Installing a Micro-Air EasyStart 368 AC Soft Start (ASY-368-X48-BLUE) in a 3.5 Ton Trane - IT WORKS!

Поділитися
Вставка

КОМЕНТАРІ • 131

  • @beforebefore
    @beforebefore 5 місяців тому +16

    This one caught my eye... because I had my Trane XL14i w/heat pump kit installed in 2004 after a lightning strike.
    Then about 8 years ago it was having trouble starting in the heat of Summer, popping the circuit breaker. The HVAC tech said the compressor was bad, time for a new aircon!
    Having had some DIY HVAC experience years before, and thus being familiar with soft-starter on large compressors (Variable Frequency Drives), I found the Hyper Engineering Sure-Start series, and bought one and installed it.
    Here we are in 2024 and it's still going strong! Before I installed it, it was hitting 70+ Amps at startup (analog meter)... which was reduced down to around 20 Amps... amazing. In fact, I could run my whole house air conditioning with my emergency 7kw genset without any problems.
    I've yet to find a single HVAC technician who understands what a soft-starter does... all they ever want to put on is A HARD starter... throw MORE Amps at it, and burn it up!

    • @nothingface0xx
      @nothingface0xx Місяць тому

      A hard start does not make it pull more amps. The extra capacitance means the compressor doesn’t have to try as hard to start which decreases the amp draw on start up. Thats why you can add a hard start to a compressor that pulls so many amps it pops the breaker and suddenly they don’t pop the breaker anymore.

  • @SlipFitGarage
    @SlipFitGarage Рік тому +11

    Nice job, Sir! I installed the same device on my AC unit a few days ago. The sole purpose for me was to lower the inrush current so I could run the AC on my backup generator. I also have been getting weird numbers with my amp clamp meter.... and I specifically purchased a new $200 Klein meter with the "inrush" feature to accurately measure the before and after amp draw when installing devices like this. My meter is showing lower numbers than the Bluetooth app. Weird. Either way, I am still very impressed with the end result of the Micro-Air installation. My 9000 watt (peak) inverter generator will now start my AC with no trouble at all. (my AC unit is only a 1.5 ton - small house) I watched your snow melting videos and I was also very impressed with that system, too. In fact, I am a little bit jealous of your snow melting driveway. I installed a new brick paver driveway about 15 years ago and I could've added anything under the driveway at that time. Either electric wires, liquid glycol lines, something, anything.... but the thought never crossed my mind. After watching your video I am really disappointed that I didn't add something for melting snow when I had the chance. Nice video. Keep 'em coming...

  • @rwstarke
    @rwstarke Рік тому +12

    I have a 4-ton (46,000 BTU) A/C unit. Two years ago I installed a Micro-Air EasyStart 368 (4-ton) Soft Starter ASY-368-X48-BLUE. It now has 26,400 starts. My AC unit now uses 12.8 to 13.8 Amps and a Start Peak of 33 to 36 Amps. I bought it at Global Yacht Supply. It was shipped from Micro-Air. It now costs $332. I have a Firman T07571 Tri-fuel and run it on NG.

    • @DeckerChristopherJ
      @DeckerChristopherJ  Рік тому +5

      Wow! 26,400 starts! This is great to hear, thanks for sharing! I’m around 100 starts right now and I’m just below 30A to start and between 10-11 running with my 3.5 ton. It’s slightly quieter and no more lights dimming in the house at startup. I’ve been super happy with the purchase so far, but your comment and experience is great to look forward to! Thanks for watching and commenting!

  • @stanwei157
    @stanwei157 Рік тому +21

    At same time, you should replace the old capacitor .

    • @troyd.521
      @troyd.521 11 місяців тому +1

      Why?

    • @craigpierce7996
      @craigpierce7996 11 місяців тому +1

      That cap looks puffy... and old... should have changed it

    • @murky2502
      @murky2502 3 місяці тому

      Yeah, at least test it. But it was rusty and they are cheap and are a wear item.

    • @fattysgarage1754
      @fattysgarage1754 3 місяці тому +2

      Exactly, replace capacitor if it is more than a few years old and I also replaced the contactor since it was 12 years old. Now I can run the whole house a/c on my portable generator. This was tested during hurricane Ian, and worked flawlessly! 3 ton unit: starting amps were 26 instead of 77 and running amps were 9.5. One of the best purchases I made.

