Caught in the dark... Shoplifter
Переглядів 1,4 тис.10 років тому
When the power fails, we won't! rjcontrol.com
Anatomy of an Automatic Transfer Switch ASCO
Переглядів 180 тис.11 років тому
Let R&J Control take the mystery out of transfer switches. Here we explain the main components of an ASCO transfer switch and the sequence of events during a power loss. This is actually our own system that powers our building in the event of a power failure.
Home Generator Transfer Test
Переглядів 45 тис.11 років тому
See an example of a typical transfer test of a Home Generator System. Here you will see the sequence of events during a routine test of of a Briggs & Stratton automatic generator system
GENPLUS trailer FINAL 10 10 12
Переглядів 18911 років тому
GENPLUS trailer FINAL 10 10 12
R&J Control OfficeTour
Переглядів 1,1 тис.11 років тому
R&J Control OfficeTour
For Sale 2005 Ford F350
Переглядів 24011 років тому
2WD Crew Cab with performance upgrades that increase both power and mileage. I look forward to answering any questions regarding this vehicle. Truck is located in Dover, NJ 07801
Gen+ Generator Monitoring/Starting System - REMOTELY
Переглядів 89612 років тому
Gen Generator Monitoring/Starting System - REMOTELY
RJControl GenPlus FINAL042312
Переглядів 33712 років тому
RJControl GenPlus FINAL042312
Fire Inspector Seminar - Re: Emergency Generators
Переглядів 33013 років тому
The atached slideshow was used as a training tool for local inspectors. It's an overview of common failures of most neglected generator systems
Schurman Div 1 Championship
Переглядів 21413 років тому
Matt Schurman acceptance speeches for both "Sportsman of the Year" and "Division 1 - Super Gas Champion" for the 2010 season.
GEN+.2
Переглядів 33514 років тому
Created on June 24, 2010 using FlipShare.
Generator Service - Repairs needed
Переглядів 49514 років тому
Initial evaluation of generator system that needs extensive repairs - More videos to follow as unit is restored to factory spec.
Onan RV for Dog Groomer www.rjcontrol.com
Переглядів 4,1 тис.14 років тому
Onan RV generator being installed and tested in a Dog Grooming Van after extensive repairs were completed
R&J Control - Emergency Generators
Переглядів 36114 років тому
R&J Control - Emergency Generators

КОМЕНТАРІ

  • @SirIssac80
    @SirIssac80 10 місяців тому

    Thanks for the help!

  • @Ingveyisnthome
    @Ingveyisnthome Рік тому

    Very Nice explanation Thanks a ton your right folks buy these and never think about them.

  • @retiredperson4054
    @retiredperson4054 Рік тому

    Nice video! I am a bit confused -- I have looked at several videos showing 400Amp Generac ATS installs... The confusion is this -- Most of what I see is that there are installs that SHOW 4 "Hots" coming into the ATS and taken up to the TOP of the Transfer Switch -- My confusion is WHY would there be 4 Hots coming from a Meter and not just 2 Hots if the Meter is supplied with 400/320 Continuous from the Transformer through the meter? Question -- Are FOUR Hots needed from the meter every time? (I am only concerned with SINGLE PHASE 400/320A 120/240V system here) Can you explain this for me?

  • @RobertBranch-FL
    @RobertBranch-FL Рік тому

    Thank you very much!

  • @kcook8119
    @kcook8119 2 роки тому

    Can't get more of a elementary level explanation than this.

  • @rickbourdier1408
    @rickbourdier1408 2 роки тому

    Thanks. The generator would be set to Auto for this test, correct? It's a Generac.

  • @michalsz2
    @michalsz2 2 роки тому

    I flipped the switch and Generator kicked in after 10 seconds, (everything worked great) But after I turned the switch back on, Generator never shuts itself, I had to kill it manually. Any ideas?

    • @charlesmason6928
      @charlesmason6928 2 роки тому

      Check trouble codes

    • @nsbyband5239
      @nsbyband5239 Рік тому

      U turned it back on to fast it tricked the system make sure to turn it back off wait few minutes then back on. And after 5 minutes if generator is still running u need service

    • @billyfowler9423
      @billyfowler9423 Рік тому

      Depending on the generator it may run for up to 30 minutes.

