Pawan bhai ki jai ho . very nice video . bhai ek sawal tha input our output me jo black colour ki core lagi he oh kisliye lagai he . uska kya kam hota he . reguler inverter me kyo nahi lagate he ??. sirf ups mehi dikhte he . ?? please bataye . ok thanks . by by .
Sir mere pass numeric 36 volt battery ka online ups hai on nahi ho raha hai Maine multimeter se IGBT 3 PIN Wala check kiya toh pata laga ke wo short hai mera IGBT no hai 11N120 CND AD hai kiya replaced kar sakta hu FGA 25N120 ANTD ?sir pls help me
Pawan bhai thanks for ups invertor repair video many people help for this. I have one question that I have genus 800va invertor many time trip ups mode and show over load but some time working fine. Pls suggest me
Singh sahab plzz check load when it shows overload If load is ok than you can check electrolytic capacitors 6800mfd/25volt for single battery inverter Thanks
Sir microtek me pin no 26 par charging volt nahi aa rahe hai. 202 bhi change kar diya or 555 bhi nikal rakhi hai .fir bhi volt nahi aa rahe .kya karan hi sakta hai.
Sir mere paas arrow ka 1kva 36v ups ha jisme igbt 11n120 kharaab ha igbt ki Pluse ok karne ke baad 40k120 igbt lagai par output coil bina lode ke garm ho rahi hai output capacitor bi dusara laga liya koi solution de
Excellent work, i have a Eaton UPS 5SC750, and i have added 65AH batteries with it but UPS on backup give me a calculated time then shutdown ( UPS thinks it self there is 7AH batteries attached can't detect 65AH batteries ), i want to bypass calculated time frame kindly give me some expert advice on that thank you
Sir mere pass 24 volt 30 amp ka battery charger hai ,usme FGH 35N60 OR 10 ohm 15watt ka load resistance khharab ho gya tha ,jise me Badale diya tha 35N60 ki jagah 40n60 laga diya tha ,but power on karne on par power Aur Ho Jata Hai but output mein battery Lagate Rahe 40n60 aur 15 ohm ka registration kharab ho jata hai,pls help
Hai sir we are using numeric 1000plus ups in home last 2 years is good working condition.but today We are put mixer grinder after this ups not working and long beep sound is coming what happened this ups?
Good work done ✅👏👏👏 I really need your help. Pls am repairing a 10KVA ups with low battery alarm, even though the batteries are all replaced. 16 batteries in total, summing to 213v from multimeter check, but what appear on ups screen is 174v . Kindly assist me , what could be the possible cause of the fault which affecting the voltage failure sensing. Thank you 🙏
Sir mare paas be aaya hai 1kva ups NUMERIC hp max 36volt aage display chal Raha hai magar dc volt cum nekal raha hai power board per charger do connection koe be uthata ho mai charger barabar volt 40 dekhta hai problem power board mai kes part mai problem hai mare ko batana please.
मेरे पास एक ऑनलाइन यूपीएस है 96 वोल्ट से ऑपरेट होता है इसमें फोल्ड यह है कि बार-बार बैकअप मोड से हट जाता है और फिर ऑन करना पड़ता है तब फिर से ऑन होता है
I'm sure this video contains a lot of important information about how this UPS works and I really like it, but unfortunately I don't understand your language.
Hello Sir.May apka bohot bara fan sir.
And apka video se mujhe bohot help milta hay
Thangs Sir.....for helping ud
Inverter overload indicater glow What is fault Sir ?
Pawan bhai ki jai ho . very nice video . bhai ek sawal tha input our output me jo black colour ki core lagi he oh kisliye lagai he . uska kya kam hota he . reguler inverter me kyo nahi lagate he ??. sirf ups mehi dikhte he . ?? please bataye . ok thanks . by by .
Kya 38N30 ki jagah 38N60 MOSFET laga sakte hain?
You didn't tell about that big transformer. What is the use it it comes with smps charger and high frequency inverter?