  • @mongo1982
    @mongo1982 10 місяців тому +4

    I bought one a couple of months ago and installed it yesterday. It reduced starting amperage from 72 A to 24 A. Verified through the Bluetooth app and also via our Sense app. It did what it said it was going to do. Worth every penny.

  • @baazooka86
    @baazooka86 Рік тому +3

    From a former Buffalonian living in Arizona I say “nice job”. This would be a nice addition to our A/C unit which about to get another good workout here this summer. Also enjoyed your winter video some months back. I remember those days all too well.

  • @jonathanliles2044
    @jonathanliles2044 5 місяців тому +7

    Nice job. A couple of things:
    If you notice the terminals for the compressor that are bolted down to the contactor don’t have insulation on them. That’s because they’re high temperature rated terminals. The insulated terminals will melt.
    You should check the capacitor if it hasn’t already failed. It looks like it’s bulging a bit. Generally if it’s +/- 10% or worse from its rated capacitance then it needs to be replaced. The +/- listed on the side of the capacitor is the out of box tolerance level. If it’s outside of the listed tolerance straight out of the box do not use it and get another one.

    • @martidav1
      @martidav1 Місяць тому

      Uh-oh. The older brand, ICM Controls, sends insulated crimp-on connectors and a butt splice. Should they know better, or is it still safe??

  • @TexasKoz
    @TexasKoz 10 місяців тому +5

    Good video. Thanks. Mine is arriving tomorrow and am excited to install it.

  • @johnadams2313
    @johnadams2313 11 місяців тому +3

    Very nice video. I ordered the same unit for my 3 ton AC. This will help. My goal is to help the AC to run better and on a generator when we have a hurricane here in Florida.

  • @ryanbrady5968
    @ryanbrady5968 Рік тому +8

    Nice video -- I installed the exact same Micro-Air soft start kit on our 3 ton Bryant unit a couple years ago so that it would start on our generator. runs great and i've also been able to use the phone app to update the firmware on the unit via bluetooth.

    • @DeckerChristopherJ
      @DeckerChristopherJ  Рік тому +6

      Thanks Ryan! That is another reason I installed it, I just forgot to mention it in the video! Glad you hear you haven't had any issues with it. It was a little pricey, but I think it was worth it. I also found the Bluetooth functionality quite impressive. I haven't needed to update the firmware yet, but that's a great point and advantage when the time comes! Thanks for taking the time to watch and comment, I appreciate it!

  • @MiHeatingGuy
    @MiHeatingGuy Рік тому +3

    Looks like a real clean install

    • @DeckerChristopherJ
      @DeckerChristopherJ  Рік тому +2

      Thanks!! I really appreciate that coming from a professional like yourself! Thanks for watching my videos! 😊

  • @carapungo
    @carapungo Рік тому +1

    very good bro. Will be installing mine shortly and this helps. Thanks for sharing.

  • @craigpierce7996
    @craigpierce7996 11 місяців тому +5

    Just installed an X72 in my 5 ton, it's working great! Initial inrush was about 78 amps. The unit took that down to 34 amps. Running amps are about the same, 11 amps. Time for a generator backup panel!

    • @dboundscpa
      @dboundscpa 4 місяці тому +1

      I've just gotten my 72 operating after nearly a year of sitting dormant on my unit because the electrician couldn't get the connections right so the compressor wouldn't start. I'm having almost identical results do what you reported. I need to have my soft start relearn though because the weather conditions weren't right for that process when we got it going.

    • @craigpierce7996
      @craigpierce7996 4 місяці тому +1

      @@dboundscpa Yes, not too hot or cold outside when learning. It was about 80 degrees when I installed mine. Note that the compressor will draw more running amps when the setpoint of your AC in the house is more than 15 degrees below outside ambient temp. At 25 degree difference, AC efficiency drops fast, meaning longer run times to meet the demand.

  • @gilsterk
    @gilsterk Рік тому +2

    This is great! ….and I’m really looking forward to the solar install!

    • @DeckerChristopherJ
      @DeckerChristopherJ  Рік тому +2

      Thanks Gil!! LOTS of videos coming on the Solar! You’re going to LOVE the videos on the production and monitoring!! Trust me! 😉😉

  • @cezarnebun9607
    @cezarnebun9607 3 місяці тому +1

    Well done sir, great attention to detail

  • @didyuknow
    @didyuknow Рік тому +4

    Thanks for this as I was having doubts on what unit to buy for my 3.5 ton compressor since the X48 is good for up to 3.5 ton units and the X72 for units above 4 tons. Given the high start up current you had (mine is 110A instead of your 170A) and the fact the unit worked for you then I am more comfortable going with the X48 version. The small price difference would not be the reason for choosing the smaller version, but making sure the compressor would be within the softstarter design operating current range.

