Live Incomer Tests at a 3 phase DB - AM2, AM2s, AM2e, 2391 Inspection and Testing Course
This video explains in detail, the requirements for carrying out live electrical testing at the incoming supply of a 3 phase distribution board. This is very useful for apprentice electricians about to take AM2, AM2s, AM2e end point assessments. Also for career CPD for electricians, and for electricians undertaking C&G 2391 Inspection & Testing Course.
Переглядів: 4 858

Відео

S Plan with Solar Thermal Wiring AM2 and AM2s
Переглядів 10 тис.3 роки тому
This video show the operation and typical wiring diagram for an S Plan heating sysytem combined with a Solar Thermal system. Useful for electricians and apprentices. AM2 and AM2s Heating
Safe Isolation in 60 Seconds
Переглядів 2,1 тис.4 роки тому
Electrical Safe Isolation Procedure. AM2 and AM2s Revision
2 way switching in 2 minutes AM2s
Переглядів 6 тис.4 роки тому
This video shows a typical 2 way and intermediate switching arrangement. Useful as a learning aide for apprentices, and a refresher for electricians and AM2s candidates
Steel Conduit Bend, Set and Measure AM2s
Переглядів 148 тис.4 роки тому
This video shows how to Measure Back of Bend, Double Sets and Running Couplers in Steel Conduit. A learning guide for apprentices, refresher for electricians and AM2s Candidates.

КОМЕНТАРІ

  • @lewisclatham3701
    @lewisclatham3701 22 дні тому

    thank you

  • @shovonsfab6581
    @shovonsfab6581 2 місяці тому

    Cool

  • @sohailjanjua123
    @sohailjanjua123 4 місяці тому

    Hi, I like your video. Thanks

  • @tumbleweed116
    @tumbleweed116 4 місяці тому

    Hi, is it a fail if you put a 13 amp fuse in. We was given two 13 Amos and one 3 amp fuse. And no specification.

    • @headsup4sparkies
      @headsup4sparkies 3 місяці тому

      Typically a heating system would need the fuse connection unit (FCU) to be fitted with a 3 Amp fuse. FCU’s come with a 13 Amp fuse as standard

  • @joeraby1370
    @joeraby1370 4 місяці тому

    Hi very helpful video! I have my am2 coming up and just wanted to know at what stage do I carry out the phase rotation test at the main switch? The motor and commando are fine as they can be done with everything closed up and on but from what I've seen the test of the main supply seems to come after RCD and functional but by that stage you would have the board cover back on?

    • @headsup4sparkies
      @headsup4sparkies 3 місяці тому

      My understanding is that the phase sequence test is only carried out at the motor terminals as a functional test.

    • @joeraby1370
      @joeraby1370 3 місяці тому

      @headsup4sparkies thanks for the reply I did also have to do the phase sequence of the main supply. I passed the AM2 anyways

    • @johnwestern
      @johnwestern 3 місяці тому

      @@joeraby1370Thanks for the feedback - good to know. Well done for passing your AM2 👏🏻🏅- Now you’re qualified, your skilled journey begins - keep striving for the best as our industry is ever changing.

  • @snipercwf
    @snipercwf 5 місяців тому

    The best steel conduit tutorial on UA-cam.

  • @mohammadshirifeshki4018
    @mohammadshirifeshki4018 5 місяців тому

    Thank you.

  • @philbayman9964
    @philbayman9964 5 місяців тому

    Another awesome video. Love them. Thank you!

  • @philbayman9964
    @philbayman9964 5 місяців тому

    Awesome video and I love how you do your animations. Brilliant top tips … very helpful! Thank you!

  • @chandsharif3505
    @chandsharif3505 5 місяців тому

    Wow its a virtual learning platform. I hope, there are lots of things can be learnt from your video. And waiting for trunking work how to bend 90, 45, Bridge and so on

  • @azadsmail8
    @azadsmail8 6 місяців тому

    Hi nice vid but I noticed that the highest reading is PEFC 950.3 this one should be doubled and recorded not the PSCC am I right? THANKS

    • @headsup4sparkies
      @headsup4sparkies 6 місяців тому

      Hi … When testing between Line and Neutral (PSCC), the voltage potential is 230V .. we double this to allow for the PSCC between Line conductors as these would have a potential of 400V. The maximum potential to earth (PEFC) is 230 so therefore is not doubled. You only double the highest PSCC value.

