RCD testing2 using Kyoritsu ELCB tester Model 5406A

Поділитися
Вставка
  • Опубліковано 12 гру 2024

КОМЕНТАРІ • 13

  • @kyoritsu7886
    @kyoritsu7886 3 місяці тому

    Hello, this is Kyoritsu Japan.
    It is so honor that you used our product.
    We highly trust we can learn more from your excellence in feedback on electrical equipment.

  • @denzyouchannel3284
    @denzyouchannel3284 Рік тому

    Can you make video how to test rcd 100mA

  • @alejandrodelacruz5439
    @alejandrodelacruz5439 5 років тому +1

    Is there kyoritsu tester rcd and insulation tester , where to buy and what model.. thanks

    • @ramokokorok9445
      @ramokokorok9445  5 років тому

      I happen to be residing in Singapore. So i could get equipment and tool like this easily through local distributor. So for my region, testing tool distributors like CE-TM and Allmeasures etc.

    • @Dog-whisperer7494
      @Dog-whisperer7494 3 роки тому

      That tester is made by kewtech industries .

  • @alejandrodelacruz5439
    @alejandrodelacruz5439 5 років тому

    Hi, can i use this device in GCFI is it the same procedure. ia am confused with with rcd and gcfi is it the same.thanks

    • @ramokokorok9445
      @ramokokorok9445  5 років тому

      Hi Adjhie, thanks for watching my video. The testing method is similar, however, this tester is designed for IEC testing procedures.

  • @ahmad7825
    @ahmad7825 5 років тому

    how to test 100ma sensitivity rcd?

    • @ramokokorok9445
      @ramokokorok9445  4 роки тому +1

      The selector may be changed to 200mA while another selector will change to "half".

  • @markiim9623
    @markiim9623 4 роки тому

    Can you test at 180degree?

    • @markiim9623
      @markiim9623 4 роки тому

      So the 10mA RCD is able to discriminate anything

    • @ramokokorok9445
      @ramokokorok9445  4 роки тому

      BS7288 did not mandate 180deg / inverted phase testing. As far as i have read, did not find any reference to 180deg/ inverted testing for SRCD. Havent checked in UL though. Do share with me if you have any lead. I could ask a pal in US.

    • @Dog-whisperer7494
      @Dog-whisperer7494 3 роки тому +2

      @@ramokokorok9445 you should do all RCD test at haft time /One times/ and fives times and on 0 d and 180d for each test this is for each of the rated current of each RCD , half times RCD should not trip 1 time RCD should trip within 300ms and at 5 times RCD should trip within 40ms