  • @da7heaven
    @da7heaven Рік тому +3

    Great video. My HVAC guy says "Soft starts tend to overhead motor windings, leading to an early death of the compressor. While they may save you energy, when they destroy the compressor."

    • @acastr1234
      @acastr1234 10 місяців тому +1

      Mine said the same thing. I have a hard starter but I'm looking into using a generator for my 3.5 ton.

    • @imowgrass
      @imowgrass 10 місяців тому +11

      Motor windings getting hot cannot happen from reduced power draw. It defies the Law of Power P=IE.

    • @blackrifle6736
      @blackrifle6736 3 місяці тому +6

      @@imowgrass *Ah, finally! A Commenter that understands Ohm's Law. Thank you.*

    • @blackrifle6736
      @blackrifle6736 3 місяці тому +3

      *Lots of ignorance and mis-information is rampant. You might wish to politely direct him to Matteo Giovanetti's tutorials. Pity that so few HVAC/R guys understand the EasyStart's functioning.*

    • @starhopper457
      @starhopper457 Місяць тому +2

      @@blackrifle6736 I'm with you, if the amps go down, how does that translate into over heating?

  • @brentsmithline3423
    @brentsmithline3423 11 місяців тому +1

    Looks like you have found you have found a great solution.

    • @DeckerChristopherJ
      @DeckerChristopherJ  10 місяців тому +1

      I’ve been very happy with it so far! Thanks for watching!

  • @rcinfla9017
    @rcinfla9017 8 місяців тому +2

    Before shoving in sheet metal screws, check inside to be sure you won't hit a refrigerant line or condenser tubing elbow with sheet metal screw sticking out backside.
    The Red wire to compressor is only the compressor Run winding current. To get total compressor current you should measure Black common wire to compressor. Run capacitor/start winding will add about 20% more current to total compressor current during run period. There is a 90 deg phase difference in Run and Start winding current so compressor common wire current will be sqrt ( (run winding current)^2 + (start winding current)^2 )
    Easystart BT also only reports the Run winding current so it is lower than actual compressor total current draw by about 20%.

  • @TheWabbit
    @TheWabbit Рік тому +1

    That was interesting, we Have almost the exact unit also installed in 2007, i replaced the old Gravity ( octopus) furnace added ducts and added A/C to my 1920s house. The compressor is pretty loud on start-ups but it's at the back of the house where the kitchen and bathroom are, so I'll leave mine alone. I can see why you would want to quiet down the almost violent start up though.
    Take care!

    • @DeckerChristopherJ
      @DeckerChristopherJ  Рік тому +2

      That’s funny that we both installed the same XR13 unit in our 1920’s houses in 2007. We added a/c to ours back then as well. I’ve done some re-ducting over the years as we’ve added on, but the unit has been flawless. I service the XV95 furnace every year myself, removing the burners and cleaning them, etc, but I haven’t touched the AC or even put a gauge on it. Still blows ice cold. I also think it’s funny you know exactly how loud the unit can be at startup! 😂. Thanks for watching and for the comment!

  • @user-tz8dp2mm8z
    @user-tz8dp2mm8z 3 місяці тому +1

    Had nothing but issues after a year with this micro air. Almost fried my compressor, had an AC tech come out and he removed the easy start and no more issues with my AC unit. If it would’ve damaged my compressor would’ve been out a lot of money. My issue was the AC unit would kick on and blow hot air, verified currents and Freon was good. Removed the micro air and everything went back to normal.

    • @mae2759
      @mae2759 21 день тому

      What brand is your AC?

  • @PH-md8xp
    @PH-md8xp 10 місяців тому +8

    Useful video. Your clamp meter appears to be malfunctioning. Using the “Peak” function isn’t really an accurate way to measure Inrush current. Clamp meters with a specific InRush feature are more accurate for this purpose. Also, on the video on UA-cam by MicroAir, he measures InRush current by clamping around the wire that goes to the Common terminal on the compressor, not the Run terminal.

    • @ElCarroSupremo
      @ElCarroSupremo 2 місяці тому

      Do you think it had a manual voltage that needed to be changed to 230~240V?