Nice video.Esme bdavala transformar kya Kam karta hi .q ki charge and power k breme aap ne acchha samjaya
Aapki video bahut hi knowledge full hoti h sir
Thanks
Share if possible
Hello, what's the settings of Delta 2 kva ups.. please explain!!
very nice and a knowledgeable video thanks
Sir AJ online ke bare me bhi kahi kuch sikhne ko Mila hai thanks sir aisi video banane ke liye
Sir mere pass ip11s- wn hitachi ka 1kv he pr usme charg amp or volt ka satting nhi he charg volt 41 volt he muje volt 40 v krne he koi upaye btaye
Sir mere pass numeric 36 volt battery ka online ups hai on nahi ho raha hai Maine multimeter se IGBT 3 PIN Wala check kiya toh pata laga ke wo short hai mera IGBT no hai 11N120 CND AD hai kiya replaced kar sakta hu
FGA 25N120 ANTD ?sir pls help me
Ustaz mohtaram ap agr is invetor par ziayada tawajo dogi bohot acha ho ga
Sar ji ups me transformation nhey hota to vo voltage keseh bnata hey
Jab charging saksham ka fuse chala jata hai supply dene ke bad tab kya
Coast of power ckt ?isit available inmkt
Pawan bhai thanks for ups invertor repair video many people help for this. I have one question that I have genus 800va invertor many time trip ups mode and show over load but some time working fine. Pls suggest me
Singh sahab plzz check load when it shows overload
If load is ok than you can check electrolytic capacitors 6800mfd/25volt for single battery inverter
Thanks
Sir microtek me pin no 26 par charging volt nahi aa rahe hai. 202 bhi change kar diya or 555 bhi nikal rakhi hai .fir bhi volt nahi aa rahe .kya karan hi sakta hai.
Sir mere paas arrow ka 1kva 36v ups ha jisme igbt 11n120 kharaab ha igbt ki Pluse ok karne ke baad 40k120 igbt lagai par output coil bina lode ke garm ho rahi hai output capacitor bi dusara laga liya koi solution de
Excellent work, i have a Eaton UPS 5SC750, and i have added 65AH batteries with it but UPS on backup give me a calculated time then shutdown ( UPS thinks it self there is 7AH batteries attached can't detect 65AH batteries ), i want to bypass calculated time frame kindly give me some expert advice on that thank you
Hello Sir. I need to use it with 12v instead of 36v. Can you please show how to do it. Thanks
Sir mere pass 24 volt 30 amp ka battery charger hai ,usme FGH 35N60 OR 10 ohm 15watt ka load resistance khharab ho gya tha ,jise me Badale diya tha 35N60 ki jagah 40n60 laga diya tha ,but power on karne on par power Aur Ho Jata Hai but output mein battery Lagate Rahe 40n60 aur 15 ohm ka registration kharab ho jata hai,pls help
Sir,G.M. hi freq. on line ups ke spears kaha mil sakate hai? mere pass bhahut sara kam in ups ka ata hai but spears ki problem aati hai
pl.reply me
Sir Eaton dx 6kva on line 16 battery error 007 Regan Kya hai battery mod per
Good tiching karte hai 👍👌👌👌👌👌👌👍👍👍👍👍👍👍
numeric 600 ex ups kam load par 40 second ke baad khud band ho jata hai, iska kuch ilaaj hai? Please reply
Sir , मेरे पास एक 3 kva microtek पीस आया है जो on होने के साथ ही mains mcb ट्रिप कर देता है। क्या करूँ
Really a good vedio, thanks.
We want more vedio like this.
Badavala transfomar out k Lia hi kya .online ups me kdhi Dekha nhi
Hai sir we are using numeric 1000plus ups in home last 2 years is good working condition.but today We are put mixer grinder after this ups not working and long beep sound is coming what happened this ups?
I have the same ups, but yeah, bettary ko fill charge nahi karta or backup v 10 minutes se jayda nahi deta, keya kare??
Good work done ✅👏👏👏
I really need your help.
Pls am repairing a 10KVA ups with low battery alarm, even though the batteries are all replaced.
16 batteries in total, summing to 213v from multimeter check, but what appear on ups screen is 174v .
Kindly assist me , what could be the possible cause of the fault which affecting the voltage failure sensing.
Thank you 🙏
बहुत बढ़िया और ज्ञानवर्धक वीडियो । पवन जी आपका वर्कशॉप किस स्थान पर है ?
Numeric 3 kva me 6 no. Fault kya hota h
Sir mare paas be aaya hai 1kva ups NUMERIC hp max 36volt aage display chal Raha hai magar dc volt cum nekal raha hai power board per charger do connection koe be uthata ho mai charger barabar volt 40 dekhta hai problem power board mai kes part mai problem hai mare ko batana please.
