump down if Daikin allows it
I have one doubt sir Mitsubishi electric VRF how to test run and how to set group address
Please explain sir
Hi sir. Can i get the address on where to buy the heatblock compound
You can buy online
Hi 👋
hey mr bon it's vrv 3, single outdoor kah ?
Yes
Hello sir, if cut the pipe, no leak refrigerant ?
Yes the Refrigerant will leak out..
Anytime you tap into a refrigerant system you would need to reclaim/recover the refrigerant..
This is one of my major gripes with Daikin, just about every other manufacturer uses a 1/4 flare male/female for the pressure switches yet Daikin still have this ridiculous setup which makes you recover all refrigerant before replacing the HP switch..
👍👍
Dear Mr. Bon. Thank you........ we are every day updates ..I am srilanka..........
Sir now I am working in Saudi Arabia. But I went to work with you. It's possible?
Hello dear
Hello 😊
Where are you from sir?
Singapore
I want job with you.
@@BonMj hlo sir
I want your mail ID
Thanks 🙏🏻
You’re welcome 😊
Sir Daikin vrv 4 coming error f4-04 please how to solve problem
F404 is “First Slave Outdoor Unit Compressor 1 Liquid Compression Error.
This is stating that the system has detected a low discharge superheat across the First Compressor (M1C) of the First Outdoor Unit.
This unit detects this by monitoring both the Suction and Discharge temperature and is triggered when the suction temperature falls below 3degC and the discharge superheat is below 10deg C.
The most common issue that causes this to happen is the outdoor unit having liquid refrigerant flooding back to to it from the indoor units.
This is only an Error Code and will allow the system to continue to run.
👍👍
@@rdenir how to solve this problem sir. please Sir what am I doing this problem solve.
@@priyeshsingh2507 are you a technician?
If not it would be very difficult to explain how to fix the problem
@@rdenir yes I am technician.but vrv first time troubleshoot. So please help me
Your personal no ???