    • @PlymouthVT
      @PlymouthVT Місяць тому

      @@ElCarroSupremo no

  • @EdwardNY8
    @EdwardNY8 2 місяці тому

    Nice sounding startup compared to mine. Looking forward to your solar videos.

  • @GlenS123
    @GlenS123 Рік тому +2

    Looks good and seems to work. Trust the control, not your handheld meter. Meter can't accurately read it no matter what it says. Typically induction motors use 6 -7 times full or run load amps. Waiting for solar!

    • @kiowablue2862
      @kiowablue2862 11 місяців тому +1

      A meter with the capability to read *_inrush_* current *_can_* perform an accurate measurement.

  • @Phil_Schaffer
    @Phil_Schaffer Рік тому +6

    Nice video Chris, very neat and tidy install. Just one comment though. A soft starter isn't really considered to be an energy saving device. While it's true that during starting, there is a little less energy loss in the wiring from the panel to the compressor due to the reduced starting current, the running load of the compressor is still the same and that energy use far exceeds the small amount of energy used during a start. The actual starting energy used by the compressor at its terminals is essentially unchanged. What the soft starter is doing is gradually ramping up the voltage to the compressor which reduces the magnatizing inrush current. This makes it easier to start and reduces equipment wear but since inrush current is nearly all inductive, it has little effect on energy usage other than increased resistive losses in the wiring for a very short time.
    I've really enjoyed your snow melt system design and construction videos. Keep up the great work. Thanks

    • @DeckerChristopherJ
      @DeckerChristopherJ  Рік тому +3

      Thanks for your comments Phil, and I couldn’t agree with you more! I definitely mis-spoke by describing it as an energy saving device the way I did. What I meant was that it used much less “energy” in current exactly as you described. I haven’t tested it yet, but I have no doubt it would start now even running off my 7,500 watt generator! Something I wouldn’t even think about trying before. Anyways, thanks for the clarification and for your kind words on my projects. I appreciate having people like yourself as viewers! 😊

    • @stevekline5608
      @stevekline5608 Рік тому

      Phil, does it reduce noise at start up and shut down?

    • @Phil_Schaffer
      @Phil_Schaffer Рік тому +1

      @@stevekline5608 I don't actually have one myself but I have used much larger three phase versions in my professional life. Generally a soft starter won't have a significant effect on start up noise unless there are other factors at play such as a loose motor mount I my experience.

    • @stevekline5608
      @stevekline5608 Рік тому

      thanks for the reply.

  • @marynunn1708
    @marynunn1708 Рік тому +1

    Great job 👍
    The lower inrush current should allow you to run on a decent sized portable generator should the need arise (eg power out rainstorm skies overcast and solar not keeping up)

  • @Zimm.G
    @Zimm.G 10 місяців тому +1

    Thanks for the video. I'm about to do the same install on my Trane 3.5XR. I would have edited out the fussing with the clamp meter, but I have a Klein and it's super confusing to me too.

  • @Jim12291958
    @Jim12291958 10 місяців тому +1

    Good video... thanks

    • @DeckerChristopherJ
      @DeckerChristopherJ  10 місяців тому +2

      Glad you enjoyed it and hopefully found it helpful! Thanks for watching!

    • @Jim12291958
      @Jim12291958 10 місяців тому

      @@DeckerChristopherJ It was helpful and thanks again for taking the time to do this.

  • @kangaroogod
    @kangaroogod 11 місяців тому +9

    How did I miss this?? It appears you were taking your amp draw on red (run) and you should have been taking it on black (common). Orange (start) and red (run) are in parallel with the start having the capacitor.

    • @DeckerChristopherJ
      @DeckerChristopherJ  10 місяців тому +2

      That explains a lot! Thanks! Next time I have the cover off I’ll give it a shot and see if I get more reasonable numbers. 👍

    • @PlymouthVT
      @PlymouthVT Місяць тому

      Red wire is common but not a common ground it is power to the compressor. That's where you should be measuring.

  • @ryanmalin
    @ryanmalin Рік тому +2

    Great video. Nice house! Id suggest measuring in rush current from the compressor common wire.

    • @DeckerChristopherJ
      @DeckerChristopherJ  Рік тому +1

      Thanks Ryan! I’ll give it a shot next time I have the cover off and see if there is a difference. Thanks for your compliments on the house! I think you’ll like some of my upcoming solar videos! Thanks for watching!

