Mainly electrical
Mainly electrical
  • 2 676
  • 8 422 443
25 YEARS IS INSANE 💀
Join this channel start learning for peanuts month .. makes no difference to me whatever you choose to do we'll be just fine .. become a member and get real guidance.. Here's the link ..
ua-cam.com/channels/4bzmBgEUo4fLy3F9q8KhnA.htmljoin
Переглядів: 4 333

Відео

R1+RN ?!?! ☎️
Переглядів 9764 години тому
Join this channel to start learning .. ua-cam.com/channels/4bzmBgEUo4fLy3F9q8KhnA.htmljoin
OPEN PEN 🖊️ ☠️
Переглядів 9949 годин тому
OPEN PEN 🖊️ ☠️

КОМЕНТАРІ

  • @asamitchell7948
    @asamitchell7948 4 години тому

    Seen this before on a block of flats with how the economy 7 was wired wasn't as many flats as you hwithbut luckily we had dual supply CUs so just put henleys in for the neutrals for the economy 7 for 5 flats

  • @sambothebold
    @sambothebold 6 годин тому

    Current carrying capacity of the pyro straight from 100 amp main fuse???

  • @sambothebold
    @sambothebold 7 годин тому

    Not seen a tncs connected in that way before. The original outer sheath earth looks like it’s been connected, could that cause issues if there is a pen fault and the mass of earth and surrounding properties. Could it be a dodgy tncs conversion because somebody found they had a naff Ze and it’s not a true PME on the DNO’s side?

  • @octymocty132
    @octymocty132 7 годин тому

    Might as well wire a perm live its almost there . A whack of the neutral is as more dangerous as a live . And how on hell has it passed time and tiem again back handers .

  • @johnrogowtzow9532
    @johnrogowtzow9532 7 годин тому

    Just brilliant can't beat it.keeps us in business,❤😂😊

  • @sambothebold
    @sambothebold 8 годин тому

    🤦‍♂️

  • @sambothebold
    @sambothebold 8 годин тому

    Neutral taken from “correct” circuit via plug in plug. Live supplied from alternate circuit via the stat. Solution - use the 2 core as a supply/return feed to and from stat using “correct” circuit live from plug 🤷‍♂️

  • @benharris3387
    @benharris3387 8 годин тому

    That's a C3!

  • @sambothebold
    @sambothebold 8 годин тому

    I can’t tell how that earth probe is connected?

    • @Kieran-jq5kk
      @Kieran-jq5kk 3 години тому

      To an upside down socket screw inside the socket face I think, probably so the screws don’t get lost whilst testing.

  • @vladimirdenisov3340
    @vladimirdenisov3340 8 годин тому

    Neutral Earth insulation broken

  • @jamesaddis8726
    @jamesaddis8726 8 годин тому

    Yehaw haha

  • @sambothebold
    @sambothebold 9 годин тому

    Ok, so thinking about this first video a bit. My understanding of this is that it would not be quite the same as loss of PEN on PME. Here when the main switch is off, there is no return to the point at which the earth connection is made from the supply neutral. So the earth cabling doesn’t become live. However the neutral bar becomes live because the line conductor to the A1 terminal on the contactor in the consumer unit exits at A2 and there is no return path to the supply neutral. And so with the main switch off, would that mean that the coil in the consumer unit would not operate because there is no return neutral, and the line conductors of circuits are live supplied from the live neutral bar and neutral conductors through various pieces of equipment ??????. My brain hurts!!!

  • @SBODevelopments
    @SBODevelopments 10 годин тому

    Shouldn’t be tested with load attached. RCD test is to check the breaker not the circuit

  • @SBODevelopments
    @SBODevelopments 10 годин тому

    Just earth the DB end of the SWA ? No point in earthing a coupler on plastic enclosures, this could just add another potential exposed conductor issue?

  • @JohnDundee-el2ro
    @JohnDundee-el2ro 11 годин тому

    Have you ever tried yir steak N chips with mushrooms and a good curry sauce

  • @chrisrice9246
    @chrisrice9246 11 годин тому

    Nice 😂

  • @garethhodson3896
    @garethhodson3896 12 годин тому

    C3 rcd recommended

  • @shlimms
    @shlimms 12 годин тому

    Are you cooking it on a plate?!

  • @gd-bq7em
    @gd-bq7em 12 годин тому

    What was going on here bro, one cable was already tapped in back of socket, was it a cable fault, you manage to sort it or have to disconnect piece of cable causing problem

    • @Mainly_Electrical
      @Mainly_Electrical 12 годин тому

      Cable fault mate .. we'll pop back sometime to get 4 sockets back on

    • @gd-bq7em
      @gd-bq7em 12 годин тому

      @Mainly_Electrical great videos these mate , real world problems, was it a ring circuit, did you just have to split it for time being

  • @Surferant666
    @Surferant666 12 годин тому

    No

  • @adriatikkrasniqi1453
    @adriatikkrasniqi1453 13 годин тому

    Enjoy the meal 🍽️

  • @coralbay00
    @coralbay00 13 годин тому

    Borrowed neutral possibly 🤔

  • @coralbay00
    @coralbay00 13 годин тому

    Was the cu compliant at the time it was installed? Despite it not being a type A rccb/rcd could the hob circuit be moved to the rcd protected side?

