VRV IV Emergency Function and A1P Board - Compressors
So, you troubleshot a Daikin VRV IV and found the primary compressor has failed and is keeping the unit from operating. The Pros are here to show you how to access Emergency Mode on the A1P board, providing a clear, step-by-step guide to restore functionality and get the system back up and running smoothly.
After your faults are cleared:
Press & Hold the "Mode” button for 5 seconds or so.
* This brings you to Setting Mode 2, displayed as "2.00"
Press & Hold the “Set” button til the counter hits "38".
* "38" is the selection to lock out the primary compressor. "39" would lock out the sub compressor.
** If you miss "38", keep holding the button down; after reaching "99" the count restarts at 1.
Press "Return" once, the display will flash "0"
* Now you're in Emergency Mode and can begin to lock out your primary compressor.
Press the "Set" button, the display will now read "1"
* You've now SELECTED the primary compressor, but haven't told the board to do anything yet.
Press "Return" 2x
* Pressing "Return" once will lock your selection in, pressing a second time will activate the setting.
Your primary compressor is now locked out! Your condenser can run off the sub-compressor.
DON'T LEAVE THE UNIT IN EMERGENCY MODE FOR TOO LONG! The added stress of running a single compressor can cause early failure.
Get your repair scheduled and parts ordered.
Once you DO complete the repairs, don't forget to restore function to your primary compressor-
Hold "Mode" for 5 seconds for so til "2.00" displays.
Press "Set" until you get to "2.38"
Press "Return" and the display should read "1".
* This means the mode is still active.
Press "Set" until the display reads "0"
Press "Return" 2x to restore operation to the Primary compressor.
For more informative videos on HVAC tutorials, cooling, RTUs, Vertical Self Contain units, BACnet controls, engineering, construction, facilities, and skilled trades, check out @MechanicalPros
Visit MRG's website at www.mechanicalresource.com to learn more about our services.
#hvac #vrv #construction #mechanical #skilledtrades #mechanicalpros #MechanicalResourceGroup #engineering #maintenance
Переглядів: 365

