    Sir please explain about level calculation for guided wave radar transmitter
    Example : Probe length 850mm
    Upper incitive 250mm
    Lower inactive 120mm
    Hence what is Cal range? I mean LRV and URV

    • @eFundaChannel
      @eFundaChannel  2 роки тому

      Please note that typical method of selection of probe & calibration range consider the following:
      1) Height of Chamber or Vessel where probe is going to Insert ;
      2) Inactive zones to be minus ( Upper & Lower); Upper Dead band is adjustable (Probe Joint to Sensor Head and part falling under Nozzle projection) and lower is fixed at the bottom of probe.
      3) Calibration Range in simplified term (Cal. Range = Difference between Upper & Lower Band) is actual measuring range.
      e.g. If probe length is 850; Upper inactive is 250mm & lower inactive is 120mm (in total370 to be minuses) remaining is 480mm (LRV: 0mm from bottom & as moving towards sensor head URV:480mm).
      Hope this will help to clarify.