  • @alanmarriott9216
    @alanmarriott9216 6 місяців тому

    How did you know where on former the 2nd mark had to go to bend?

    • @headsup4sparkies
      @headsup4sparkies 3 місяці тому

      All measurements when forming conduit, should progress from one end. The conduit is always placed in the former with the “measured end” under the stock. Then each mark should line up on the former at the “point of bend” which is were the conduit and former separate prior to bending. Some people do mark the formers, but this mark is unreliable as it alters depending on which hole you place the stock on. The exception to this is where the mark on the conduit is for the “back of bend”. Then you would follow the instructions as shown in the video.

  • @mykegyver7610
    @mykegyver7610 11 місяців тому

    You should voice an animated movie character. (I am not joking)

  • @captainkidd1811
    @captainkidd1811 11 місяців тому

    Art

  • @nevermind824
    @nevermind824 Рік тому

    Nice tip about scoring the conduit for the thread line.

  • @SigmaPotato327
    @SigmaPotato327 Рік тому

    very nice

  • @lewiswebb1843
    @lewiswebb1843 Рік тому

    Thanks mate, got my am2s this Monday and this is spot on 👍🏻

    • @pvegod1484
      @pvegod1484 7 місяців тому

      Did you pass it mate? I’ve got mine in a couple week bricking it

    • @lewiswebb1843
      @lewiswebb1843 7 місяців тому

      Yea passed 1st time mate 👍🏻 I’ll be honest, if your here looking up videos to pass then you’ll probably be one of the guys that will pass either 1st time or on a return attempt 👍🏻 good luck 🤞🏻

  • @jonathan_ansell
    @jonathan_ansell Рік тому

    christ ! - kill the music and the avatar... then you've got a great video !

  • @monikacieminska5380
    @monikacieminska5380 Рік тому

    Fantastic video. Thank you 👌😀

  • @AndrewBaker-z9r
    @AndrewBaker-z9r Рік тому

    Excellent video as always, thank you.

  • @anowerhsahed1091
    @anowerhsahed1091 Рік тому

    Very good work

  • @Rossisearle
    @Rossisearle Рік тому

    helpful but surely that Zdb your say is Ze because the is the 3 phase dno supply? is zdb would be at 2nd or 3nd distribution circuit ? ASKING

    • @headsup4sparkies
      @headsup4sparkies Рік тому

      Hi … If the board is at the origin of supply - then Zdb and Ze would be the same. Ze recorded on certificate and Zdb recorded on schedule of test results. If there is a sub main between the origin and the board under test .. then Zdb is measured at board with earth disconnected - and Ze from origin recorded on the certificate.

    • @headsup4sparkies
      @headsup4sparkies Рік тому

      The distribution board at the origin supplying the sub main, would also record this supply’s Zs on on it’s own schedule of test results, taken in the same manner but with the earth connected.

    • @headsup4sparkies
      @headsup4sparkies Рік тому

      The board in the video is assumed not to be at the origin of supply … Hope this helps 👍🏻

    • @Rossisearle
      @Rossisearle Рік тому

      ​@@headsup4sparkies right... So like a three phase distribution circuit?

    • @headsup4sparkies
      @headsup4sparkies Рік тому

      Yes … we call them “Sub-Mains” when we distribute the supplies from DNO to distribution boards… and the circuits from there are “final sub-circuits” supplying current using equipment without further distribution.

  • @glenngray3351
    @glenngray3351 Рік тому

    Hi I am having a few issues on identifying the types of wiring and reference method on the Generic schedule of circuit details. Can help or advise please?