    • @kiowablue2862
      @kiowablue2862 11 місяців тому

      Agreed. The common wire is where MicroAir development team engineer took his measurement from.
      Ref: ua-cam.com/video/bp4U-husy1o/v-deo.html

  • @jbhobbyist9372
    @jbhobbyist9372 8 днів тому

    Where is the little white temp sensor located or don't you have one? Also before you started your install was there a start capacitor and relay in the lower left side area that you removed?

  • @MADMIKE66
    @MADMIKE66 Місяць тому

    I was excited to get mine setup, and was disappointed to see that it didn’t reduce the output running power, just the initial startup. Guess I didn’t understand what the device actually did before I bought it.

  • @felaxchow207
    @felaxchow207 Рік тому +1

    Works great on my 2.5 ton heat pump. It dropped the LRA from 56 to 20 amps. I can heat or cool my 800 ft² home on a 9,600 Wp inverter generator or off the 13.2 kW UPS off the critical loads panel in a pinch. The overload protection feature in the unit is top-notch and has saved my compressor a couple of times due to the beginnings of a faulty run capacitor. The bluetooth interface is great feature to allow you to check on the overall health of the outdoor unit and diagnose any faults it might encounter.
    I had to my mine on the outside cover using stainless machine screw stand offs, so I have to unmount my EasyStart unit before I can remove the electrical service cover. Having a defrost control board took away the free space needed to mount inside the cover, but I gained a little bit more bluetooth range for the minor inconvenience.
    Looking forward on your solar journey, currently I have 7.2 kW of grid-tied solar and the critical loads UPS long before I had my solar system installed. The challenge is gettng both of them to play nice with each other when the grid goes down to have the ability to charge the batteries.

    • @DeckerChristopherJ
      @DeckerChristopherJ  Рік тому +2

      Great info! Thanks for sharing! Another viewer commented that my capacitor looked a bit puffy, so it’s good to know that the unit will provide protection if it starts failing! The Solar videos are coming soon, I’m editing them now! Thanks for watching and commenting, I appreciate it!

    • @RadioRich100
      @RadioRich100 Рік тому

      How can you possibly know what your LRA is? If your using a clamp meter they are far from accurate.

    • @felaxchow207
      @felaxchow207 Рік тому +1

      @@RadioRich100 easiest way to find out your outside unit's compressor LRA is on the specification label. However, most of the time it is quite sun faded and barely readable on older units.
      I use a Fluke 336 True RMS clamp meter and I find it pretty much spot on with the nameplate rating. The budget model clamp meters might put you in the ballpark. The variables that can throw things off is if the run capacitor is partially bad and drifting out of spec or there's a hard start kit added on that was not accounted for on the nameplate specs.

  • @Urugami45
    @Urugami45 Рік тому +3

    Thanks for the video. Can you tell us what the inrush current is now, after it's had a few dozen starts to learn the motor?

    • @DeckerChristopherJ
      @DeckerChristopherJ  Рік тому +4

      Last I checked after 30+ starts now that we’ve had the A/C on for a few days and it was down to 29.5. Hope that helps! Thanks for watching and commenting!

    • @Urugami45
      @Urugami45 Рік тому +1

      @@DeckerChristopherJ Thanks for the update. Yes, it helps. (And I fixed "Indian" to "inrush"... stupid autocorrect)

  • @mr.boniato6402
    @mr.boniato6402 Місяць тому

    Can I use Wago wire connectors for this?

  • @didyuknow
    @didyuknow Рік тому +2

    the start up current may have been very high because your compressor was already going bad? (i.e. low in oil? Have you been adding gas before without oil?)
    There should be a sticker on the outside of the unit indicating the LRA (Locked Rated Amps). A 3.5 ton unit should have typically 112A for LRA and 18 A for RLA (running load Amps). The strange thing on your meter was that it was indicating a peak of 16A even before the compressor was running. B more careful when mounting it and selecting max only after you have clamped the unit on the wire.

    • @DeckerChristopherJ
      @DeckerChristopherJ  Рік тому +2

      Yea, I noticed my meter was reading amperage even with the power to the unit off too. I believe my meter was inaccurate. I’m guessing my original startup amperage was around the stated 115, and this unit has brought it down to below 30.

  • @mikegreene9215
    @mikegreene9215 11 місяців тому +1

    I was just wondering the same thing about the starting amps on your unit.....164 did seem really high. I have a 2020 home 3.5 ton and my starting amps were 71.9 amps. Did you ever try again with another meter?