    • @Mainly_Electrical
      @Mainly_Electrical 12 годин тому

      Boards fine Daz few C3s there would be. We'll end up swapping it anyway the guys selling it and wants no C3s. Socket no RCD by back door would fail it yes

  • @fergusdangerfield156
    @fergusdangerfield156 13 годин тому

    There certainly are some, not only talented, but consiecious people in the sparky game

  • @drivewasher
    @drivewasher 13 годин тому

    Borrowed neutral very dangerous!

    • @sergepetrov8598
      @sergepetrov8598 11 годин тому

      You have actually explained the problem in two words.

  • @jonhunter8737
    @jonhunter8737 13 годин тому

    Hmm. The old socket can be used to provide power outdoors bullshit. Dear IEE, just say all sockets should be rcd protected. Tester in my company have raised C2s for this gibberish in tower blocks of flats. With a long enough extension cable, ANY socket can provide power outdoors.

  • @mb-electricalservices
    @mb-electricalservices 13 годин тому

    That's clearly a modern kitchen so I would be asking questions about the electrician's ability to produce a satisfactory MEIWC or EIC (depending on the extent of the kitchen upgrade works) whist at the same time, adhering to BS7671. You can't move that circuit it to the RCCB side as that is a type AC and you'll also take the potential load over the maximum allowable for that RCCB. Socket circuit 8 has multiple circuits and circuit 4 has a large crack in the brass terminal block. Consumers tails are not identified by colour either. C3 with a recommendation that the CU be upgraded. This is just my opinion, I welcome constructive criticism.

  • @shaun30-3-mg9zs
    @shaun30-3-mg9zs 14 годин тому

    Outside light of the socket, what a bodge

  • @Jondude0
    @Jondude0 15 годин тому

    Can a pme fault detection device also detect pen faults and vice versa can a pen fault detection device detect pme faults?

  • @bobturner3645
    @bobturner3645 16 годин тому

    Yes it requires additional protection.

  • @garygoodall7234
    @garygoodall7234 16 годин тому

    That's a perfect new build kinda board that installed by a quality electrician 💩🤡😆

  • @jonnyduncan7056
    @jonnyduncan7056 16 годин тому

    It wouldn't take 5 mins to move it over to the RCD protected side!! No code and bill them accordingly..

    • @peterigrenyi9176
      @peterigrenyi9176 15 годин тому

      And you gonna make that RCD type A while u r at it too?

  • @Alex-wz4op
    @Alex-wz4op 16 годин тому

    i hate how dumb you make me feel :D, Top job @mainly heres me thinking im ready to qualify </3

  • @davidslade9851
    @davidslade9851 16 годин тому

    C2 all day long as it could be used to supply outdoor equipment.

  • @timballam3675
    @timballam3675 16 годин тому

    No problem the return is through the earth...

  • @benbarnett5622
    @benbarnett5622 17 годин тому

    Always find em burnt to a crisp aswell 🤣

    • @Mainly_Electrical
      @Mainly_Electrical 16 годин тому

      Yes , This would've gone open circuit eventually , shows the importance of going to the very end of the circuit

  • @arcadia1701e
    @arcadia1701e 17 годин тому

    Yes. Likely to supply outdoor equipment.

  • @MADSPARKS31
    @MADSPARKS31 17 годин тому

    100% C2 for me, as you could potentially plug an extension lead outside. ☠️ ⚡️

  • @G1ZQCArtwork
    @G1ZQCArtwork 17 годин тому

    So in a nutshell, the flats situation is the same scenario as losing the PEN conductor in a PME supply, but only when the contactor is energised.! By redirecting the live supply which triggers the contactor back through the system having lost only the Neutral when the main flats switch is off, which does not switch the contactor live, as it is fed from an earlier position. Phew.!!

  • @MikeB470
    @MikeB470 17 годин тому

    No one would be working on that board between midnight and 7am so no problem 😀

  • @MegaMetinMetin
    @MegaMetinMetin 18 годин тому

    Always ring

  • @markpotter8280
    @markpotter8280 18 годин тому

    4.16 protection against electromagnetic effects where cables enter consumer unit/ distribution board I think also needs to be taken into consideration. Great shout about the neutrals becoming live honestly I doubt I would have spotted that (feeling ashamed)

  • @tonyclark9851
    @tonyclark9851 19 годин тому

    Neutral fault

  • @ImranKhan-cf8gs
    @ImranKhan-cf8gs 20 годин тому

    What’s that silver snake duct