Відео

MCS Control Panels: Your Non-Proprietary Game-Changer
Переглядів 6208 місяців тому
Micro Controls Systems offers a versatile, non-proprietary solution, allowing you to tailor your control panel to your exact needs. Whether you opt for the basic package or prefer to customize in the field, the flexibility is yours. Unlike many panels on the market, MCS comes with a user-friendly touchscreen interface that's like having the entire chiller's vital signs right at your fingertips,...
Chiller Wisdom: Leveraging Group Know-How
Переглядів 1988 місяців тому
As a technician, joining a chiller group can be a game-changer for you. Here's the rundown: Troubleshooting: Got a head-scratcher of a chiller problem? Toss it into the group. You'll likely get a fix that's been field-tested and isn't in the manuals. Networking: It's not just about fixing chillers. These groups can connect you with folks who can throw business your way or share a lead on the la...
Ditching Wire Nuts: Reliable Motor Connections Explained
Переглядів 1,2 тис.9 місяців тому
In the world of motor connections, following the rules is crucial. NFPA 79-2007 clause 13.5 9.2 is clear: "Electrical connections at motor terminal boxes shall be made with an identified method of connection. Twist-on wire connections shall not be used for this purpose." 📜 But what happens when motor terminal boxes keep getting smaller, making a solid connection a tight squeeze? 🤔 That's where ...
Critical Motor Connection: Why Wire Nuts Won't Cut It ⚡❌
Переглядів 4839 місяців тому
⚡💡 Wire nuts - they seem cheap and convenient, right? 💲🔌 But hold on! 🛑 When it comes to motor connections, they're a big no-no! ❌🔥 These little guys aren't cut out for the current and can lead to motor failure. 😱 Learn why NFPA 79-2007 clause 13.5 9.2 is a must-know for your electrical knowledge bank. 💡📚 #ElectricalSafety #MotorConnections #NFPA79 Visit MRG's website at www.mechanicalresource....
When the Job Gets Derailed
Переглядів 3779 місяців тому
We began our HVAC diagnostic mission geared up to tackle superheat and subcooling adjustments🌡️💧. However, we encountered an immediate challenge. Despite the condenser fan operating smoothly, the suction pressure unexpectedly plummeted to around 50 psi 🤔🔌. This anomaly triggered recurrent on-off cycles due to the low-pressure switch. In response, we swiftly transitioned into a comprehensive dia...
Electronic Leak Detector vs Evaporator Coil
Переглядів 2809 місяців тому
🔍 After applying Cal Blue spray to the joints and brazed sections without detecting any leaks, the next step in pinpointing a refrigerant leak using an electronic detector is to head straight for the evaporator coil. 🕵️‍♂️ Begin by removing the drain pan, ensuring it's dry, and then carefully insert the leak detector into the drain pan. 🩺 If the detector starts beeping in this area, you've succ...
Mastering the Art of Pipe Grooving: Setting Your Attachment Right!
Переглядів 6139 місяців тому
When grooving pipes for HVAC systems like cooling towers and chillers, one thing you don't want is an inconsistent connection. That's why it's crucial to set your Groover attachment correctly. Using a Rigid Powerdrive 300 with a Rigid 975 Combo Roll Groover attachment, we'll guide you through the process. Remember, don't turn too quickly, or you might end up with an oblong groove that can compr...
Pipe Grooving: Tips for Consistent Connections
Переглядів 18510 місяців тому
Learn one of the keys to achieving perfect pipe grooves with a Rigid 975 in a sneak peak of our latest tutorial. Graham's advice ensures your grooves are consistently even and leads to reliable connections every time. Join us to enhance your pipe grooving skills! Visit MRG's website at www.mechanicalresource.com to learn more about our services. You can also find us on social media: Facebook: f...
Mastering Copper Pipe Flares: DIY Techniques for HVAC Pros
Переглядів 2,1 тис.10 місяців тому
In our latest video tutorial, we're diving into the art of crafting perfect copper pipe flares for your HVAC projects. Step up your skills as we guide you through the steps of creating flawless flares using a clutch flare tool. Because when it comes to ensuring a leak-free system, trusting the manufacturer's flares isn't enough. Learn from the pros and avoid common blunders like forgetting to d...
Brazing and Soft Soldering: Techniques, Tools, and Tips
Переглядів 77310 місяців тому
