Instrumentation and Controls Training
MOV Limit Switch Maintenance
Using a tumbler map to set the MOV timing. Uses an L120 for demonstration.
Переглядів: 2 879
Відео
Control Valve Actuator Removal
Переглядів 2,7 тис.3 роки тому
Uses the actuator force to disconnect the actuator yoke from the valve yoke boss. Fisher Reverse Acting Actuator. Back To The Wood by Audionautix is licensed under a Creative Commons Attribution 4.0 license. creativecommons.org/licenses/by/4.0/ Artist: audionautix.com/
Excel Data Import with Scrolling Trendline
Переглядів 4383 роки тому
Importing raw data and building trend lines for data analysis.
Coax Connector Protector Kit Bently Nevada
Переглядів 9 тис.3 роки тому
Protective boot installation for coax cables.
Actuator Leak Test
Переглядів 12 тис.3 роки тому
Performing a leak test and locating leaks on a Fisher Spring & Diaphragm Actuator.
Excel Conditional Formatting Probe Test Worksheet
Переглядів 7 тис.4 роки тому
This video gives detailed instruction on how to input the formulas necessary to create an auto-calculating form with pass/fail conditional formatting.
Vibration Probe and Cable Ohm Check, Bently Nevada
Переглядів 64 тис.4 роки тому
This video demonstrates one of the methods used to verify the integrity of a coax cable and probe. It can also be used as a quick method for verifying the extension cable length. This video is in reference to a vibration monitoring system, but can be used for any instrument using a coaxial extension cable.
DeltaV CIOC Rack Assembly Hard Core Henry Style
Переглядів 1,2 тис.4 роки тому
A quick look at the process of assembling a DeltaV Electronically Marshalled CIOC column. One Handed Assembly.
Burner Management Flame Detection Viewing Head
Переглядів 7094 роки тому
This video covers the configuration of gain/filtering parameters for a flame scanner/viewing head.
Reverse Action Control Valve Bench Set Test
Переглядів 21 тис.4 роки тому
How to test the "bench set" and make adjustments to the spring tension of a reverse action spring and diaphragm actuator.
Direct Acting Control Valve Bench Set Adjustment
Переглядів 39 тис.4 роки тому
An example of how to test and adjust the "bench set" of a spring and diaphragm actuator without removing the actuator.
Vibration Monitoring Proximity Probe Working Principle
Переглядів 102 тис.5 років тому
Working Principles of Vibration Measurement, Axial Thrust and Keyphasor.
Proximity Probe Dynamic Test Demonstration TK3
Переглядів 47 тис.5 років тому
Testing a proxy probe using Bently Nevada TK3. If you want to build your own test spreadsheet check out the video link at the end of this video.
Proximity Probe Static Test Demonstration, TK3
Переглядів 67 тис.5 років тому
Incremental Scale Factor Verification. False failure may be indicated over the first 20 mils of the slope. Electrical zeroing the device for the first data point will eliminate this, but is not necessary. Keep in mind; this device is used to measure changes in distance, not the actual distance. This test ensures linear response to object movement. A "How To" video on building a spreadsheet is p...
Multimeter Tutorial
Переглядів 1,5 тис.5 років тому
An explanation of all multimeter functions in reference to a FLUKE brand meter. Including all secondary functions and alternate (hidden) modes of operation.
How to Test and Replace a Multimeter Fuse
Переглядів 3,5 тис.5 років тому
How to Test and Replace a Multimeter Fuse
How about the older style! Mine says installed Moses 6-30-1992
Hi, how are you? Can you please share the excel file?
Are you willing to share your spreadsheet?
Jim, not to be critical, but you have the polarity of your voltmeter backwards. Bently uses a -24VDC power supply and the output of the proximeter is (-) negative. This is critical when understanding the gap voltage is part of diagnosing a machine condition. It is use for radial shaft position (X/Y) and axial position for thrust measurements. Monitoring shaft centerline using DC Gap voltage can tell the analyst alot about shaft position in the bearing. When using a standard proximiter, it is -24VDC and when using the Bently 990 transmitter, it is +24VDC. This is also critical to know because the phase reference on the 990 transmitter is 180 degrees out of phase.
Hi, Great video 👍🏻👍🏻.. I have a doubt. How to calculate ISF %error manually ? Please share the formula. Thank you 😊
@@Somethingspecial897 the LINEST function in excel is good for calculating a deviation from straight line for a set of data points.
Thanks for explaining it in a simple and not missing the technical and application of the Proximity probes, a great help to instrument techs and engineers.
Muchas gracias, excelente explicación .
Gracias, excelente explicación.
Great explanation, very informative Thanks SIr
did it thank you Mr jim
You betcha
Greate information in this video. Is there a link somewhere that I can download your Resistance Check Spreadsheet?
