Benefits of Smart Load Port in NitroX Inverter || How to set values to operate Smart Load Port?
Вставка
- Опубліковано 28 тра 2024
- Benefits of Smart Load Port in NitroX Hybrid Inverter || How to set values to operate Smart Load Port?
#Smartload #nitrox #Inverex #Hybridsystem #Enontraders - Наука та технологія
Sir F35 fault py video banyn
Good work
Light jab jati hy wapda se raat k waqt tu Ac on ho tu complete system off ho jata hy nitrox 3kw inverter hy iska koi solution?
Bro fault 14 or 56 par b video bana den k kesy fix karen
They have uploaded F14 fault code video, a day ago.
ua-cam.com/video/v7OsBf4J6Eg/v-deo.html
Video for F14 Fault code. F56 Video will be uploaded later tonight.
F14 DC over current failure
How to solve the problem it's battery sitting problem or pv DC is overload
Which inverter do you have?
Mera inveter micro inv input par set hai
Wapda chali gai lekin solar working ma tha
Phir bhi heavy load off ho gya
Solution please
Smart load pe set karain
ua-cam.com/video/WLLX8OPYVTk/v-deo.html
Iam facing f34 Ac overload error when wapda is connected it should not overload help me how to solve this error
Your Phase Wire or Neutral wire is loose or Week at some point.
Check Wire From meter first it should be properly screwed, otherwise check all the termination of Grid Side wire only that is coming to inverter.
Sometimes Service main also need PG clamps to be properly tightened so check thoroughly.
You can also check it by changing the phase from red to yellow or blue if you have 3 phase meter.
Phase or neutral wire of Grid supply.
Why there is always difference of units.. between consuming and production … between grid and home..
Difference of 100W-300W…
Why???
Inverter takes power to run itself
Salam. My inverter nitrox 6kw is feeding into grid when the settings are set at zero export to load with unchecked box of solar sell. I do not have net metering. It sells 10 to 60w to grid at some instances due to which my wapda meter reverse light is on. Need help
Do you have install CT?
Reduce zero export power to "0".
@@sunectricenergy4668 yes ct is installed
@@sunectricenergy4668 it was 020, i changed it to 000
@@sunectricenergy4668 yes ct is installed