    • @headsup4sparkies
      @headsup4sparkies Рік тому

      This can be simple - or complex, depending on the variety of methods employed on the route. You can select the most used method on the route / the method with most detrimental effect .. or so on. The inspector should use engineering judgement to decide … this link to IET - Supporting BS7671 Appendix 4 .. might help electrical.theiet.org/media/1617/appendix-4-of-bs-7671.pdf

  • @detroutspinners9933
    @detroutspinners9933 Рік тому

    Brilliant video, really appreciate the time taken to animate the test sequences as well. Helps to visualise what you’re doing so much better!

    • @headsup4sparkies
      @headsup4sparkies Рік тому

      Thank you 🙏.., I’m glad you found this helpful 😀

  • @sports872
    @sports872 Рік тому

    Enjoyed the video. Would like to see more testing videos if possible.

  • @brianhewitt8618
    @brianhewitt8618 Рік тому

    excellent 👍

  • @ronnymoscoso1212
    @ronnymoscoso1212 Рік тому

    Cual es el modelo y la marca de la dobladora

    • @headsup4sparkies
      @headsup4sparkies Рік тому

      www.google.co.uk/search?q=hilmor+pipe+bender&ie=UTF-8&oe=UTF-8&hl=en-us&client=safari#imgrc=D9SEkwT73edTWM

  • @mario.elektryk
    @mario.elektryk Рік тому

    Very detailed video. 👌 Much appreciated.

  • @alanmarriott9216
    @alanmarriott9216 Рік тому

    Great video but how do you know when doing the 1st and 2nd bends on set where bend starts on former please!?

    • @headsup4sparkies
      @headsup4sparkies Рік тому

      When the conduit is resting in the former, the bend will be at the point where the conduit and former separate (underneath) … I generally place my little finger underneath to “feel” where that point is - and try to get the mark in the conduit at that point.. However - you don’t have to get it exactly right, as you can simply adjust the depth of the set. To add depth, put a little more in each bend. To decrease the depth, take a little out of each bend. Making sure to adjust the existing bend and NOT putting and additional bend in. Some people attempt to “mark” the former on top at the “point of bend” but you often have to change the position of the “stock” to get the measured conduit mark where you need it - as soon as you do this, the mark on the former will now be in the wrong place. Try not to over think it - bending conduit is more of a knack than an exact science. The ability to manipulate the bends neatly is the main skill. Practice makes perfect 👌🏻

  • @Ste2023
    @Ste2023 2 роки тому

    This brings bk memories of browsing.

  • @VM-MV
    @VM-MV 2 роки тому

    thanks!! very useful video!

  • @KeithWilliamMacHendry
    @KeithWilliamMacHendry 2 роки тому

    Excellent detail & instruction, thank you. 🙏🏻

  • @skabbymuff111
    @skabbymuff111 2 роки тому

    Very informative, thank you. Subscribed.

  • @santhaariyarathna2262
    @santhaariyarathna2262 2 роки тому

    Super

  • @MomentsWithBrandon
    @MomentsWithBrandon 2 роки тому

    Loved this vid, super simple and easy to understand compared to others, hope you release more content

  • @gustavocervantes5435
    @gustavocervantes5435 2 роки тому

    Great video

  • @MultiOutdoorman
    @MultiOutdoorman 2 роки тому

    Fabulous presentation, excellent visuals too !.... If i might just contribute ? In my view, the purpose of the solar hot water system is to reduce the need for energy consumption ! The reason I mention this is because the solar needs to operate independently from the boiler . The D.H.W timer should be programmed to schedule a periodic " top up" of the storage tank to overcome any shortcomings of the solar performance during dull weather, and reduce legionella by bringing the water temperature up to a suitable level. My system for instance, runs twice daily to address water & / or heating, based on the Honeywell programmer settings. I also use an S-Plan too, using my combi boiler to provide heat, triggered by the room / cylinder stats leading eventually to the output of the microswitch in the zone valve(s). My kitchen hot tap still runs from the combi directly though ! It has worked a treat for about 6 years and i find the boiler hardly needs to run between May and end of September due output of the 8 square meters of thermal solar panels on our roof. The boiler is still timed to come on but the cylinder stat is usually open by that time so no heat is required. Winter time is another story ... but the boiler still only needs to heat lukewarm water already warmed in the bottom of the cylinder. I often wish i had a second tank in summertime as it often shuts the pump off and stagnates until somebody takes a midday shower. A "destrat" pump and a few controls help to maximise efficiency. Brill animation ... Thanks for sharing.