Explore the world of brazing and soft soldering with our comprehensive tutorial, designed for technicians seeking hands-on insights. 🔥 Follow our step-by-step guide as we delve into essential techniques, from mastering flame color to torch positioning 🔵🕯️, while utilizing tools like the sil-fos brazing rod and a B tank torch 🛠️🔗. But before we light up the torch, let's talk about a crucial foun...
Brazing & Soft Soldering
Переглядів 19510 місяців тому
Explore the fundamentals of brazing and soft soldering in this preview. Join us as we delve into the essential techniques that form the backbone of HVAC work. With a live demonstration on the horizon, get ready to enhance your skills and elevate your craftsmanship in the world of HVAC. Stay tuned for the full-length tutorial where we break down the process step by step! 🔥🛠️ Visit MRG's website ...
Compressor Autopsy #2
Переглядів 84711 місяців тому
Our cutting-edge custom compressor cutter opener(a technical term, don't ya know?) is officially up and running. Tune in as we make the first incision into a failed compressor and discuss the clues that led to its untimely demise. 😱 From worn bearings to electrical anomalies, we are committed to uncovering the truth. 🔎🕵️‍♂️ As Quentin will tell you, "Compressors don't die, they're murdered". Fo...
Quick Guide: Browning Belt Tension Checker in Action! 🛠️🔍
Переглядів 1,6 тис.11 місяців тому
Need to get accurate belt tension measurements? 🔧 In this 3-minute guide, we'll show you the ropes on using the Browning Belt Tension Checker. Proper belt tension is crucial for the longevity and efficiency of your equipment. 🛠️ Learn the step-by-step process of how to effectively use the tool, ensuring you get consistent and precise readings every time. 📊 Whether you're new to the tool or just...
Mastering Motor Maintenance: Correctly Greasing Bearings
Переглядів 2,9 тис.11 місяців тому
Did you know that a whopping 40% of motor bearing failures can be attributed to improper greasing? Whether it's too much, too little, or the wrong type, getting the lubrication just right is essential for optimal motor performance and longevity. 🛠️⚙️ Join Bryan as he demystifies the art and science of motor bearing lubrication in this comprehensive guide. He demonstrates, step-by-step, how to c...
Debuting the Ultimate Compressor Autopsy Station
Переглядів 46211 місяців тому
Debuting the Ultimate Compressor Autopsy Station
Eliminate A/C Condensate Damage with Proven HVAC Tools: P-Traps, Drain Guns, Pumps & More!
Переглядів 47311 місяців тому
Eliminate A/C Condensate Damage with Proven HVAC Tools: P-Traps, Drain Guns, Pumps & More!
P-Traps 101: Tools & Tips for Smooth Drains
Переглядів 44011 місяців тому
P-Traps 101: Tools & Tips for Smooth Drains
🔌⚡ Master Mini Split Wiring: Ultimate Guide for Peak Performance! 🛠️💨
Переглядів 12 тис.11 місяців тому
🔌⚡ Master Mini Split Wiring: Ultimate Guide for Peak Performance! 🛠️💨
🔌⚡ Wire a Mini Split Like a Pro: Sneak Peek Inside the Ultimate Guide! 🛠️💨
Переглядів 18811 місяців тому
🔌⚡ Wire a Mini Split Like a Pro: Sneak Peek Inside the Ultimate Guide! 🛠️💨
Mastering Cooling Tower Setup: Key Installation Tips for Optimal Performance and Longevity!
Переглядів 484Рік тому
Mastering Cooling Tower Setup: Key Installation Tips for Optimal Performance and Longevity!
Unveiling the Power of the GPS DM-2 Demo Unit: Agglomeration in Action!
Переглядів 211Рік тому
Unveiling the Power of the GPS DM-2 Demo Unit: Agglomeration in Action!
The Full Potential of Your GPS DM-2: The Importance of Proper Placement
Переглядів 118Рік тому
The Full Potential of Your GPS DM-2: The Importance of Proper Placement
Simplifying Installation, Enhancing Performance: Centrotherm's Ventilation Pipes
Переглядів 216Рік тому
Simplifying Installation, Enhancing Performance: Centrotherm's Ventilation Pipes
Effortless Venting: Centrotherm's Hassle-Free Gasketed Design
Переглядів 182Рік тому
Effortless Venting: Centrotherm's Hassle-Free Gasketed Design
Essential Cooling Tower Safety: The Importance of Shutting Off Your VFD First!
Переглядів 245Рік тому
Essential Cooling Tower Safety: The Importance of Shutting Off Your VFD First!
Cooling Tower Gearbox Maintenance: Key Tips for Peak Performance
Переглядів 694Рік тому
Cooling Tower Gearbox Maintenance: Key Tips for Peak Performance
Efficient Condensate Management: How to Set Your Daikin Navigator to Forced Off Mode
Переглядів 551Рік тому
Efficient Condensate Management: How to Set Your Daikin Navigator to Forced Off Mode
Mastering Air Louver Settings on Daikin Navigator
Переглядів 356Рік тому
Mastering Air Louver Settings on Daikin Navigator
Getting Your Air in Order: Achieving Perfect Distribution with Daikin Navigator
Переглядів 214Рік тому
Getting Your Air in Order: Achieving Perfect Distribution with Daikin Navigator