    • @DeckerChristopherJ
      @DeckerChristopherJ  10 місяців тому +1

      Hey Mike. I haven’t tried it again yet, but others have mentioned I may have been clamping onto the wrong wire. Next time I have the cover off, I’ll give it a shot. We haven’t used the AC much this summer as the weather has been mild here in Buffalo, but we do have it on today and I just checked the stats via Bluetooth. With 94 starts under its belt, it pulled 32.8 amps at last startup. It has been working great! Thanks for your comment and for watching!

  • @catfish500mark9
    @catfish500mark9 10 місяців тому

    Do these work on heat pumps?

  • @modestohodesto7140
    @modestohodesto7140 Рік тому +3

    Nice job. Please provide an update. I would also order a spare capacitor yours looks a little puffy on top.

    • @DeckerChristopherJ
      @DeckerChristopherJ  Рік тому +4

      Thanks for the kind comment and the suggestion! I didn’t notice the puffiness, but I will take your advice and order one to have on hand just in case! Thank you! 😊

  • @dboundscpa
    @dboundscpa 6 місяців тому +1

    I came across your video on installing the MicroAir Soft Start when looking for specific information about installing that device. Mine is slightly different in that it is for the larger AC, so it is the 72 instead of the 48. My problem is that my compressor is not kicking on after installation. The vendor who sold me the device has confirmed that my electrician has connected all the wires properly and has sent a replacement device, then confirmed again that wired connections are correct, but the compressor still does not start. All this is strictly on city power. I have given up on the process for a long time, but would REALLY like to get the soft start installed AND FUNCTIONAL. Any recommendations? Your video really didn't seem to address the wiring very much.

    • @Jcasta8
      @Jcasta8 Місяць тому

      Read the manual

  • @artmclellen4611
    @artmclellen4611 9 місяців тому +1

    you might try to zero it out by putting the clamp tip next to the wire on the out side of the circle at the tip.

  • @rbhndrsn14
    @rbhndrsn14 10 місяців тому

    Is that an R22 system? Seems that those compressors pull a little more amps than the newer models

  • @jazzmannca
    @jazzmannca Рік тому

    I've been researching soft starts, specifically the microair easystart 368 and have a question. Does this "investment" (because it's almost $400) save money on the monthly electric bill or is it saving money by extending the life of the capacitor or the condenser fan motor? Other than lowering the max amps, what is the benefit of installing this on a regular house condenser where there isn't a generator involved? Or should someone only install this if they're going to run the a/c on a generator? Is that the point?

    • @eugeneschwing4907
      @eugeneschwing4907 4 місяці тому

      They help tremendously if you are running your a/c with a generator. My 3-ton a/c went from 62 amps starting to 30 amps. I wish I had checked the running amps, the app shows 11.2 running amps when running though. I live in SE Louisiana and we have outages regularly due to storms, I can run my whole home on a 12kw generator with this installed. You will probably not save any money on your electric bill though.

  • @aholmes6612
    @aholmes6612 Місяць тому

    The X48 is for up to 3.5 tons, 4 to 6 tons requires the ASY-368-X72-Blue

  • @user78405
    @user78405 Місяць тому

    lot of times , its best get bigger power generator for your home that does not need this at all...lot of big box generac have higher cranking amperage for your ac and more devices in your home

  • @alejandroflores8610
    @alejandroflores8610 Рік тому

    Will it save me money on my energy bill?

  • @nolannsautodetail5468
    @nolannsautodetail5468 Рік тому

    Will that work with a carrier 4 ton. Or 4.5. Anyone know. Thank you in advance

    • @alexgarcia7401
      @alexgarcia7401 Рік тому +2

      ASY-368-X72-BLUE is the model you are looking for according to the micro air website. It will work with both 4ton or 4.5ton. The ASY-368-X48-BLUE looks like it will handle a 4ton as well but for the 4.5 ton the first one I mentioned will work.

  • @user-dc6mg2rk8p
    @user-dc6mg2rk8p 11 місяців тому

    Do I need a 368-48 or a 368-72 for a 4 ton?

    • @AbsolutePayroll
      @AbsolutePayroll 10 місяців тому +1

      the website will help you figure that out

  • @howardchang7429
    @howardchang7429 Годину тому

    meter reading definitely off. No one have a 200amp breaker for the AC.

