PROFIBUS Rack Failure OB86 programming for SIEMENS TIA Portal | PROFIBUS DP

Поділитися
Вставка
  • Опубліковано 27 лис 2024

КОМЕНТАРІ • 28

  • @uxofpv5747
    @uxofpv5747 3 роки тому +1

    Muchas gracias, excelente vídeo.

    • @hdhosseini
      @hdhosseini  3 роки тому

      Thanks , please stay connected.

  • @fernandoosuna9622
    @fernandoosuna9622 3 роки тому +1

    I learned a lot with your video, Thank you so much!!

    • @hdhosseini
      @hdhosseini  3 роки тому

      Thanks , please stay connected.

  • @MrGrelen
    @MrGrelen 2 роки тому

    Tha k you for explaining 👍👍

    • @hdhosseini
      @hdhosseini  2 місяці тому

      Many thanks for your feedback.

  • @DDMMAGALHAES
    @DDMMAGALHAES 3 роки тому

    Is it possible use a s7 1200 to check it ?

  • @SpottedEagleOwls
    @SpottedEagleOwls 28 днів тому +1

    how can i prevent the cpu from stopping when ob86 is called

    • @hdhosseini
      @hdhosseini  День тому

      Please watch this video for answers:
      ua-cam.com/video/iNb1smwg5XQ/v-deo.html

  • @prashantpitroda2385
    @prashantpitroda2385 2 роки тому

    hello sir, this is the case of profibus, but if profinet slaves are there then where to write slave address or what slave address should be write?

  • @sinanartemis6176
    @sinanartemis6176 Місяць тому

    dear sir, do you have an online course i want to take. especially on simatic manager stl

    • @hdhosseini
      @hdhosseini  Місяць тому

      Thanks for your message, Please visit:
      hdhosseini.com
      If you are interested, please contact info@hdhosseini.com for creation of an account.

  • @osmarlima2012
    @osmarlima2012 3 роки тому

    Hi Hamid!! Good job!! Thank you for sharing with us, could you explain what is %LB11?

    • @hdhosseini
      @hdhosseini  3 роки тому +2

      Thanks for your message , LB11 is the local memory related to OB86 that keeps the slave address.

  • @kgauravb
    @kgauravb 4 роки тому

    Hi,
    What is B#16#39 and 38 command..??

    • @hdhosseini
      @hdhosseini  4 роки тому

      Thanks for your message:
      B#16#39 when the error occurs
      B#16#38 when the error clears

  • @vorapobautomation9760
    @vorapobautomation9760 4 роки тому

    How to show where is slave fault or which module fault in HMI ?

    • @hdhosseini
      @hdhosseini  4 роки тому

      when you have the slave number (e.g 3) , it is up to your creativity to select an alarm or a nice automation system structure then marking the failed slave.

  • @juanluisgtz8206
    @juanluisgtz8206 4 роки тому

    Nice vídeo!
    Could you explain how to call when a slot (digital card, analog) is going to fail?
    With profibus please

    • @hdhosseini
      @hdhosseini  4 роки тому

      Thanks for your message,
      First you need to have the module with diagnostic capabilities.Then , You can use OB82 for checking internal failures and OB83 for removing /inserting modules.
      Check the online help of STEP 7 or TIA Portal for more information.

  • @kgauravb
    @kgauravb 3 роки тому

    Hello very informative and thank you for sharing could you please tell how to store the last error state if error occurred only for few seconds and restore itself. How to know which station had a problem if it comes only for a second or two in a month or a week? I'm having an issue of plc going into stop mode..!! How to stop plc for going into stop mode my PLC model is s7-300

  • @derina.maleek9408
    @derina.maleek9408 4 роки тому

    Please more video on obs we want that subject thank you

    • @hdhosseini
      @hdhosseini  4 роки тому

      Thanks for your message , please stay connected for new related OB-related topics