КОМЕНТАРІ

  • @manuellastrollo2168
    @manuellastrollo2168 День тому

    Sir want to see your control circuit of 12 leads

  • @anthonystewart4369
    @anthonystewart4369 6 днів тому

    That inverter board looks the same as the LG multi v board

  • @spydermaaaan
    @spydermaaaan 15 днів тому

    Very clear Thank you!!

  • @robertobat9072
    @robertobat9072 17 днів тому

    Hi there we have 6 of them units on a building an we have nothing but trouble almost every unit have blown compressors and can not find a solution any ideal

  • @trevernunez9177
    @trevernunez9177 18 днів тому

    How do you actually get to the Daikin fan board in the emerion?

  • @andys5203
    @andys5203 19 днів тому

    Great video. Do you have to shut the condenser off to check the wet bulb? Thks

  • @lwh7301
    @lwh7301 21 день тому

    Seems like every video like this glosses over the most important point of figuring when to add/subtract refrigerant in a few seconds, and then takes a minute talking about cleaning the filter.

  • @kylebell7879
    @kylebell7879 22 дні тому

    Is that temp chart valid for r12?

  • @ryanmicallef3328
    @ryanmicallef3328 25 днів тому

    Is it possible to get a recording off the service checker and put it into a file to then be able to put it into an email

  • @dereksosa5801
    @dereksosa5801 26 днів тому

    Nice video thank you

  • @TheIceman101
    @TheIceman101 29 днів тому

    I have the same Issue, headed out to clean one this morning.

    • @TheIceman101
      @TheIceman101 15 днів тому

      Cleaned out the water loop, now the unit is good but the tower needs to be serviced like right now. Water looks like coffee.

  • @SteveCaps-pj9xz
    @SteveCaps-pj9xz Місяць тому

    Hello there. Can you operate the oil pump and guide vanes to test their operation when doing an annual maintenance on the chiller? Thanks.

  • @TexByte
    @TexByte Місяць тому

    Thank you so much . This helped me fix a WSHP.

  • @jeffshore682
    @jeffshore682 Місяць тому

    Good video, there are a few drawbacks to the H10- just remember to stay away from wet coils, as the air pump will suck moisture into the heated diode and cause problems, making you have to pull the sensor out and dry it out with nitrogen. Another issue is the sensors tend to wear out and need replacing after a lot of use. The little leak calibration bottle will leak out and evaporate quickly in warm climates. I use infrared leak detectors nowadays as you don't need to worry about moisture and the sensors last a very long time. I have over 40 years of experience in the trade and started out using the H 10 and many techs do agree that its a great unit.

  • @diegofelix3108
    @diegofelix3108 Місяць тому

    Hello can make my hermostat to shut off at 1 ° difference from the setting that I have it indoor?

    • @diegofelix3108
      @diegofelix3108 Місяць тому

      Because I have a wired remote controlled and always turn of at 4 ° difference from the setting that I have it if you can help me out I would really appreciate it thank you

  • @user-rh3mt7df4m
    @user-rh3mt7df4m Місяць тому

    Can Explain how to connect with tayp 3

  • @marknasri1201
    @marknasri1201 Місяць тому

    Thx

  • @logan12-k4k
    @logan12-k4k Місяць тому

    What size are the two screws that hold the feet?

  • @user-mn2dk4yp2v
    @user-mn2dk4yp2v Місяць тому

    🎉important info man

  • @DG-Chiefs-fan
    @DG-Chiefs-fan Місяць тому

    I’m very new at HVAC and this helps me understand better. Great video thanks from all of the newer people getting into the trade 👍🏽

  • @constantinbalmus3021
    @constantinbalmus3021 Місяць тому

    Good evening Bryan, may you kindly advice which of the Daikin external VRV unit model can be controlled with the BRC1E73 Remote Controller? I would really appreciate your advice.

  • @anielfernandez1059
    @anielfernandez1059 Місяць тому

    Excellent video guys!, I’m a mechanical engineer visiting your channel for the first time and I just subscribed!

  • @victorsilverman8994
    @victorsilverman8994 Місяць тому

    Good morning sir quick question where is the best place to get these value ranges

  • @Saabjock
    @Saabjock Місяць тому

    Can an R22 system with an original piston-type expander be converted to TXV when a new evaporator is installed?

