Todays repairs
Todays repairs
  • 87
  • 18 242
Seasons 4 No AC Dehumidification
Seasons 4 AC would not come on, store was humid, all of frozen food dripping with condensation. Found inverter stuck at 18hz, so main blower was not turning fast enough to activate air switch relay, which was keeping the AC off. Put the inverter into hand and brought it up to 50hz, AC fired off.
Переглядів: 10

Відео

Evaporator coil plugged no airflow
Переглядів 967 годин тому
No AC call, found evaporator coil plugged with dust and dirt. Maintenance is so important
Blown capacitor on Copeland Compressor
Переглядів 407 годин тому
Copeland capacitor blown, compressor not running.
Klien circuit tester
Переглядів 369 годин тому
Klien circuit tester, what a great tool!!!!!!!!!!!
Oil Failure tripped breaker
Переглядів 3612 годин тому
Had a call for an oil failure on a Bitzer Compressor, found tripped breaker, bad contactor, due to a rub through on one of the 8 gauge wires going to the compressor from the contactor.
Season 4 Ventor Motor
Переглядів 7214 днів тому
Seasons 4 Power flame Ventor motor replacement. Heat was not working, store was cold and damp. We run heat all year long as the seasons 4 does not have any type of dehumidification system. Basically you run the AC off of the humidity in the store, when the store gets to cold the heat will come on to warm it up, while the AC is still running.
Starting the condenser fan motors Hoffman Control
Переглядів 4921 день тому
Wired in LiL Popper, testing Hoffman control to see if it will work
Seasons 4 Condenser fans not coming on
Переглядів 5921 день тому
Seasons 4 Condenser fan motors not coming on and all 4 scroll compressors tripped on high pressure. Found only 9-10 volts going to the Hoffmann control for the condenser fan motors. Voltage going to Hoffmann control was to low, needs to be 24 volts. Had 24 volts going to the top of the fuse and only 9-10 volts coming out. Installed a 5 amp Lil Popper to take the place of the fuse for now. Had t...
Changing hot gas solenoid parts
Переглядів 6021 день тому
Multi deck meat case not going into hot gas defrost, all Iced up and in alarm. Had to rebuild the hot gas solenoid. for some reason it would not open up when the solenoid was energized. Rebuilt it and it was fine.
Evaporator Tripping Breaker
Переглядів 3521 день тому
Grocery Freezer Evaporator tripping breaker. Found wire rubbed through motor and took out the circuit breaker. Reset the breaker but the fans did not come on. It blew the wire apart. Had to splice the wires back together.
Frozen Food Anti sweats not working
Переглядів 5521 день тому
Frozen food 5 doors anti sweats not working. The circuit breaker was tripped. Found wires shorted out in race way. Nothing like working with wiring that's in water.
Changing Powerlink breaker 1
Переглядів 39728 днів тому
Changing a Powerlink breaker for electric defrost.
Grocery Freezer Noisy Evap
Переглядів 34Місяць тому
Grocery freezer evaporator making noise. Broken fan blade and mounting holes. Made a repair using fender washers.
Blown Condenser Fan Motor
Переглядів 20Місяць тому
Received a service call for a Continental 3 door freezer in alarm. Found a bad 208-230 volt condenser fan motor. I replaced it with a rescue motor that is good from 115 volt - 230 volts. Worked perfect. Had to pack the compressor with ice to cool it down. It was as hot as a firecracker.
Traulsen Evaporator Leak
Переглядів 25Місяць тому
Traulsen 3 door freezer. Low on refrigerant, not making temperature. Found leak on evaporator coil. Using an H10 leak detector. Will have to replace the evaporator coil.
Blown solenoid coil
Переглядів 379Місяць тому
Blown solenoid coil
Welding a uboat
Переглядів 185Місяць тому
Welding a uboat
Motor bolts coming out of motor
Переглядів 46Місяць тому
Motor bolts coming out of motor
Liquid Line Core Drier Plugged Up
Переглядів 142Місяць тому
Liquid Line Core Drier Plugged Up
Deli Cooler Liquid Line Solenoid
Переглядів 11Місяць тому
Deli Cooler Liquid Line Solenoid
Schrader tool removal
Переглядів 8Місяць тому
Schrader tool removal
Rock Rocker Pressure Washer
Переглядів 228Місяць тому
Rock Rocker Pressure Washer
comparing an old Amprobe to a newer Fluke
Переглядів 18Місяць тому
comparing an old Amprobe to a newer Fluke
Trane Condenser Fan Motor Change
Переглядів 17Місяць тому
Trane Condenser Fan Motor Change
Multi Deck Deli Case Leaking water
Переглядів 12Місяць тому
Multi Deck Deli Case Leaking water
Video2 Traulsen Freezer
Переглядів 32 місяці тому
Video2 Traulsen Freezer
Video1 Traulsen Freezer Tripping Circuit Breaker
Переглядів 602 місяці тому
Video1 Traulsen Freezer Tripping Circuit Breaker
changing condenser fan motor
Переглядів 3002 місяці тому
changing condenser fan motor
Multi Deck Self contained
Переглядів 272 місяці тому
Multi Deck Self contained
Hussmann Anti sweat harness
Переглядів 202 місяці тому
Hussmann Anti sweat harness

КОМЕНТАРІ

  • @jaredvanpelt8947
    @jaredvanpelt8947 День тому

    The gallon size of the blue condenser coil cleaner is easily the best bang for your buck if you rinse very well with a hose no damage or smell is caused to the costumer and it cleans extremely effectively, I do recommend a mask. It is no joke.

