ASi fault find - checking symmetry

Поділитися
Вставка
  • Опубліковано 5 жов 2024

КОМЕНТАРІ • 9

  • @FQP-7024
    @FQP-7024 3 роки тому

    Very interesting, nice change in content. 😉👍

    • @barryc1701
      @barryc1701  9 місяців тому +1

      Yes +15v to shield and -15v to shield.

  • @euclisesberreshity6167
    @euclisesberreshity6167 9 місяців тому

    Good afternoon sr. Let's see if i got pretty well what you've told in this video. So, you mean if i meassure the positive + ground we have to have 15volts ?

  • @minhanh5580
    @minhanh5580 Місяць тому

    Hello. Sir, could you please advise me on how to configure the Asi master of the Ac13xx series with Asi slave interfaces such as Emergencystop or Ac2410, Ac2412 Do I need to use any software or do the configuration directly on the Asi master keyboard? Thanks

    • @barryc1701
      @barryc1701  Місяць тому

      @@minhanh5580 to add a new slave you need to address it first. All new slaves have a default address of 0. Easiest was is to use an addressing tool like the AC1154. Once addressed you can add them to the network and this will put the AC13xx into fault, this is expected. In the controllers menu find the command quick setup and this add the new slave to the network list and clear the fault. That is all you need to do.

    • @minhanh5580
      @minhanh5580 Місяць тому

      @@barryc1701 Yes. Can you explain to me how the Asi master controller AC13xx can recognize the characteristics of each slave device? Even though I understand when adding a new slave device using the addressing tool like AC1154. For example, "I have an emergency stop button and an AC2412. How does the Asi master controller know that it is an emergency stop button and recognize that it is AC2412 I/O for control"?

    • @barryc1701
      @barryc1701  Місяць тому

      @@minhanh5580each slave has an asi profile. When you do a quick setup in the master this profile is also saved. This allows the master to identify if the slave is a digital I\O, analogue or a safety slave.

    • @minhanh5580
      @minhanh5580 Місяць тому

      @@barryc1701 My factory is currently using a faulty AC1335 Asi central unit displaying an error "control 30 devices from different brands" with a broken LCD screen. Now, I want to replace it with a new AC1335 central unit from Asi with quick address setting in the master menu to configure slaves 1 to 30, right? Thank you for the very helpful information.