    • @realSamAndrew
      @realSamAndrew 24 дні тому

      Yes. You just need to make sure you have the right TXV that's made for your air handler and made to work with R22.

  • @peterryanhouse
    @peterryanhouse 2 місяці тому

    Really nice video, from a Florida Daikin rep.

  • @Lemonades1321
    @Lemonades1321 2 місяці тому

    Wow awesome explanation. Thank you.

  • @kathybrewer7985
    @kathybrewer7985 2 місяці тому

    I want to know the order of stacking the reeds in the reed valve... this doesn't show that.

  • @jayryan7473
    @jayryan7473 2 місяці тому

    You're not even going to test the groove by putting a fitting on the end and checking fit?

  • @invertir34
    @invertir34 2 місяці тому

    Super informative video, and these guys seem super trustworthy. Appreciate it!

  • @dhood15277
    @dhood15277 2 місяці тому

    What will pickup R422b? I wonder. I'm converting over but expect future leaks.

  • @tips9999
    @tips9999 2 місяці тому

    Hi

  • @brianmcdermott2430
    @brianmcdermott2430 2 місяці тому

    Great info. Thank you , Craig

  • @jimmymwaba4693
    @jimmymwaba4693 2 місяці тому

    You people are amazing ,the explanation its really understood correctly thanks

  • @francisobey325
    @francisobey325 2 місяці тому

    Good work weldon

  • @lesstech74
    @lesstech74 2 місяці тому

    We will be looking into this. York is now locking us out of optiview equipment.

  • @travismontgomery7261
    @travismontgomery7261 2 місяці тому

    Great video Jeff! Thanks for putting this out here.

  • @soulsoothing6133
    @soulsoothing6133 2 місяці тому

    Why why all this videos don’t show the actual detail wiring

  • @mtz5582
    @mtz5582 2 місяці тому

    I do not understand here...isn't an inverter circuit ment to convert DC to AC...!!!! The scroll compressors I've seen on Heat pumps eg..Toshiba SMMS-i versions are rated with DC Voltage ...Please if coild clarify for me as I am still a rookie ..Thank you

  • @EllipseEnterprise
    @EllipseEnterprise 2 місяці тому

    I have a compressor that's dead. And now it's time to replace it and I really don't know how. It's a Daikin VRV IV. I'm From Namibia 🇳🇦. Can you please help.

  • @HungPham-ff2wj
    @HungPham-ff2wj 2 місяці тому

    Thank anh.anh co the cho em quyen sach do duoc không

  • @m.haslam8495
    @m.haslam8495 3 місяці тому

    I have been working on Dakin VRV Systems for over thirty years. Never had an issue when going into recovery/evacuation mode. It's critical when you want to work on a system like a compressor replacement.

  • @m.haslam8495
    @m.haslam8495 3 місяці тому

    Daikin recommend 15°

  • @hvacwithlife5262
    @hvacwithlife5262 3 місяці тому

    Good

  • @jasonjohnsonHVAC
    @jasonjohnsonHVAC 3 місяці тому

    There is silver on the contact points....be very careful of using an abrasive. If you wear off the silver....the points will get very hot and very fast.

  • @garypoplin4599
    @garypoplin4599 3 місяці тому

    11:29 - On a burnout repair I could justify replacing the liquid receiver, also. How else would you get the burned oil out of the receiver?

  • @prosperdzansi1243
    @prosperdzansi1243 3 місяці тому

    Please your number please I need some part to buy

  • @muhammadaslam3332
    @muhammadaslam3332 3 місяці тому

    Excellent, interesting, informative and fruitful for all those whose are concerns with HAVC. Welldone.

  • @muhammadaslam3332
    @muhammadaslam3332 3 місяці тому

    I am already professional in HVAC, I really appreciate for suchlike informative and fruitful explanation for all those whose are in this field. Welldone. Keep continue likewise.

  • @zabood5375
    @zabood5375 3 місяці тому

    Thank you 🙏🏼

  • @louislopezsr9823
    @louislopezsr9823 3 місяці тому

    How would you go about changing the rotation of open transition wye delta (480v)