  • @user78405
    @user78405 Місяць тому

    usually inverters don't need it when every split system all controlled by computer to softstart ...bad con to the idea is computers tend to fail easily than manual start that known always hard start by capacitor way give torque to push scroll compressor gear when its like your car starting a engine ...due to components in sealed compressor has oil in bottom and drive shaft to move gear on top to compression begins for freon do its magic . Another thing, condenser and evaporator has to be clean all the time or else your softstart gonna fail to start in lower amperage when dirty coils do need to hard start in higher amperage to push harder the compressor

  • @John-iv2oz
    @John-iv2oz Рік тому +2

    Dude, great video but did you see all that rust on your capacitor. It is about to fail. if you replace it also you will get even better economy on your electric bill.

    • @DeckerChristopherJ
      @DeckerChristopherJ  Рік тому +1

      Thanks for the kind comment and suggestion John! I have ordered a replacement! 👍

  • @didyuknow
    @didyuknow Рік тому +1

    you could have mounted the unit upside down, but I believe there is a note in the installation instructions not to do that?

    • @DeckerChristopherJ
      @DeckerChristopherJ  Рік тому +1

      I actually reached out to the manufacturer and asked if this was permissible before my installation and they said no. I believe they can be mounted in any orientation ACCEPT up side down. As you saw, I was able to get mine in there right side up so it all worked out! 😊 Good luck with your install, I’ve been very happy with the purchase so far. After 40+ starts I’m below 30A.

    • @didyuknow
      @didyuknow Рік тому +1

      @@DeckerChristopherJ i INSTALLED MINE AND THE SURGE CURRENT DROPPED FROM 100A cold start to 25A after the soft start was installed. very happy with the results. Folks remember to turn off also the switch located inside next to the inside unit.

    • @DeckerChristopherJ
      @DeckerChristopherJ  Рік тому +1

      @@didyuknow That’s awesome! Combined with all of the other protections the unit provides, and the fact that I could run it off my generator now, I’m happy with my purchase! Thanks for coming back to update!

  • @jaxsonhugh9334
    @jaxsonhugh9334 Рік тому +1

    That run capacitor is looking a little rough

  • @carlosreyes6448
    @carlosreyes6448 11 місяців тому

    Is that 30.5 amps at 240volts?

  • @bman6502
    @bman6502 2 місяці тому

    I understand the advantage of slow start if you want to run a generator, but is there really any advantage outside of that? And if so, why won’t manufacturers install at the factory???

    • @howardchang7429
      @howardchang7429 Годину тому

      It's optional for generator. Don't think makers will do it for free.

  • @richardgoff6739
    @richardgoff6739 21 день тому

    Wow, 163 amps.

  • @bigredwag
    @bigredwag Рік тому

    What's your calculated ROI?

    • @sigcrazy7
      @sigcrazy7 11 місяців тому +1

      An Easy Start doesn’t save any power, so there really isn’t a ROI calculation to be made, unless you can quantify how much longer the equipment will last, along with the lessening of stress on the rest of your house’s loads. That is a difficult number to figure. The real value of the soft starter is its ability to allow the compressor to run on a smaller backup power source. What is the ROI when the power is out for a week after a hurricane, and you’re still able to reside in your A/C cooled house during those 105° Houston days? In those conditions, the soft start would be priceless.

    • @sigcrazy7
      @sigcrazy7 11 місяців тому +1

      Another point. By installing a soft starter, you can lessen the size requirements of a whole-house generator installation. Whereas you may need a 25Kva unit to start your A/C without a soft start, you will do just fine with a 15 or even 12 Kva backup with a soft start. The savings from purchasing a smaller backup unit, along with the increased efficiency of running a smaller generator at a higher load vs an oversized generator at minimal load, will more than offset the cost of the soft starter. Most homes only use 1-2 Kva continuously, so a huge generator just to start the A/C isn’t an efficient way to go since it uses more fuel to simply spin the larger unit and run the larger engine.

    • @AbsolutePayroll
      @AbsolutePayroll 10 місяців тому

      @@sigcrazy7 in addition, it does save a tiny amount of power. For example, if the before start up is 100a and you have 26400 startups like the gentlemen stated above, then you install an easy start, and your startup is now 30a, then that 70a x 26400 startups can save you some $$$ because some power companies charge for peak. The best ROI is the the generator use and easier on the surge. For example, your car when it starts REVS at startup, then as the engine goes into idle you are saving engine wear and some gasoline.