Thank you sir....god bless you....keep posting knowledge.....i really appreciate your hardwork...
How much is this kit?
Hello buddy, can you provide this spreadsheet?
can i use 8 mm probe to measure radial vibration of a 27 mm nickel alloy shaft?
Say, I am using the same valve but I have been given values to start the valve travel at 11 and 13 psi as my full travel. Should I adjust the spring tension first according to these values or should I do on the positioner?
The actuator should have a rated benchset and travel distance. When the control valve assembly was engineered, the actuator specs were selected based on the force required to operate the valve. This test verifies the actuator performs according to the original design. The positioner reduces the error that is a result of mechanical friction.
Thanks
Need some videos of repairs out in the field
Im having issues with a valve currently for leaking by. Hard to find the right kits or someone is not getting the right info for them. Is there a website or something to find the right kits? Based in west texas.
Emerson owns Fisher Valves. From the Emerson website you can find the local business partner as well as drawings.
Simple explanation, but hard to find it. Do you know any supplier I can buy proximeters from? I am located in Brazil.
I don't know. Baker Hughes owns Bently Nevada and they have a global presence. I'm sure there is a local representative. I would check their website.
Hi. Where could I get your excel table ? I would like to get it
Build it in excel. I show all the necessary formulas in one of my videos.
Thank you Sr. I'll do it
Can you provide exell sheet formula
Your email id please send
PLEASE... Can you provide excel sheet? Thank you very much! +++
What is tha input and output radial axial vibration plz answer
I am not sure what you are asking. Can you provide some context?
Like Video.
NICE JOB 👍 WELL EXPLAIN
Simple to the point explanations, thank you.
Thanks sir, it is a very informative vidéo with a clear explanation
where can I get the test sheets?
Can you provide excel sheet? Thank you very much
How does the eddy current generate in the metal? Does the varrying magnatic field has something with it?
You are correct
WOULD YOU LIKE TO SEND THE TALEBA FOR SENSOR CALIBRATION
Good exlonation jim,thanks.
Dear sir. I have two probes with different part number, PN: 86691-08065-0435-25 and PN:86691-09246-0435-25. I only know they are 2.5 m length but i am not sure they can be used interchangeably. Is it possible? What are their differences?
I don't have that manual, so I cannot say for certain. From a performance standpoint it should work. Difference will be in the custom features. Such as mounting options, length of armored jacket, etc..
Very good explanation, now I have a better understanding of Proximity probes.
ua-cam.com/video/qd2-NfglGfw/v-deo.htmlsi=pr6vKxgK2ZchdIKA
Can you provide excel sheet? Thank you very much
Jim, where do you get the values for Peak to Peak travel and Measured Value?
I posted videos explaining how to perform the dynamic and static tests.
hello, when i connect the power supply 24VDC positive to the com and negative to the Vt(-24 VDC) it creates an alarm on the power supply and shut down the power supply. Please advice on wiring?
Power to com and -24. Output signal to out.
Thank you very much for the information, although I have a question, at minute 2:24 you put the value of 1 in the voltage column. why 1? What shouldn't be 10mil*200mV= 2V?
The response rate of 200mV / mil is only valid within the range of linearity. 0-10 mils is outside this range.
Best video on youtube!
How tight should the jams be tightened. What are the risks of not setting the jam nuts?
The jams keep the connection block in place In most applications, the feedback arm connects to the block. In some cases, even a slight rotation can create feedback error or loss of position indication.
What do you supply proximity power with? What kind of lines?
Excellent work 👍
Hi thanks for the video ! We bought a couple of these fisher control valves and we noticed that they don't all have the same bench set values, what's the reason for this ? I also noticed that you did your bench set from 9 to 15 psi, so when will the valve start to move? Is it 9 psi or 3 psi?
The bench set is engineered to operate the valve based on the process stream and will determine the pressure required to open the valve.
@@jimdiggins101 thanks so much for the Response! Atleast now I know that I didn't buy the wrong things 😃
Dear Jim thanks for video, I only have two questions, at the end we obtained values that were out of tolerance, right? And this was probably because we use other extension cable model, right? In advance thanks for your response! And good job!! 🤘
Correct. Incorrect length is the most common cause of error
Excellent!Can you provide excel sheet? Thank you very much
Thank you for your video. I have a confused question " Can vibration monitoring module supply +24VDC and -24VDC ?"
Are you referring to the proximitor card on the bently nevada monitoring rack?
@@jimdiggins101 Yes, Sir
interesting...
I seen some valve bodies have a line on it instead of a flow arrow? Is the line an indication for flow?
Some have a line on the body that has a downward angle, which represents the flow path through a globe valve. That may be what you are referring to. This alone does not indicate flow however, but for general service, you install with the angled downward part facing up stream so the flow enters below the plug and flows up through the port.
@@jimdiggins101 thanks for the info.
Excellent
Thanks