Daikin VRV3 | How to rectify error code E6 (replace compressor)
Вставка
- Опубліковано 9 лют 2025
- Brand : Daikin VRV3
modrl : RXQ10PAY13
compressor type : 1 Inverter compressor and 1standard compressor.
Error code : E6
standard compressor over amps.
(more than 10amps)
#Daikin #VRV3 #VRV #VRV4
Nice sir because of your videos i learned a lot about trouble shooting thank you and god bless ,, i '' '' m in philippines
Thanks bro.
Help share ya.
Nice video uncle 👍🏽👍🏽👍🏽
Thanks
Thanks a lot bhon
Thanks
Sir Bon do you pump down it or or need to recover the refrigerant while on emergency settings?
Good job my friend!
Thanks
thanks sir Bon
💞
Great video. Can you make more videos using Bluetooth D checker?
Thanks
No problem
@@BonMj Bon do you recommend Bluetooth checker for commercial applications? People say you can’t command coils on or off through app.
@@epicone2449 Bluetooth checker is good but expensive.
@@epicone2449 yes ,cant on and off through app
Nice video sir.
Before you unjoint compressor you pump the freon indoor side or released?
Indoor side
nice sir
Thanks
@@BonMj Welcome Sir
Do you need to vaccuum the lines before powering on the unit after replacing the compressor?
Only CU.
How to set vaacum mode in vrv 3 and when set vaccum uses share plz
What reading inverter compressor when faulty ??
Check other video got show
Sir , why it is mentioned three phase on compressor. 380 - 415 Instead of DC. I see on the make compressors it will clearly mentioned dc and frequency range from 70 to 180.
This is 3phase compressor
M.Mujeeb don't be confuse in some condenser unit of VRV 3 ,one of the compressor installed is standard compressor,it's not driven by IPM board which is for inverter compressor only.
In Australia it is illegal to release gas into the atmosphere, Which service port would you reclaim from after closing service valves?
Daikin .system 1 ..wall mount ..also error code E6. if on the Aircon , few seconds only compressor and fan running after that not run...will you give good advise.pls
Check power supply voltage, may compressor or pcb faulty
👍🇹🇷
Bro vrv iv error code f4 -04problem all light blinking cheng EEV but problem is not solve ,how many problems....???please Reply Bon sir
Please check indoor EEV.
May indoor EEV not functioning well
Plz making a video with subtitles plz
My friend.. Mitsubishi vrv city multi error code 7117.what is tha problem pls tall me
Check control pcb to inverter pcb connection any loose.
Or one of the pcb faulty
How much HP LP setting please tell me
VRV 3
Normally LP=100 to 120, HP=380 to 400psi
@@BonMjvrv3 standard one compressors faulty conturul pcp this setting compressor change ges recover peping how much setting
@@expertair8641 single CU or multi CU
Single CU is set 19 times
Sir How to find out how many hp
By model
@@BonMjsir give me 1example plz
@@mdafsarkhan9278 RXQ10AYM =10HP
@@BonMj thanks sir
@@mdafsarkhan9278 welcome
Hello sir bon.
I also encountered that problem but there is no error.
The magnetic contactor will engage but I can only hear the standard compressor jam or it's like humming sound.
So I decided to replace the compressor . Hope my diagnose is correct
Idu all light blinking
Outdoor blinking F4-04 but sometimes cu still working