    • @headsup4sparkies
      @headsup4sparkies 2 роки тому

      Thank you very much for your contribution… this particular system is aimed at the AM2 requirements .. You are clearly experienced with these systems. From my own research, the only thing I can be sure of is that there is no such thing as a “typical” system.

  • @davidshanahan3693
    @davidshanahan3693 2 роки тому

    Excellent tutorial.

  • @Roq-stone
    @Roq-stone 2 роки тому

    Very clear and easy to follow demonstration

  • @moali6196
    @moali6196 2 роки тому

    Great video well informed

  • @17italyman
    @17italyman 2 роки тому

    where you had the running coupler and lock ring can you not just measure say half of the coupler so that when you tighten up the running coupler with the end you wont have any tread showing ?

    • @headsup4sparkies
      @headsup4sparkies 2 роки тому

      I’m afraid not .. the running coupler needs to run from one piece onto the next piece. Therefore it will always leave some thread behind it. The way it’s shown leaves half the thread on the existing piece, and puts half the thread on the new piece. Therefore leaving half the thread exposed on the back of the existing piece, with both ends electrically (earthing) and mechanically secure.

    • @17italyman
      @17italyman 2 роки тому

      @@headsup4sparkies ah yeah makes sense now thank you

    • @17italyman
      @17italyman 2 роки тому

      @@headsup4sparkies also the nipple part you threaded into the box is this something for the am2 that they will provide ?

  • @frog.n.toast2938
    @frog.n.toast2938 2 роки тому

    great video. keep posting

  • @fraserreid719
    @fraserreid719 2 роки тому

    Wasting 4 inch of pipe I would get battered by my tradesman back in the day 😂

  • @highgatehandyman6479
    @highgatehandyman6479 2 роки тому

    Good lesson

  • @2010Mrturk
    @2010Mrturk 2 роки тому

    I’ve hit subscribe but only 4 vids available. Can you do a vid on the DOL pls ?

    • @headsup4sparkies
      @headsup4sparkies 2 роки тому

      Actually working on Contactor and DOL video now .. once it is launched on the other platform it will be on here too

  • @TheGOLDRUSH817
    @TheGOLDRUSH817 2 роки тому

    Where can I find that bending station

    • @headsup4sparkies
      @headsup4sparkies 2 роки тому

      Pretty much any UK electrical wholesaler … here’s a link from a quick search www.toolstop.co.uk/irwin-hilmor-el32-conduit-bending-machine-with-vice-and-20-25-32mm-formers-t113100d-p80043/

  • @jeremykemp3782
    @jeremykemp3782 2 роки тому

    very good

  • @Tom-fu9cr
    @Tom-fu9cr 2 роки тому

    great video. really useful

  • @albertwesleyable
    @albertwesleyable 2 роки тому

    Came for the conduit, stayed for the music 🔥

  • @xiakarimLive
    @xiakarimLive 2 роки тому

    What is the name of this bender? Where can I buy it from?

    • @headsup4sparkies
      @headsup4sparkies 2 роки тому

      There are different names, but I think the most common in the UK is made by Hilmor .. here’s is an example link from a UK wholesaler .. www.tlc-direct.co.uk/Main_Index/Conduit_Steel_Index/Conduit_Bender/index.html?ad_position=&source=adwords&ad_id=414374435730&placement=&kw=&network=g&matchtype=&ad_type=&product_id=&product_partition_id=&version=finalurl_v3&gclid=Cj0KCQiAwqCOBhCdARIsAEPyW9lmDNmlUux6qJls7H9S6mp5RPNTMG9YdOS4OYPuVNj5bmCCiSHvCiQaAn33EALw_wcB