  • @mikev.892
    @mikev.892 2 роки тому

    After watching SEVERAL videos this is by far the best and the simplest way to test your generator.

  • @drpoundsign
    @drpoundsign 2 роки тому

    My inherited Generac stopped testing itself on Saturdays a few years ago. The maintenance guys (who I had change the oil each year) insisted it was OK. But, of course, when I turn off the main...Nothing happens! It starts manually, but does not transfer Question: if I start it manually, and then throw the main switch in the panel, should it switch to generator current?? My "current" situation IS: I have a brownout condition caused by water in the main conduit/meter. I had an electrician diagnose this yesterday. The fridge compressor makes a dying noise when starting (I've unplugged it) some overhead lights are brown, and like, TWO watts, while the one in the study is like an arc lamp!! The HVAC transformer got blown again, along with other things.

  • @afugezi8114
    @afugezi8114 3 роки тому

    Great video, thanks 🙏🏼

  • @MrUsaer
    @MrUsaer 3 роки тому

    Thanks for the video. Gave me just enough confidence to "throw the switch". Is the ONLY function of flipping the switch limited to just turning off the utility power? And once that is done the ATS takes over? The reason I ask is that. I am constantly getting ATS Communication Failure WARNING messages. Sometimes the warnings last a few minutes or sometimes a few hours before I get a "warning cleared" message. This will usually happen between 1 time and 5 times a day. My Kohler installer put in a new control board, but I continue to get the Warnings.... but NOT getting the "Cleared" messages anymore since the new board was installed. I did as you did in the video and everything worked. (Normally my gen would not automatically go on or off when there was an ATS Warning message showing. So now I am wondering if the ATS is actually working now with the new board and maybe the "warning" messages are somehow just "false alarms". So if the ONLY function of flipping the switch in the video is to turn off the utility power, then maybe my ATS is working regardless of still having an ATS COMMNICATION Warning.

  • @franciscoorozco3493
    @franciscoorozco3493 3 роки тому

    Omg thank you so much!!!!! I work at a retirement home and I just got promoted and I have to do this every month and I was kind a nervous on how to do it but this video guided me and I DID IT!!!

  • @jorgealva1820
    @jorgealva1820 4 роки тому

    Does the ATS model J07ATSB30600N5XP require DC to operate the relays?

  • @marktheamerican4162
    @marktheamerican4162 4 роки тому

    Thank you , a very clear explanation !

  • @tyhkee1
    @tyhkee1 5 років тому

    I see a utility phase issue going on there. Why is it A-C-B and not A-B-C? Utility company feeding the building load in reverse.

    • @SkepticforTruth
      @SkepticforTruth 4 роки тому

      Ansi requires the high leg to be installed in c phase, nec wants it in b phase per 408.3 (E), also should be marked orange per 110.15.

    • @GypsyMoFoJoe
      @GypsyMoFoJoe 5 місяців тому

      @@SkepticforTruth I guess orange tape was back ordered?

  • @RJSteed
    @RJSteed 6 років тому

    I have a 17kw gen, 70 amp output connected to a 200 amp transfer switch. It does run the ac unit and many of the lights. I have not yet had the opportunity to do more test, as I am waiting for propane. Does this seem right?

  • @JulesBartow
    @JulesBartow 6 років тому

    I hate triacs because they don't click like a relay. The best is hearing the clunk of a contactor --reminds me of a 155mm artillery shell loading into the breech just before I decimated a fishing village and a herd of water buffalo in the Mekong Delta. You failed to take the mystery out of transfer switches. There is no schematic, no wiring diagram, no load calculations for AWG selection, no overcurrent protection mentioned, no demonstration of a black out or brown out and the generator starting up, and no mention of a UPS for some circuits until the generator comes up to speed. Could you please show your system actually operating and put the microphone right up to that Schneider Electric big ass relay to prove the French aren't totally useless. We should be able to hear clunks and see the indications which Line is being used.

    • @canadajim
      @canadajim 3 роки тому

      There are no overcurrent protections in an ATS.

    • @bobbygene8274
      @bobbygene8274 Місяць тому

      It is called familiarization for a reason. What you ask is technical data. Buy your own switch and find out.

  • @jogog9204
    @jogog9204 7 років тому

    You guys look alike is the older fello your father?