    • @tonyd3266
      @tonyd3266 10 місяців тому +2

      With a 20kv whole house system with buried Gas being over $20k 9/2023 in Florida, my 5ton central air would be able to start and run on a $900 12kw portable gen for the 3-5 days we too often have out with down lines post hurricane beachside. After 25 years of dealing with hurricane aftermath I finally see a wiser path than the $20k generac that's used 4 days a year on avg.

  • @trith72
    @trith72 8 місяців тому

    Very likely your batteries were getting low in that meter, and that caused the false readings.

  • @bwoutrage21
    @bwoutrage21 11 місяців тому +1

    Came across your video. Your numbers are weird. I agree with others, the soft start will not save you much in energy cost, but maybe with solar it is a positive. If you were going to run a generator then the soft start like is a good investment. If not you maybe should have gone with a “hard start” kit. It will also drop the starting current draw to help the compressor. Each of the units are basically helping in saving the compressor. As far as noise, try a good quality compressor blanket. Again your numbers bother me. I would like to know what your panel sheet says for the start up amps ?? I bet when new the compressor was spec’ed out to draw maybe 25 - 30 amps at most even for a 3.5 ton unit. 3.5 tons and 16 yrs old …. Your reading of 100 amps is very possible. If that number is correct then your compressor is short time, and I would expect that a soft start or hard start kit would drop the start up amps to maybe 35 - 40 amps. If not using a generator I would have used a hard start kit. But the way you did the installation and how you used the meter tells me your the expert. If I were you I would have a good HVAC tech come out and check that system out with the soft start kit disconnected and then with the unit re-connected. Here’s a hint. Each season or whenever the unit is checked out, record the startup amps, voltages, pressures etc on the inside of the removable cover in perm marker with the dat checked. By the way start check your evaporator coiler signs of corrosion if you haven’t been doing that.

  • @RadioRich100
    @RadioRich100 Рік тому +1

    Those clamp meters are not accurate at measuring inrush current.

  • @anthonygambitta6220
    @anthonygambitta6220 Місяць тому

    My 3.5 ton unit is drawing only 117 amps during start, 24 amps running. Your meter is inaccurate or the A/C is very inefficient!

  • @ElCarroSupremo
    @ElCarroSupremo 2 місяці тому

    *People. Be careful around that cap. It'll sting you. And if your ticker has issues, it might stop you.*

  • @OnlyDrones
    @OnlyDrones 4 місяці тому +1

    Micro-Air does make an install Kit, ($10) that includes a Large Piece of Self-Adhesive Tape, that will work great and not chance Drilling into a component on the A/C.

  • @kenhamner2777
    @kenhamner2777 9 місяців тому

    Out of stock and back ordered everywhere I look 🤦🏼‍♂️

    • @DeckerChristopherJ
      @DeckerChristopherJ  8 місяців тому +1

      Ugh. I’m sorry to hear that. I noticed that it went out of stock a few times over the summer too, but seemed to come back relatively quickly. After a full summer of use, I’ve been very happy with the results and would install it again! Thanks for watching and commenting!

  • @johncarr123
    @johncarr123 10 місяців тому

    Use 26lb gorilla tape to mount the unit

  • @PlymouthVT
    @PlymouthVT Місяць тому

    Is the ac as cold as it was before you installed the soft start kit or does it not get as cold with the lower current draw? And how can you be pulling 163 amps through a 40 amp breaker in your breaker panel lol?

    • @dmbsituation
      @dmbsituation Місяць тому

      Though 163 seems high, lots of these are pulling momentary high amps on 40/50 amp breakers

    • @RobertCunningham-cw4bv
      @RobertCunningham-cw4bv Місяць тому

      Breakers don't trip on instantaneous current, they basically trip with the heat caused by a continuous overcurrent. Still in a short period of time but not in the 1/20th of a second of the startup current.

  • @Phone-sh7jg
    @Phone-sh7jg Рік тому +1

    How long does it take to instal?

    • @DeckerChristopherJ
      @DeckerChristopherJ  Рік тому +3

      It took me about an hour, but that included the extra time to setup cameras and explain what I was doing for the UA-cam video. You could probably get it done quicker. Hope that helps, thanks for watching!

    • @Phone-sh7jg
      @Phone-sh7jg Рік тому

      @@DeckerChristopherJ excellent vid!