  • @billhofmann1188
    @billhofmann1188 2 дні тому

    Dirty!

    • @todaysrepairs
      @todaysrepairs День тому

      Yes wasn't easy to get it clean, had to take off the back end of the unit to get to the entire coil.

  • @elvissalcinovic9711
    @elvissalcinovic9711 16 днів тому

    What is your job title? And do you guys have any control engineers at your workplace?

    • @todaysrepairs
      @todaysrepairs День тому

      I'm a refrigeration Tech/Mechanic, we don't have any control people, everything is under contract. Thank you

  • @leocheng9346
    @leocheng9346 27 днів тому

    Hi, I also have an Ardco door. I overadjusted the door closer ratchet mechanism (the thing which goes on top of the rod) and I am unsure if I broke something. I recently took off the door and when I flipped the door upside down the rod was able to slide out from the channel. Do I need to buy a replacement part or if I pry the metal channel would I be able to reassemble the rod back into place? Thank you so much!

    • @todaysrepairs
      @todaysrepairs 25 днів тому

      Hello, most likely you broke the torsion rod. You can buy a replacement kit with all of the pieces you need to rebuild the door. When you receive the new torsion rod you will have to cut it to the length that you want. If you gently take the aluminum off, you will be able to get to all of the parts inside the channel. When putting the aluminum back, I use either a pair of channel locks with tape wrapped around the jaws as not to scratch the door or a pair of channel locks for doing toilets and plumbing (no teethe) some guys can just snap it back into place, I need to use the channel locks. If you have the numbers off of the door, I believe the company is Dover Food Retail. Hope this helps. Thankyou

  • @boginet17
    @boginet17 Місяць тому

    its agood circuit

  • @Goonerbro420
    @Goonerbro420 Місяць тому

    that hurt watching you go over paint like that

    • @todaysrepairs
      @todaysrepairs Місяць тому

      Your right, I should have cleaned it up first, that would have been the right thing to do. Thanks for watching.

  • @billhofmann1188
    @billhofmann1188 Місяць тому

    What technique!

    • @todaysrepairs
      @todaysrepairs Місяць тому

      I should have cleaned it up and made a better ground, the rod wouldn't have stuck as much. I had refrigeration issues I had to get to. Thanks for watching

  • @Paine137
    @Paine137 Місяць тому

    I find that it works better to lower the level. If it hits 99, there’s too much signal. Topping out under 99 then allows you to see a nuanced difference between proximate breakers, which dials the accuracy in.

    • @todaysrepairs
      @todaysrepairs Місяць тому

      Thank you for the tech tip. I will try it on a lower level.

  • @davidl3830
    @davidl3830 Місяць тому

    Great video, to the point!

  • @chrisretired5379
    @chrisretired5379 2 місяці тому

    Bought one of these units as well. Great for underground circuits in concrete floors, and outside in the dirt. 👍👍👍👍

  • @Derkiesmefpipe
    @Derkiesmefpipe 2 місяці тому

    350 lol

    • @todaysrepairs
      @todaysrepairs 2 місяці тому

      Yes I know, you can buy these for around 250.00, Unfortunately, the company I work for had to buy it through Grainger, they charged us $350.00. It pays to shop around if you can.

  • @kalinin191
    @kalinin191 2 місяці тому

    Great video, short, straight to the point, solution at the end, beautiful

    • @todaysrepairs
      @todaysrepairs 2 місяці тому

      Thank you, I try to keep the videos short. Hopefully someone can learn something from them. No reason to do a video that last a half an hour. Thank you

    • @kalinin191
      @kalinin191 2 місяці тому

      @@todaysrepairs long form are a good time if you can maintain the same quality as your short, james butler well and septic has great videos long and short, hes a great story teller

  • @paulcoulter7181
    @paulcoulter7181 2 місяці тому

    That looks to be for a York.

    • @todaysrepairs
      @todaysrepairs 2 місяці тому

      It maybe a York, it actually came out of an Octagon Main Unit for a supermarket. United Refrigeration could not match anything up. Octagon went out of business years ago. Thank you

  • @happytrails5342
    @happytrails5342 2 місяці тому

    Nice flashlight, what brand?

    • @todaysrepairs
      @todaysrepairs 2 місяці тому

      It is a Klien rechargeable. It also has a laser pointer built into it. Thank you

  • @davidl3830
    @davidl3830 2 місяці тому

    Nice

  • @jimhrn8522
    @jimhrn8522 3 місяці тому

    Opposite end bearing floats should have come out with rotor.

    • @todaysrepairs
      @todaysrepairs 3 місяці тому

      You are 100% correct, most of the time lower bearing comes out with the rotor and I replace both

  • @jimhrn8522
    @jimhrn8522 3 місяці тому

    Bad opposite end shaft, bearing should be there, quick metal is your friend.