  • @thebrewpedia9093
    @thebrewpedia9093 7 років тому

    Is that system energized? I'm judging by the control lights on, that it is. Definitely do not want to open any energized equipment without proper PPE.

    • @Icybearg
      @Icybearg 4 роки тому

      Of course that was only for a demo...but definitely when working around live wiring and panels PPE no doubt!

  • @pastorurbina5394
    @pastorurbina5394 7 років тому

    Good morning, friend, install a power plant to a swich transfer series H 300 series to feed 57 houses and I would like to know how do I control the power input by means of a frequency or a wifi antenna. Taking into account that I will install a circuit in each house with contactors and relay to control. But I need to do it via frequency or wifi, since wiring is very expensive. If you can help me I appreciate it.

    • @bobbygene8274
      @bobbygene8274 Місяць тому

      Control wiring is the LEAST of your concerns.

  • @MrTheHillfolk
    @MrTheHillfolk 8 років тому

    Love me some asco 300 controllers. In my 20 years I've replaced like 4 controllers. Cutler hammer? Those blow out all the time. I've probably changed like 30 in the past 5 years.

    • @Icybearg
      @Icybearg 7 років тому

      meaning cutler hammer is "PON"

    • @docalexander2853
      @docalexander2853 2 роки тому

      I have an old ASCO switch that was never used because it was a backup for the I-30 Turnpike. The Generator's output was 37.5 Amps. If it is worth anything, how much do you think it is worth? Thanks

    • @MrTheHillfolk
      @MrTheHillfolk 2 роки тому

      @@docalexander2853 depends , they could have used any size switch. It could be a 50 amp switch or maybe a 100. There should be a model tag that has the particulars. Used stuff can range in price but it's usually worth at least 1/2-2/3 of the original cost

  • @davetaylor2449
    @davetaylor2449 8 років тому

    Can you hear that, ka-ching, ka-ching, ka-ching, just wait till you see that bill.

  • @steveschrader9250
    @steveschrader9250 9 років тому

    Shouldn't the wild leg be on B phase

    • @TheSethnichols36
      @TheSethnichols36 5 років тому

      What is a wild leg

    • @tyhkee1
      @tyhkee1 5 років тому

      I see black, blue and red. Wild leg is orange

    • @kcook8119
      @kcook8119 2 роки тому

      Phase rotation test will show how the power company delivered to the customer.

    • @steveschrader9250
      @steveschrader9250 2 роки тому

      I'm seeing wild leg is being phased out here in Kansas city. But typically it's on B phase, and it is marked orange.

    • @kcook8119
      @kcook8119 2 роки тому

      @@steveschrader9250 The common color code in GA is Black, orange, yellow but depending on the electrician that wired it could also be blk, red, blue.

  • @alaaelbadawi2353
    @alaaelbadawi2353 10 років тому

    hi , i was just wounding if the arrangements of the phases were right. is it suppose to be black red blue for low voltage. ? and phases in the ATS is arranged black blue red. i don't know if the color code differs from a state to state.I loved your video as a great intro to ATSs, however it would be great if you teach me something i don't know about the code arrangement. Thank you

    • @wessleyrutherford8224
      @wessleyrutherford8224 9 років тому

      Site phasing is always dictated by the incoming commercial phasing. "Normally" Black Red Blue for a A-B-C rotation, but if the commercial coming in is not in an A-B-C configuration, you make the generator phasing match the incoming phasing, by changing any two of the three phase leads location. Which can sometimes give you what you see on the video.

  • @EpicWinNY
    @EpicWinNY 10 років тому

    I stole about 300 ft of 4 Ort and sold it for crack

  • @RJCONTROL
    @RJCONTROL 11 років тому

    The transfer switch does exactly that... It "transfers" between utility power and generator power based on need. It can be rated as Service Entrance so that it can be the primary disconnect on the incoming utility service. The generator itself, should always have an output breaker on the unit and sized appropriately to the system's rating.

  • @ChapelHillElectric
    @ChapelHillElectric 11 років тому

    Does the ATS serve as a disconnect for the utility power to the building? Do you need another disconnect mounted for the generator? Is their one built in to the generator itself?

    • @kcook8119
      @kcook8119 2 роки тому

      The generator will have a breaker and utility will have a breaker to isolate power from the ATS either way.