Halo sir mara ek emerson 1kv/800watt.36bdc online ups ON out put supply plz iska koye upai bataye sir ji
Mujhe yehsb sikhne ke liye Kya parhna parega engineering ya fir diploma
ITI, DIPLOMA YA B.TECH KOI BHI CHALEGA
Sir discharge krne ka sahi tarika keya batiye plz.....
sir emerson ups main fault 11 a raha hai to repair kase kare
सर् चार्ज़िंग वोल्टेज अप ओर डाउन कैसे करे
Good Paji 👍
Thanks
u r from?
Sir we have also an online ups of luminous 72 Volt which is completely dead . And the Inverters is high frequency inverter
Fuse ok h bt no display
Dear Pavan Pratap
I have 2kv 72v numerics online ups is dead could you please help in repairing it, support in getting it fixed
Sir is ups Mai battery full charge hoti Hain lekin LCD pe battery low dekhata hai please help
Explained very nicely. Too much helpful for beginners. Thanks a lot.
Sir bypass on hota hai but battery pe on nahi ho raha hai
Ye ups me bada transfermar q laga hi
sir mere e baik ke chargiar riper karvane hai kase bheje
240 v dc 5kw fault hai numeric ups only bypass working no display what is solution prosses
Nice explanation,thank u sir Ji !
ac nehi a raha he. conputer ups
plz help
सर numric hp 2000 3 kva 96 volt me 6 नंबर falut दे रहा है
2 kav 24v ka utl Gamma PCU h sir vo ledi to Cho krta h Lekin on nahi hota sir kaa problem h
इस UPS में वार्निग 10 आने का क्या कारण है ?
Sir igbt based stabilizer's k bare me kuch bataye sir
How to connect to bulb trublshoot
Sir you dont reply to emails?
Nice vdo sir, very useful, thank you sir
Thanks
online 3kv UPS ma 06 error a raha hy ??
Model name
🙏👌very nice teaching sir 👌🙏
Sir luminous eco volt PCB repair ka video banaaooo
Sir, pls make a video for programming ic 30f2010 sinewave inverter.
Sir very nice vedio
Sir Training dete hai please tell me
Out put voltage nahin a raha
Transformerless inverter ke bare mein video banaen
do you service APC online UPS ?
Hey. I got engineer who is into repairing all sort of ups, even industrial ups..
My details are in my UA-cam Channel, get in touch with me
V nice Sir 👌👍
Very good 👍🙏 thank you sir
Sir is card ka full dittels class ka video bnaye
Nice video 👍👍👍
we are waiting for pic16f72 tutorial.
Sir vertiv liebert Mt+ ka bataiye
Set microteck online Kabhi video banaen
Thank U Sir ji for this post 🙏🙏🙏
Always welcome
Sir kya aap online ripeyer ki training dete ho..
7981636836 if u need any help
You are the great sir
Sir pic 16 f 72 ka agla tuturiyal banayen pls pls sir
Sir derive ic.chiak karna k leya jik banado sir
Ok
Power card ka SMPS card repair karana bataiye
Good job
Sr aap 1 video ups Ka 3000v
350 volt Dc Ac me 250 se kam hota hai
Thanks for sir information k liye
Useful video
Thanks sir ji
Sir consul ka ups h 3kva / 96 volt DC ka sir ye 125 volt bc nikal rha h sir is ka charger card kharab hai ya sahi plz sir confirm kar do
Kam kro usko
Sir TL494 PWM IC ka pora detail ka video baniya sir
kis liye ? TL494 sg3525 almost same behavior .
मेरे पास एक ऑनलाइन यूपीएस है 96 वोल्ट से ऑपरेट होता है इसमें फोल्ड यह है कि बार-बार बैकअप मोड से हट जाता है और फिर ऑन करना पड़ता है तब फिर से ऑन होता है
Thanks...sirji
Utl chargar ripeyar ki video daal do ya to apna nomber de do
I'm sure this video contains a lot of important information about how this UPS works and I really like it, but unfortunately I don't understand your language.
Best video as ir
Thanks
Nice
Thanks you sir gerat
Nice sir
Sir aap ka mobile no mil saka hai sir
👍👌👍👌👍
Thank you sir