Sir my question is Let us take unit conversion Min=(bar*lit)/(lit/min) Here lit gets cancelled of then bar is pending Which becomes bar*min Here LHS Not equal to RHS
Sir I have a question, as you have mentioned that If a cylinder is 6 letter and pressure is 300 bar we need to multiply 300 x 6 / 40 we ll get the answer. Since we know there are 5 main types of SCBA, which are 2L, 3L, 6.8L, 9L and 10L My question is what if we have 300 bar pressure in 9L of cylinder? This will change the duration of use of SCBA. What makes this change? Thanks from Pakistan 🇵🇰
Very good question Champion. It is the cylinder volume which is making difference here. In a simple words to achieve 300 bar in 6 liter will take less time then achieving or filling 300 bar in 9L and there will be significant change in their weight as well.
Dear Sir Please making the video all type of flooding system . Water flooding system Foam flooding system Co2 flooding system Novec suppression system 1234 FM 200 Inert gas flooding system Thanks you great knowledge share on UA-cam
Sir my question is Let us take unit conversion Min=(bar*lit)/(lit/min) Here lit gets cancelled of then bar is pending Which becomes bar*min Here LHS Not equal to RHS
Love sir Is type ka video lane ke liye thank you blo ke me app ko sarminda karna nehi chatahnu❤
👌Detailed and clear description 👍
Glad it was helpful!
Good Information
Thank you
Thank you sir 🙏
very well executed 🙏🏻
Thanks for give calculation of SCABA working duration
You are sharing so informative stuffs thanks alot
👍
Cyllinder ko kitne baar k baad reffiling karana padta hai... standard rules k hissaab se.. .
Very good explain
👍
Grate sir
Awesome Sir
🙏
Sir can you please explain about safety disc capacity and DSU db ?
Superb
Woow super
👍
Sir my question is
Let us take unit conversion
Min=(bar*lit)/(lit/min)
Here lit gets cancelled of then bar is pending
Which becomes bar*min
Here LHS Not equal to RHS
Great sir
❤️
Very interested topic thanks sir
👍
Sir aap bahut achha padhate ho ❤️❤️❤️
❤️
Very informative video.
👍
Great
Thank you 🙏 ❤️ Sir
Thanks sir❤🙏
Nice sir ❤️
❤️
Super 👍
Sir.. Minimum at what Bar pressure we can use/replace the Cylinder?
Sir I have a question, as you have mentioned that If a cylinder is 6 letter and pressure is 300 bar we need to multiply 300 x 6 / 40 we ll get the answer.
Since we know there are 5 main types of SCBA, which are 2L, 3L, 6.8L, 9L and 10L
My question is what if we have 300 bar pressure in 9L of cylinder? This will change the duration of use of SCBA. What makes this change?
Thanks from Pakistan 🇵🇰
Very good question Champion. It is the cylinder volume which is making difference here. In a simple words to achieve 300 bar in 6 liter will take less time then achieving or filling 300 bar in 9L and there will be significant change in their weight as well.
Thankyou sir
👍❤️🙏
Thanks sir ❤❤❤
I am requesting you sir plzz y can provide one class about what is Audit,type of audit.
Already uploaded video on this topic
Sir app Lao bg4 or Elba .and oxipack. ka bare me kucha
Thank you sir
👍
Tq 😘😘
👍❤️🙏
* Sir cylinder 6 liters se jada rehega tho kese karna hai
* Aur 300 bar se jada rehega to tab kese karna hai sir
Sir IOSH ka chapter kabse start kr rahe h padhana plzz bataye na
It will take time but definitely
What is safety margin
45 minutes kaise aaya details me btaye
Why is multiple by 6.
Dear Sir
Please making the video all type of flooding system .
Water flooding system
Foam flooding system
Co2 flooding system
Novec suppression system 1234
FM 200
Inert gas flooding system
Thanks you great knowledge share on UA-cam
Noted
wrong information this is not 1.5 cu ft it is letter bro
Sir explain kro na
Sir my question is
Let us take unit conversion
Min=(bar*lit)/(lit/min)
Here lit gets cancelled of then bar is pending
Which becomes bar*min
Here LHS Not equal to RHS
Thanks sir 👍
❤️