OLTC: On Load Tap Changer. A complete and Practical explanation

Поділитися
Вставка
  • Опубліковано 26 лип 2024
  • In this video, OLTC is explained with example with respect to following points.
    1. Structural aspects
    2. Working principle
    3. Switching and Diverter Chamber
    4. Drive Mechanism Box
    5. Tap change operation
    6. Components identification
    7. Aplications
    Video URL: • OLTC: On Load Tap Chan...
    For Business Enquiries Please mail to: tektalksengineered@gmail.com
    #oltc #onloadtapchanger #tapchanger #threephasetapchanger #avr

КОМЕНТАРІ • 34

  • @mrida3017
    @mrida3017 Рік тому +2

    Thanks for the video, I want to correct one thing: 1:25 these are tie-in resistors which are used to limit the recovery voltage during the operation of change-over selector.
    Change-over selector is equipped to OLTC when we need higher operating positions with a limited tap selector contact quantity.
    For example: OLTC with 10 selector contacts and without change-over selector: can operate up to 10 positions only, while the same OLTC when equipped with change-over selector can operate up to 19 positions (10*2 -1).
    The transition resistors used to limit the circulating current duration tap switching are located inside the diverter switch insert in the oil compartment of OLTC.

  • @surajchakraverty624
    @surajchakraverty624 3 роки тому +1

    Thank you for the enlightenment sir. Wonderful sharing packing with full of information.

  • @shengjitee2539
    @shengjitee2539 4 роки тому +2

    Thanks a lot for the educational video!

  • @rameshtripathy5978
    @rameshtripathy5978 3 роки тому +1

    Excellent description & helpful too !

  • @runbou3485
    @runbou3485 Рік тому +1

    Thankអរគុណ👏

  • @markangelomuan6855
    @markangelomuan6855 2 роки тому +1

    Good presentation. Thanks

  • @runbou3019
    @runbou3019 2 роки тому +1

    អគុណបង

    • @ElectroGlobe1
      @ElectroGlobe1  2 роки тому

      សូមស្វាគមន៍ (Welcome)

  • @ashishmahajan7223
    @ashishmahajan7223 4 роки тому +3

    Hi sir,i have the following questions:
    1. How does the OLTC work automatically as in how does it measure the change in load and changes it taps accordingly?
    2. As shown,there is also a counter inside and while doing the O&M, we check how many times OLTC operated.I wanted to know is there a certain value in the counter above which we can tell that it can cause problem to the OLTC?
    3. The motor used is AC or DC?

    • @ElectroGlobe1
      @ElectroGlobe1  4 роки тому +1

      Thank you for your comment.
      Following are the answers to your questions.
      1. There can be two ways to monitor voltage change, if one observes voltage change beyond limit, OLTC is operated. Also there are OLTCs with AVR system called as automatic voltage regulation. In this case voltage is monitored and regulated automatically. That means OLTC changes tap automatically.
      2. Yes. After certain number of operations, it is advised to do OLTC servicing in consultation with respective manufacturers. Also life of OLTC is related to number of OLTC operations.
      3. The motor used is AC motor.

  • @wilbertabrea354
    @wilbertabrea354 4 роки тому +1

    Nice!!
    May i ask about off load tap changers? Are they connected on high voltage side too?
    Thanks.

    • @ElectroGlobe1
      @ElectroGlobe1  4 роки тому

      Thank you. Yes octc is connected on HV side.

  • @lalitgalani575
    @lalitgalani575 3 роки тому +1

    sir, is there any video for dissolved gas analysis of transformer oil

    • @ElectroGlobe1
      @ElectroGlobe1  3 роки тому

      Video about DGA will be as soon as possible.

  • @wilbertabrea354
    @wilbertabrea354 3 роки тому

    Sir, do you have video regarding oil degasifiers? Thanks

    • @ElectroGlobe1
      @ElectroGlobe1  3 роки тому

      Please check the video about silica gel Breather
      ua-cam.com/video/hp-yAxRdOHM/v-deo.html

  • @vishalkarthik.v7209
    @vishalkarthik.v7209 3 роки тому +1

    Sir ,so the concept is put the HV winding inside LV winding ...

  • @himanshu2232
    @himanshu2232 4 роки тому +1

    Sir please make vedio on capacitor bank in substations

    • @ElectroGlobe1
      @ElectroGlobe1  4 роки тому

      Sure. Video on capacitor bank will be uploaded soon.

    • @himanshu2232
      @himanshu2232 4 роки тому

      @@ElectroGlobe1 sir I will always wait for your new vedio .

    • @himanshu2232
      @himanshu2232 4 роки тому +1

      @@ElectroGlobe1 please upload more vedio,your vedio is more informative for us.

    • @ElectroGlobe1
      @ElectroGlobe1  4 роки тому +1

      @@himanshu2232 thank you

  • @enamulhaque630
    @enamulhaque630 4 роки тому +1

    What is current rating of tap changer

    • @ElectroGlobe1
      @ElectroGlobe1  4 роки тому

      Current rating varies for different OLTCs. Standards for OLTC has details about current rating. Hope this answers your query.

    • @enamulhaque630
      @enamulhaque630 4 роки тому

      @@ElectroGlobe1 Actually my question was how current rating of OLTC relates to Transformer rating. Or no relationship

    • @ElectroGlobe1
      @ElectroGlobe1  4 роки тому

      @@enamulhaque630 yes. OLTC and Transformer ratings are related.

  • @zachsieg2332
    @zachsieg2332 Рік тому +1

    The narration of this video makes this completely unwatchable